38
9.
OPERATION AS A CLOCK
When configured as a clock the BA377E can display
local time in a variety of twelve or twenty four hour
formats. The displayed time can be adjusted via the
front panel push buttons which may be protected by
a user definable four digit security code to prevent
unauthorised or accidental adjustment.
The clock may be synchronised to an external time
standard via the instrument's reset terminals. When
these two terminals are connected together by an
external switch contact, the clock display will be
reset to a preconfigured time and will resume
running from this time when the contacts are
opened.
When fitted with the optional galvanically isolated
control outputs the clock can be configured to turn
each solid state output on and off twice during each
twenty four hour period.
Fig 18 shows a simplified block diagram of the
BA377E configured as a clock.
The instrument can be supplied with the following
factory fitted accessories:
Backlight Internally powered
Dual isolated control outputs
Fig 17
BA377E block diagram with clock
configuration.
9.1
Initialisation and loss of power
Each time power is applied to a BA377E initialisation
is performed. After a short delay the following
display sequence occurs:
All segments of the display are activated
Instrument starts functioning using the
configuration stored in the instrument's
permanent memory.
Following initialisation, the instrument will display a
flashing display which is a request for the local time
to be entered. The clock will not start to function
until a display time has been entered, or the remote
reset contacts are closed and opened to synchronise
the clock to a preconfigured time.
If during normal operation the power supply is
interrupted for more than 30ms, the display will
return to the flashing condition and the display time
will have to be re-entered. Longer interruptions may
be tolerated by powering the Clock from a lightly
loaded galvanic isolator or via a Zener barrier from
an instrument supply with large output capacitance.
9.2
Controls when configured as a clock
The BA377E clock is configured and adjusted via
four front panel push buttons. In the display mode
i.e. when the instrument is displaying time, the push
button functions are:
(
+
&
Shows in succession, firmware
version number, instrument function
CLoc
and output accessories that
are fitted:
-A
Dual Control Outputs
(
+
)
Access to configuration menu
Note:
When optional control outputs are fitted, the
BA377E clock may be configured to provide direct
access to the control output
on
and
off
times from
the display mode when the
(
+
*
push buttons
are operated. - see section 9.4.13
9.3
Displays when configured as a clock
The BA377E clock has a single digital display plus
annunciators.
Time
Shows time in selected 12 or
display
24 hour format.
Reset
Activated while clock is being
annunciator
synchronised and external
reset contacts are closed.
Control output
Show status of both optional
annunciators
control output.
Содержание BA377E
Страница 1: ...Issue 6 4th May 2021 BA377E Single input Intrinsically safe Timer or Clock Issue 6...
Страница 28: ...28...
Страница 29: ...29...
Страница 40: ...40...
Страница 51: ...51...
Страница 52: ...52...
Страница 53: ...53...
Страница 54: ...54...
Страница 55: ...55...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...61...
Страница 62: ...62...