8.   CONFIGURATION EXAMPLE

In this example a BA474ND indicating temperature
transmitter is required to display temperature in
degrees Celsius with maximum resolution. The
temperature sensor is a 3 wire Pt100 resistance
thermometer and the 4/20mA transmitter output is
required to representing –10 to +250

o

C. .  A left hand

justified bargraph representing 100.0 to 200.0

o

C is

required. Resistance thermometer failure is to be
indicated by an overrange output current of 21.0mA.
After configuration access to the configuration menu
is to be protected by code 1209.

Configuration is performed using the four push
buttons which are located behind the removable
switch cover below the digital display – see Fig 7.
The BA474ND can be supplied with factory fitted
external push buttons if frequent adjustments are
required.

The transmitter configuration may also be performed
via HART

 

communication from a local or remote

configurator.  The HART

 

communication protocol

includes additional functions allowing the complete
temperature loop, including the temperature sensor
and the transmitter load, to be calibrated, see the
BEKA HART

 Interface Guide which may be

downloaded from www.beka.co.uk/manuals

Step 

1

Access the configuration menu &
select the type of input.

See: Fig 7 and section 7.2.1
New BA474ND indicating temperature
transmitters are supplied conditioned
with default access code ‘0000’ that
allows unrestricted access to the
configuration menu.

To enter the configuration menu press
buttons 

P

 and 

E

 simultaneously which

will cause the first prompt ‘InPut’ to be
displayed.   Press 

P

 to enter the function

and the transmitter will display the
current type of input.   To configure the
transmitter to operate with a three wire
resistance thermometer press the 

 or

 button until ‘3rtd’ is displayed.  When

selected press 

E

 to enter the selection

and return to the ‘InPut’ prompt in the
configuration menu.

Step 2

Select resistance thermometer type

See:  Fig 7 and section 7.2.10
Using the 

 or 

 button select the

‘r,tYPE’ prompt from the configuration
menu and press 

P

 to enter the function

which enables the type of resistance
thermometer to be selected. The
transmitter will display the existing type
of resistance thermometer, using the 

or 

 button select ‘100r’ which is the

required Pt100 sensor. Enter the
selection by pressing the 

E

 button that

will return the display to the ‘r.tYPE’
prompt in the configuration menu.

Step 3

Select units of digital display

See: Fig 7 and section 7.2.3
Using the 

 or 

 button select ‘dEG’

from the configuration menu and press 

P

to enter the function which enables the
digital display units of measurement to
be selected. Using the 

 or 

 button

scroll through the options and select ‘ºC’
which represents degrees Celsius.
Press 

E

 to enter the selection and return

the transmitter display to the ‘dEG’
prompt in the configuration menu.

Step 4

Select display resolution

See: Fig 7 and section 7.2.4
Using the 

 or 

 button select ‘rESn’

from the configuration menu and press 

P

to enter the function which determines
the resolution of the digital display.
Using the 

 or 

 button select ‘Hi’ to

provide the required 0.1 resolution
display.  Press 

E

 to enter this selection

and return the display to the ‘rESn’
prompt in the configuration menu.

Step 5

Sensor fault detection

See: Fig 7 and section 7.2.6
Using the 

 or 

 button select ‘FAuLt’,

the input sensor fault detection function,
from the configuration menu and press

P

.  Using the 

 or 

 button scroll

through the options and select ‘uP 21’
which forces the output current to
21.0mA when a sensor failure is
detected.   Enter the selection by
pressing 

E

 which will also return the

transmitter display to the ‘FAuLt’ prompt
in the configuration menu.

Step 6

Configuration of 4/20mA output

See: Fig 7 and section 7.2.7
The BA474ND transmitter input at which
the transmitter output current is 4mA
and 20mA is defined by the ‘CAL’
function which contains two sub-
functions.
Using the 

 or 

 button select ‘CAL’

from the configuration menu and press 

P

which will show the ‘ZEro’ sub-function
prompt.  Press 

P

 again to enter this sub-

function, which will reveal the existing
input at which the transmitter output
current is 4mA.   Adjust the display to
the required –0010.0 using the 

 or 

button to adjust the flashing digit and the

P

 button to move control to the next

digit.   A negative display is achieved by

Содержание BA474ND

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA474ND...

Страница 2: ...fice Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB...

Страница 3: ...Issue 7 4 th March 2014 BA474ND Type n certified field mounting indicating temperature transmitter with intrinsically safe sensor input Issue 7...

Страница 4: ...f bargraph display bAr 7 2 9 Access code CodE 7 2 10 Resistance thermometer type r tYPE 7 2 11 Decimal point position dP 7 2 12 Lower input display in Lo 7 2 13 Higher input display in Hi 7 3 Default...

Страница 5: ...ormation for IECEx installations and for use in combustible dust atmospheres is contained in appendices to this manual The transmitter is HART Registered and is compliant with HART protocol standard r...

Страница 6: ...used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450oC T2 300oC T3 200oC T4 135oC T5 100oC At an ambient temperature between 20 and...

Страница 7: ...intrinsic safety approval the sensor may be installed in Zone 0 or 1 BEKA Application Guide AG310 provides comprehensive information on the design installation and maintenance of Extra low voltage dc...

Страница 8: ...Zener barrier or galvanic isolator is required thus reducing complexity and cost There are four requirements when designing a BA474ND loop 1 The output voltage of the supply powering the transmitter...

Страница 9: ...terminal should be connected to a local earth The BA474ND enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries The BA474ND liquid crystal...

Страница 10: ...lly safe and non intrinsically safe terminals within the transmitter terminal enclosure Conductors of intrinsically safe circuits and non intrinsically safe circuits should not be contained in the sam...

Страница 11: ...ected by an access code the first parameter InPut will be displayed If the transmitter is protected by an access code CodE will be displayed first Pressing P will allow the four digit security code to...

Страница 12: ...ts low or high display resolution See section 7 2 4 Transmitter Summary display of function FAuLt Sensor fault analogue indication Selects 1 of 3 under over range output currents to indicate that a se...

Страница 13: ...rmocouple has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 7 2 3 Units of digital display dEG The transmitter digital display may be in one of...

Страница 14: ...ss P which will display the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depen...

Страница 15: ...return control to one of the digits 7 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain access N...

Страница 16: ...oned using either the or button Pressing the P button again will return control to one of the digits 7 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter...

Страница 17: ...15...

Страница 18: ...16...

Страница 19: ...17...

Страница 20: ...on site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to...

Страница 21: ...r the function which enables the type of resistance thermometer to be selected The transmitter will display the existing type of resistance thermometer using the or button select 100r which is the req...

Страница 22: ...P to enter the bArLo sub function which will reveal the existing digital display at which the bargraph starts Set the display to 0100 0 using the or button to adjust the flashing digit and the P butto...

Страница 23: ...raph flashing and 4 20mA fixed at 3 6 3 8 or 21 0mA Sensor fault detection has been activated Sensor and input wiring 9 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENA...

Страница 24: ...Scale and tag marking BA474ND indicating temperature transmitters are fitted with a blank escutcheon around the liquid crystal display If specified when the transmitter is ordered this can be supplie...

Страница 25: ...he outputs are polarised and current will only flow in one direction Terminals 8 and 10 should be connected to the positive side of the supply Ron 8ohms 1 2V Roff greater than 180k Note Because of the...

Страница 26: ...functions Display Description of function ALr1 Alarm 1 ALr2 Alarm 2 The two functions each contain seven identical sub functions one set for configuration alarm 1 and the other for configuration alar...

Страница 27: ...25...

Страница 28: ...reveal the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 10 4 8 Alarm...

Страница 29: ...xists the alarm will be reactivated 10 4 12 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA474ND transmitter is in the operat...

Страница 30: ...to be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transm...

Страница 31: ...nput input terminals 1 2 3 4 is galvanically isolated and intrinsically safe Ex iaD When the transmitter is installed in a Zone 22 dust hazardous area this allows the transmitter sensor input terminal...

Страница 32: ...d and that it is free from foreign bodies Use as a Ex nA Ex tD instrument with an intrinsically safe Ex ia sensor input Transmitter in Zone 22 sensor in Zone 20 or 21 Maintenance may only be performed...

Страница 33: ...x gas and dust certification of the transmitter are identical to the ATEX certifications described in the main section and in Appendix 1 of this instruction manual Like the ATEX certificate the IECEx...

Отзывы: