background image

17

The rate and total annunciators will also be
interchanged.  Pressing the Up and Down buttons
simultaneously will interchange the displays.

Note:

 Both decimal points must be repositioned

after the displays have been interchanged.

6.7 Lower display:  ‘dISPLAY.2’

This function turns the lower display on or off.
When turned off, the BA338C will only have one
eight digit display which may be programmed to
show total flow or rate of flow.

To check the status of the lower display, select
‘dISPLAY.2’ from the menu and press P which will
reveal if the function is ‘On’ or ‘OFF’.  The setting
can be changed by pressing the Up or Down
button followed by the E button to return to the
main menu.

6.8  Rate scale factor:   ‘SCALE-r’

Together with the instrument timebase, this
function defines the arithmetic relationship
between the pulse input frequency and the rate
display.  When used with a flowmeter SCALE-r
should be set to the K-factor of the flowmeter  i.e.
the number of pulses the flowmeter produces for a
unit of flow.  e.g.  45.6 pulses per litre.   See
section 7 for a worked example.

SCALE-r is a dividing factor that may be adjusted
between 0.001 and 99999999.

To check or change the rate scale factor select
'SCALE-r' from the main menu and press P to
reveal the existing setting, one digit will be
flashing.  The value of the flashing digit can be
changed by pressing the Up or Down buttons.
When this digit is correct pressing P will transfer
control to the next digit.

To position the decimal point in the rate scale
factor, move the flashing digit to the left hand side
of the required decimal point position and
simultaneously press the Up and Down buttons.

When the required rate scale factor has been
entered, press E to store the number and return to
the main menu.

6.9  Timebase:  ‘t-bASE’

The timebase multiplies the rate display by 1, 60 or
3,600 depending upon whether the BA338C is
required to display rate per second, per minute or
per hour.    See Fig 8.

To  check  or  change  the  timebase,  select   't-
bASE' from the main menu and press P which will
reveal the current setting.   Pressing the Up or
Down button will index through the  three options:

tb-1

for flow / second

tb-60

for flow / minute

tb-3600 

for flow / hour

Select the required multiplier and press E to return
to the main menu.

6.10  Rate filter:   ‘FILtEr’

This digital filter has two independent adjustable
parameters enabling the rate display frequency
response to be tailored for optimum performance.

The filter parameters are controlled by a two digit
number.  The first digit defines the amount of
filtering applied to the display as shown below.

First digit

Filter time constant

seconds

0X

              0

1X

              1.3

2X

              4.3

3X

              6.5

4X

              8.7

5X

            11.3

6X

            15.7

7X

            20.9

8X

            25.2

9X

            31.5

The second digit defines the deviation from the
displayed rate at which the filter will be overridden
and the rate display will move rapidly to the new
value.

Second

digit

Magnitude of step

change which will

produce a rapid

response

X0

              Off

X1

              1%

X2

              2%

X3

              4%

X4

              8%

X5

            12%

X6

            16%

X7

            24%

X8

            32%

X9

            64%

By careful adjustment of the two parameters a
stable display with an acceptable step input
response can be obtained for most applications.

Содержание BA338C

Страница 1: ...ry 2011 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator Total display BA338C Intrinsically safe Externally powered pulse input panel mounting rate...

Страница 2: ...te interval 6 5 Type of input 6 6 Position of the decimal points 6 7 Lower display 6 8 Rate scale factor 6 9 Timebase 6 10 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Reset...

Страница 3: ...ost any pulse output flowmeter The total display may be reset to zero by a remote switch contact or from the front panel push buttons Optional accessories enable the flow rate to be transmitted to oth...

Страница 4: ...fied Body Intertek Testing Services ITS confirming compliance with the European ATEX Directive 94 9 EC for Group II Category 1 gas atmospheres EEx ia IIC T5 The instrument bears the Community Mark and...

Страница 5: ...lvanic isolator connected to terminals 3 and 4 The two system certificates specify maximum permitted cable parameters when 28V 300 devices are used 3 3 2 Contact 2 wire proximity detector or open coll...

Страница 6: ...nfirming that it complies with the requirements for Group II Category 1 G EEx ia IIC T5 Tamb 40 to 60o C specified in the ATEX Directive When connected to a suitable system the BA338C may be installed...

Страница 7: ...uit that is used for all BA338C installations protected by Zener barriers For simplicity connections for the optional pulse output 4 20mA output and backlight are included in the appendix to this manu...

Страница 8: ...tified intrinsically safe voltage source within the hazardous area which can withstand a 500V rms insulation test to earth for one minute and has output parameters equal to or less than Uo 28V dc Io 1...

Страница 9: ...is used to transfer the signal to the rate totaliser in the hazardous area Fig 5 Pulse source in safe area 4 3 1 Power supply Any certified galvanic isolator may be used to power the BA338C providing...

Страница 10: ...ces should be connected to terminals 3 and 4 These terminals comply with the requirements for simple apparatus They may be directly connected to any certified intrinsically safe voltage source within...

Страница 11: ...ent secured with four panel mounting clips The BA338C liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument For reflective di...

Страница 12: ...ith the requirements of the European EMC Directive 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs To prevent circulating currents cable screens should only be earth...

Страница 13: ...decimal points Moving the position of a decimal point in a scale factor will therefore affect the instrument calibration The BA338C updates its total flow calculation twice per second If the instrumen...

Страница 14: ...14...

Страница 15: ...AY 2 Lower display Turns the loweer display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between th...

Страница 16: ...sing Up or Down will scroll through the five options UOLts Voltage pulse input Threshold 1V and 3V 5kHz max Input terminals 3 and 4 COIL Low voltage pulse Threshold 20mV peak 5kHz max Input terminals...

Страница 17: ...on the decimal point in the rate scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required ra...

Страница 18: ...next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons Wh...

Страница 19: ...6 15 Security code CodE The calibration and conditioning of the instrument may be protected by a four digit security code which must be entered before access to the programme menu is granted New inst...

Страница 20: ...nput Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off using the Up or Down bu...

Страница 21: ...c metre so the BA338C is required to display 1 cubic metre for every 1 050 x 1 000 pulses received SCALE t should therefore be set to 1 050 000 Select SCALE t from the main menu and press P which will...

Страница 22: ...trument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pre...

Страница 23: ...alarms 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Страница 24: ...status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Programmable functions for each alarm include adjustable setpoin...

Страница 25: ...ay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 3 4 tYPE Type of alarm Defines whether the alarm operates on the...

Страница 26: ...or the alarm type has been changed Both alarms must therefore be enabled after calibration changes 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditio...

Страница 27: ...resis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When th...

Страница 28: ...l disable the security code allowing direct access to the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code...

Страница 29: ...ght powered by Zener barrier The display brilliance depends upon the current flowing through the backlight This is determined by the supply voltage and the end to end resistance of the Zener barrier o...

Страница 30: ...ce and inductance specified by the system certificate of the circuit connected to the BA338C Fig 16 shows how the pulse output circuit may be powered from the BA338C supply to drive a counter in the s...

Страница 31: ...the rate display by the d P function The value of the flashing digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next...

Страница 32: ...4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 3 FM Approval Appendix 1 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14 Guarantee 8 5 HI...

Страница 33: ...d with the following gases Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM entity parameters are similar to the ATEX param...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...36...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40...

Страница 41: ...41...

Отзывы: