BEKA BA474ND Скачать руководство пользователя страница 28

26

10.4.4  Alarm selection:  ALr1  or  ALr2

As shown in Fig 12, each of the two alarms has an
identical set of sub-functions enabling each alarm to
be independently conditioned.  ‘ALr1 provides access
to the alarm 1 sub-functions and ‘ALr2’ provides
access to the alarm 2 sub-functions.   The following
sections 10.4.5 to 10.4.11 describe each of these
sub-functions in detail

10.4.5  Alarm enable:  EnbL

This sub-function allows the alarm to be enabled or
disabled without altering any of the alarm
parameters.  To check or change the sub-function
select 'EnbL' from the alarm sub-menu using the 

or 

 button and press 

P

 which will reveal the current

setting.  The function can be changed by pressing the

 or 

 button followed by the 

E

 button to enter the

selection and return to the ‘EnbL’ prompt in the alarm
menu.

10.4.6  Setpoint adjustment:   SP1

The setpoint of each alarm relates to the transmitter
digital display and may be positioned anywhere in the
transmitter display range.

To adjust the setpoint select 'SP1' from the alarm
menu and press 

P

 which will reveal the existing alarm

setpoint with one digit flashing.  The flashing digit
may be adjusted using the 

 or 

 push button and

the 

P

 button to move control to the next digit.  When

the required setpoint has been entered press 

E

 

to

enter the new setpoint and return to the ‘SP1’ prompt
in the alarm menu.

Note:

 If, when configured for a voltage or resistance

input the displayed decimal point has been set to
autorange, it may be necessary to manually position
the decimal point before adjusting ‘SP1’ or ‘SP2’.
This can be achieved by repeatedly operating the 

P

button until the activated decimal point flashes, the
decimal point can then be positioned using either the

 or 

 button.   Pressing the 

P

 button again will

return control to one of the digits.

10.4.7  Alarm function:   Hi.Lo

Each alarm can be independently conditioned as a
high or low alarm.   To check or change the alarm
function select 'Hi.Lo' from the alarm menu using the

 or 

 button and press 

P

 to reveal the current

setting.  The function may be changed by pressing
the 

 or 

 button, pressing the 

E

 button will enter

the setting and return the display to the ‘Hi.Lo’ prompt
in the alarm menu.

10.4.8  Alarm output status:   no.nC

This sub-function allows the alarm output to be open
or closed in the non-alarm condition.  When deciding
which is required, care must be taken to ensure that
the alarm output is fail safe.    See Fig 11.

‘no’

Alarm output open in non-alarm condition

‘nC’ Alarm output closed in non-alarm condition

CAUTION

When the transmitter supply is
removed both alarm outputs will open
irrespective of conditioning.  Therefore
for fail safe operation both alarm
outputs should be conditioned to be
open in the alarm condition.

To check or change the alarm output status select
'no.nC' from the alarm menu using the 

 or 

 button

and press 

P

 to reveal the current setting.  The

function can be changed by pressing the 

 or 

button followed by the 

E

 button to enter the setting

and return to the ‘no.nC’ prompt in the alarm menu.

10.4.9  Hysteresis:   HStr

Hysteresis is shown in the same units as the
transmitter digital display.
To adjust the hysteresis, select 'HStr' from the alarm
menu using the 

 or 

 button and press 

P

 which will

reveal the existing figure with one digit flashing.  The
flashing digit can be adjusted using the 

 or 

 push

buttons, and the 

P

 button to move control to the next

digit.  When the required hysteresis has been
entered, press 

E

 

to enter the new setting and return

to the ‘HStr’ prompt in the alarm menu.

e.g.  A BA474ND transmitter with a high alarm set at
90.0 and hysteresis of 10.0 will perform as follows:

The alarm will be activated when the display
equals or exceeds 90.0, but will not be
deactivated until the display falls below 80.0.

Note:

 If, when configured for a voltage or resistance

input the displayed decimal point has been set to
autorange, it may be necessary to manually position
the decimal point before adjusting ‘HStr’.  This can be
achieved by repeatedly operating the 

P

 button until

the activated decimal point flashes, the decimal point
can then be positioned using either the 

 or 

button.   Pressing the 

P

 button again will return

control to one of the digits.

Содержание BA474ND

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA474ND...

Страница 2: ...fice Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB...

Страница 3: ...Issue 7 4 th March 2014 BA474ND Type n certified field mounting indicating temperature transmitter with intrinsically safe sensor input Issue 7...

Страница 4: ...f bargraph display bAr 7 2 9 Access code CodE 7 2 10 Resistance thermometer type r tYPE 7 2 11 Decimal point position dP 7 2 12 Lower input display in Lo 7 2 13 Higher input display in Hi 7 3 Default...

Страница 5: ...ormation for IECEx installations and for use in combustible dust atmospheres is contained in appendices to this manual The transmitter is HART Registered and is compliant with HART protocol standard r...

Страница 6: ...used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450oC T2 300oC T3 200oC T4 135oC T5 100oC At an ambient temperature between 20 and...

Страница 7: ...intrinsic safety approval the sensor may be installed in Zone 0 or 1 BEKA Application Guide AG310 provides comprehensive information on the design installation and maintenance of Extra low voltage dc...

Страница 8: ...Zener barrier or galvanic isolator is required thus reducing complexity and cost There are four requirements when designing a BA474ND loop 1 The output voltage of the supply powering the transmitter...

Страница 9: ...terminal should be connected to a local earth The BA474ND enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries The BA474ND liquid crystal...

Страница 10: ...lly safe and non intrinsically safe terminals within the transmitter terminal enclosure Conductors of intrinsically safe circuits and non intrinsically safe circuits should not be contained in the sam...

Страница 11: ...ected by an access code the first parameter InPut will be displayed If the transmitter is protected by an access code CodE will be displayed first Pressing P will allow the four digit security code to...

Страница 12: ...ts low or high display resolution See section 7 2 4 Transmitter Summary display of function FAuLt Sensor fault analogue indication Selects 1 of 3 under over range output currents to indicate that a se...

Страница 13: ...rmocouple has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 7 2 3 Units of digital display dEG The transmitter digital display may be in one of...

Страница 14: ...ss P which will display the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depen...

Страница 15: ...return control to one of the digits 7 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain access N...

Страница 16: ...oned using either the or button Pressing the P button again will return control to one of the digits 7 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter...

Страница 17: ...15...

Страница 18: ...16...

Страница 19: ...17...

Страница 20: ...on site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to...

Страница 21: ...r the function which enables the type of resistance thermometer to be selected The transmitter will display the existing type of resistance thermometer using the or button select 100r which is the req...

Страница 22: ...P to enter the bArLo sub function which will reveal the existing digital display at which the bargraph starts Set the display to 0100 0 using the or button to adjust the flashing digit and the P butto...

Страница 23: ...raph flashing and 4 20mA fixed at 3 6 3 8 or 21 0mA Sensor fault detection has been activated Sensor and input wiring 9 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENA...

Страница 24: ...Scale and tag marking BA474ND indicating temperature transmitters are fitted with a blank escutcheon around the liquid crystal display If specified when the transmitter is ordered this can be supplie...

Страница 25: ...he outputs are polarised and current will only flow in one direction Terminals 8 and 10 should be connected to the positive side of the supply Ron 8ohms 1 2V Roff greater than 180k Note Because of the...

Страница 26: ...functions Display Description of function ALr1 Alarm 1 ALr2 Alarm 2 The two functions each contain seven identical sub functions one set for configuration alarm 1 and the other for configuration alar...

Страница 27: ...25...

Страница 28: ...reveal the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 10 4 8 Alarm...

Страница 29: ...xists the alarm will be reactivated 10 4 12 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA474ND transmitter is in the operat...

Страница 30: ...to be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transm...

Страница 31: ...nput input terminals 1 2 3 4 is galvanically isolated and intrinsically safe Ex iaD When the transmitter is installed in a Zone 22 dust hazardous area this allows the transmitter sensor input terminal...

Страница 32: ...d and that it is free from foreign bodies Use as a Ex nA Ex tD instrument with an intrinsically safe Ex ia sensor input Transmitter in Zone 22 sensor in Zone 20 or 21 Maintenance may only be performed...

Страница 33: ...x gas and dust certification of the transmitter are identical to the ATEX certifications described in the main section and in Appendix 1 of this instruction manual Like the ATEX certificate the IECEx...

Отзывы: