BEKA BA474ND Скачать руководство пользователя страница 11

9

7. CONFIGURATION

The BA474ND Indicating Temperature Transmitter
may be configured and calibrated via HART

  digital

communication, or configuration may be performed
using the menu accessed via the four push buttons
located behind  the  instrument  switch  cover, see
Fig 5.  When frequent adjustments are required the
transmitter can be supplied with a keypad mounted
on the outside of this cover.
Configuration and calibration via HART

 may be

performed using a portable configurator connected to
the BA474ND test pillars, which are located adjacent
to terminals 5 & 6, or to any other point in the 4/20mA
loop.  Alternatively, proprietary configuration software
installed on a personal computer may be used.  In
addition to the configuration functions available via
the transmitter push buttons, HART

 

communication

enables loop calibration and custom linearisation to
be performed, see the BA47XBA67X Indicating
Temperature Transmitter HART

 Interface Guide

which may be downloaded from
www.beka.co.uk/manuals
.

7.1  Configuration menu

Throughout this manual the four BA474ND push
buttons are identified 

P  E

   

 

 and legends

displayed by the transmitter are shown within
inverted commas  e.g. ‘CAL’ and ‘dEG’.    Section
7.1.2 contains a summary of each configuration
function including a cross reference to a more
detailed description.

The functions contained in the configuration menu
vary depending upon the transmitter input selected,
see Figs 6, 7 & 8.

When the transmitter is being configured, the
transmitter 4/20mA output current is locked at the
value prior to entering the configuration menu.

When the optional alarms are fitted additional
functions are added to the configuration menu which
are described in section 10.4.

7.1.1  Access

Access to the configuration menu is obtained by
operating the 

P

 and 

E

 buttons simultaneously.  If the

transmitter is not protected by an access code the
first parameter 'InPut’ will be displayed.  If the
transmitter is protected by an access code, ‘CodE’
will be displayed first.  Pressing 

P

 will allow the four

digit security code to be entered digit by digit using
the 

 or 

 button to adjust the flashing digit and 

P

 to

move control to the next digit.  When the correct code
has been entered, pressing 

E

 will cause the first

parameter ‘InPut’ to be displayed.    If an incorrect
code is entered, or no button is pressed for ten
seconds, the transmitter will automatically return to
the operating mode.
If the transmitter displays ‘LoC’ when the 

P

 and 

E

buttons are operated simultaneously, the transmitter
push buttons have been locked by a HART

command, see the BA47XBA67X Indicating
Temperature Transmitter HART

 Interface Guide

which may be downloaded from
www.beka.co.uk/manuals

7.1.2  Summary of functions

The functions that may be configured vary depending
upon the input selected.

Thermocouple and RTD inputs

The BA474ND will always display sensor
temperature.

Configuration allows:

Digital display units and resolution to be selected.

Bargraph display to represent required part of the
digital displayed range.

4/20mA output current to have required input
range.

Voltage and resistance inputs

The BA474ND can display the voltage or resistance
input in any engineering units.

Configuration allows:

Zero and span of digital display to be adjusted.

Bargraph display to represent required part of the
digital displayed range.

4/20mA output current to have required input
range.

Each of the functions in the configuration menu is
summarised below, including a cross-reference to a
more detailed description.

Transmitter            Summary

   

display               of function

‘InPut’

Transmitter input

Selects

 o

ne of the following inputs:

Thermocouple ‘tHC’
3 wire RTD 

‘3rtd’

4 wire RTD

‘4rtd’

Differential RTD

‘d_rtd’

Voltage ‘Volt’
3 wire resistance 

‘3rES’

4 wire resistance

’4rES’

See section 7.2.1

The content of the configuration menu depends upon
which transmitter input is selected, see following
summary and Figs 6, 7 and 8.

Содержание BA474ND

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA474ND...

Страница 2: ...fice Cutbush Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB...

Страница 3: ...Issue 7 4 th March 2014 BA474ND Type n certified field mounting indicating temperature transmitter with intrinsically safe sensor input Issue 7...

Страница 4: ...f bargraph display bAr 7 2 9 Access code CodE 7 2 10 Resistance thermometer type r tYPE 7 2 11 Decimal point position dP 7 2 12 Lower input display in Lo 7 2 13 Higher input display in Hi 7 3 Default...

Страница 5: ...ormation for IECEx installations and for use in combustible dust atmospheres is contained in appendices to this manual The transmitter is HART Registered and is compliant with HART protocol standard r...

Страница 6: ...used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450oC T2 300oC T3 200oC T4 135oC T5 100oC At an ambient temperature between 20 and...

Страница 7: ...intrinsic safety approval the sensor may be installed in Zone 0 or 1 BEKA Application Guide AG310 provides comprehensive information on the design installation and maintenance of Extra low voltage dc...

Страница 8: ...Zener barrier or galvanic isolator is required thus reducing complexity and cost There are four requirements when designing a BA474ND loop 1 The output voltage of the supply powering the transmitter...

Страница 9: ...terminal should be connected to a local earth The BA474ND enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries The BA474ND liquid crystal...

Страница 10: ...lly safe and non intrinsically safe terminals within the transmitter terminal enclosure Conductors of intrinsically safe circuits and non intrinsically safe circuits should not be contained in the sam...

Страница 11: ...ected by an access code the first parameter InPut will be displayed If the transmitter is protected by an access code CodE will be displayed first Pressing P will allow the four digit security code to...

Страница 12: ...ts low or high display resolution See section 7 2 4 Transmitter Summary display of function FAuLt Sensor fault analogue indication Selects 1 of 3 under over range output currents to indicate that a se...

Страница 13: ...rmocouple has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 7 2 3 Units of digital display dEG The transmitter digital display may be in one of...

Страница 14: ...ss P which will display the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depen...

Страница 15: ...return control to one of the digits 7 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain access N...

Страница 16: ...oned using either the or button Pressing the P button again will return control to one of the digits 7 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter...

Страница 17: ...15...

Страница 18: ...16...

Страница 19: ...17...

Страница 20: ...on site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to...

Страница 21: ...r the function which enables the type of resistance thermometer to be selected The transmitter will display the existing type of resistance thermometer using the or button select 100r which is the req...

Страница 22: ...P to enter the bArLo sub function which will reveal the existing digital display at which the bargraph starts Set the display to 0100 0 using the or button to adjust the flashing digit and the P butto...

Страница 23: ...raph flashing and 4 20mA fixed at 3 6 3 8 or 21 0mA Sensor fault detection has been activated Sensor and input wiring 9 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENA...

Страница 24: ...Scale and tag marking BA474ND indicating temperature transmitters are fitted with a blank escutcheon around the liquid crystal display If specified when the transmitter is ordered this can be supplie...

Страница 25: ...he outputs are polarised and current will only flow in one direction Terminals 8 and 10 should be connected to the positive side of the supply Ron 8ohms 1 2V Roff greater than 180k Note Because of the...

Страница 26: ...functions Display Description of function ALr1 Alarm 1 ALr2 Alarm 2 The two functions each contain seven identical sub functions one set for configuration alarm 1 and the other for configuration alar...

Страница 27: ...25...

Страница 28: ...reveal the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 10 4 8 Alarm...

Страница 29: ...xists the alarm will be reactivated 10 4 12 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA474ND transmitter is in the operat...

Страница 30: ...to be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transm...

Страница 31: ...nput input terminals 1 2 3 4 is galvanically isolated and intrinsically safe Ex iaD When the transmitter is installed in a Zone 22 dust hazardous area this allows the transmitter sensor input terminal...

Страница 32: ...d and that it is free from foreign bodies Use as a Ex nA Ex tD instrument with an intrinsically safe Ex ia sensor input Transmitter in Zone 22 sensor in Zone 20 or 21 Maintenance may only be performed...

Страница 33: ...x gas and dust certification of the transmitter are identical to the ATEX certifications described in the main section and in Appendix 1 of this instruction manual Like the ATEX certificate the IECEx...

Отзывы: