15

All new BA338C rate totalisers are supplied
calibrated as requested at the time of ordering.  If
calibration information is not supplied, the
instrument will be conditioned for an open collector
input, with SCALE-r and SCALE-t set to 1 and a
timebase of seconds.

6.3  Summary of programmable functions

This section summarises all the programmable
functions.  When read in conjunction with Fig 9 it
provides a quick aid for programming the
instrument.  If more detail is required, each section
contains a reference to a full description of the
function.

SUMMARY

Display

Description of function

‘UpdAtE’

Display update time

Allows the interval between display
updates to be selected.
See section 6.4

'InPut'

Type of input

Enables one of five types of input
to be selected:
UOLtS Voltage pulse
COIL

Magnetic pick-off

Pr.dEt NAMUR proximity

detector.

COntACt

Switch contact

OP.COL

Open collector

See section 6.5

'd.P.'

Decimal points

Defines the position of the decimal
point in both the rate and total
displays and enables the rate and
total displays to be interchanged.
See section 6.6

‘dISPLAY.2’ Lower display

Turns the loweer display, which
normally shows rate, on or off.
See section 6.7

Display

Description of function

'SCALE-r' Rate Scale Factor

Defines the arithmetic relationship
between the pulse input frequency
and the rate display.  May be adjusted
between 0.001 and 99999999.
When used with a flowmeter, SCALE-
r should be set to the flowmeter K
factor (pulses per unit of
measurement)  if the display is
required in the same flow units as the
K factor.
See section 6.8

't-bASE'

Timebase

Selectable multiplier to display  flow
rate in units per second, per minute or
per hour..
Select:

tb-1

for flow / second

tb-60

for flow / minute

tb-3600 

for flow / hour

See section 6.9

'FILtEr'

Rate filter

Adjustable digital filter to reduce noise
on the rate display.  Two parameters
each adjustable between 0 and 9.
See section 6.10

'SCALE-t' Total Scale Factor

Defines the arithmetic relationship
between the number of input pulses
and the total display.

 

May be adjusted between 0.001 and
99999999.
When used with a flowmeter SCALE-t
should be set to the flowmeter K
factor (pulses per unit of
measurement).

 

See section 6.11

'CLIP-OFF'  Clip off

To prevent the totalisation of very low
flow rates, clip-off enables the user to
select a flow rate below which
totalisation is inhibited.
See section 6.12

Содержание BA338C

Страница 1: ...ry 2011 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator Total display BA338C Intrinsically safe Externally powered pulse input panel mounting rate...

Страница 2: ...te interval 6 5 Type of input 6 6 Position of the decimal points 6 7 Lower display 6 8 Rate scale factor 6 9 Timebase 6 10 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Reset...

Страница 3: ...ost any pulse output flowmeter The total display may be reset to zero by a remote switch contact or from the front panel push buttons Optional accessories enable the flow rate to be transmitted to oth...

Страница 4: ...fied Body Intertek Testing Services ITS confirming compliance with the European ATEX Directive 94 9 EC for Group II Category 1 gas atmospheres EEx ia IIC T5 The instrument bears the Community Mark and...

Страница 5: ...lvanic isolator connected to terminals 3 and 4 The two system certificates specify maximum permitted cable parameters when 28V 300 devices are used 3 3 2 Contact 2 wire proximity detector or open coll...

Страница 6: ...nfirming that it complies with the requirements for Group II Category 1 G EEx ia IIC T5 Tamb 40 to 60o C specified in the ATEX Directive When connected to a suitable system the BA338C may be installed...

Страница 7: ...uit that is used for all BA338C installations protected by Zener barriers For simplicity connections for the optional pulse output 4 20mA output and backlight are included in the appendix to this manu...

Страница 8: ...tified intrinsically safe voltage source within the hazardous area which can withstand a 500V rms insulation test to earth for one minute and has output parameters equal to or less than Uo 28V dc Io 1...

Страница 9: ...is used to transfer the signal to the rate totaliser in the hazardous area Fig 5 Pulse source in safe area 4 3 1 Power supply Any certified galvanic isolator may be used to power the BA338C providing...

Страница 10: ...ces should be connected to terminals 3 and 4 These terminals comply with the requirements for simple apparatus They may be directly connected to any certified intrinsically safe voltage source within...

Страница 11: ...ent secured with four panel mounting clips The BA338C liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument For reflective di...

Страница 12: ...ith the requirements of the European EMC Directive 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs To prevent circulating currents cable screens should only be earth...

Страница 13: ...decimal points Moving the position of a decimal point in a scale factor will therefore affect the instrument calibration The BA338C updates its total flow calculation twice per second If the instrumen...

Страница 14: ...14...

Страница 15: ...AY 2 Lower display Turns the loweer display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between th...

Страница 16: ...sing Up or Down will scroll through the five options UOLts Voltage pulse input Threshold 1V and 3V 5kHz max Input terminals 3 and 4 COIL Low voltage pulse Threshold 20mV peak 5kHz max Input terminals...

Страница 17: ...on the decimal point in the rate scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required ra...

Страница 18: ...next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons Wh...

Страница 19: ...6 15 Security code CodE The calibration and conditioning of the instrument may be protected by a four digit security code which must be entered before access to the programme menu is granted New inst...

Страница 20: ...nput Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off using the Up or Down bu...

Страница 21: ...c metre so the BA338C is required to display 1 cubic metre for every 1 050 x 1 000 pulses received SCALE t should therefore be set to 1 050 000 Select SCALE t from the main menu and press P which will...

Страница 22: ...trument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pre...

Страница 23: ...alarms 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Страница 24: ...status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Programmable functions for each alarm include adjustable setpoin...

Страница 25: ...ay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 3 4 tYPE Type of alarm Defines whether the alarm operates on the...

Страница 26: ...or the alarm type has been changed Both alarms must therefore be enabled after calibration changes 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditio...

Страница 27: ...resis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When th...

Страница 28: ...l disable the security code allowing direct access to the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code...

Страница 29: ...ght powered by Zener barrier The display brilliance depends upon the current flowing through the backlight This is determined by the supply voltage and the end to end resistance of the Zener barrier o...

Страница 30: ...ce and inductance specified by the system certificate of the circuit connected to the BA338C Fig 16 shows how the pulse output circuit may be powered from the BA338C supply to drive a counter in the s...

Страница 31: ...the rate display by the d P function The value of the flashing digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next...

Страница 32: ...4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 3 FM Approval Appendix 1 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14 Guarantee 8 5 HI...

Страница 33: ...d with the following gases Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM entity parameters are similar to the ATEX param...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...36...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40...

Страница 41: ...41...

Отзывы: