4

2.1

Controls

Both models are controlled and calibrated via four
front panel push buttons.    In the display mode i.e.
when the indicator is displaying a process variable,
these push buttons have the following functions:

(

While  this  button  is  pushed  the
indicator will display the input current
in  mA,  or  as  a  percentage  of  the
instrument span depending upon how
the  indicator  has  been  configured.
When  the  button  is  released  the
normal  display  in  engineering  units
will return.  The function of this push
button  is  modified  when  optional
alarms are fitted to the indicator.

&

While  this  button  is  pushed  the
indicator  will  display  the  numerical
value  and  analogue  bargraph*  the
indicator  has  been  calibrated  to
display  with  a  4mA

Φ

 input.   When

released  the  normal  display  in
engineering units will return.

*

While  this  button  is  pushed  the
indicator  will  display  the  numerical
value  and  analogue  bargraph*  the
indicator  has  been  calibrated  to
display  with  a  20mA

Φ

 input.   When

released  the  normal  display  in
engineering units will return.

)

No  function  in  the  display  mode
unless the tare function is being used.

(

 + 

&

Indicator  displays  firmware  number
followed by version.

(

 + 

*

Provides  direct  access  to  the  alarm
setpoints  when  the  indicator  is fitted
with  optional  alarms  and  the  

AC5P

access  setpoints  function  has  been
enabled.

(

 + 

)

Provides  access  to  the  configuration
menu via optional security code.

Note:

* BA324NG 

only

Φ

  If the indicator has been calibrated

using the CAL function, calibration
points may not be 4 and 20mA.

3.

CERTIFICATION

Both models have ATEX and IECEx gas and dust
certification.  This section of the instruction manual
describes  ATEX  gas  certification.    ATEX  dust
certification is described in Appendix 1 and IECEx
approvals are described in Appendix 2.

3.1

ATEX Ex nA certification

Notified Body Intertek Testing and Certification Ltd
have issued both models with a common EC-Type
Examination Certificate number ITS11ATEX47255.
This  confirms  compliance  with  harmonised
European  standards  and  it  has  been  used  to
confirm  compliance  with  the  European  ATEX
Directive  for  Group  II,  Category 3G  equipment,
Ex   nA  ic   IIC   T5   Gc   Ta   =   -40   to   +70°C.     The
indicators carry the community mark and, subject
to local codes of practice, may be installed in any
of  the  European  Economic  Area  (EEA)  member
countries.  ATEX certificates are also acceptable
for installations in Switzerland.

This  section  of  the  instruction  manual  describes
ATEX  installations  in  explosive  gas  atmospheres
conforming  with  EN

 

60079-14

 

Electrical

installations design, selection and erection

.  When

designing systems for installation outside the UK
the local Code of Practice should be consulted.

3.2

Zones, gas groups and T rating

Both indicators have been certified Ex nA ic IIC T5.
When connected to a suitable system they may be
installed in:

Zone 2

explosive gas air mixture not
likely to occur, and if it does
will only exist for a short time.

Be used with gases in groups:

Group

A

propane

Group

B

ethylene

Group

C

hydrogen

In gases that may be used with equipment having
a temperature classification of:

T1

450°C

T2

300°C

T3

200°C

T4

135°C

T5

100°C

At ambient temperatures between -40 and +70°C.

This  allows  both  models  to  be  used  with  most
common industrial gases except carbon disulphide
and ethyl nitrite which have an ignition temperature
of 95°C.

Содержание BA304NG

Страница 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Страница 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Страница 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Страница 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Страница 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Страница 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Страница 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Страница 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Страница 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Страница 10: ...10...

Страница 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Страница 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Страница 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Страница 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Страница 15: ...15...

Страница 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Страница 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Страница 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Страница 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Страница 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Страница 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Страница 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Страница 23: ...23...

Страница 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Страница 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Страница 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Страница 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Страница 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Страница 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Отзывы: