background image

11

6.2

Indicator function:  

FunC

This configuration function defines the relationship
between the indicator’s 4/20mA input current and
the  indicator’s  display.    Three  alternatives  are
available:

5td

Standard linear relationship

root

Square root extraction

Lin

16 segment adjustable lineariser

To reveal the existing indicator function select 

FunC

from the configuration menu and press 

(

.   If the

function is set as required, press  

)

 to return to

the menu, or press the 

&

 or 

*

 button to change

the setting, followed by the  

)

 button to return to

the configuration menu.

5td

Linear

Provides  a  linear  relationship  between
the  4/20mA indicator  input  current  and
the indicator display.

root

Square root extraction

Primarily intended to linearise the square
law  4/20mA  output  from  differential
flowmeters. 

For reference, the following table shows
the output current from a non-linearised
differential flowmeter.

% of full flow

Current output mA

2.5

4.01

10.0

4.16

25.0

5.00

50.0

8.00

75.0

13.00

100.0

20.00

When  the  root  function  is  selected  the
indicator will display flow in linear units. 

Lin

16 segment adjustable lineariser

Enables  non-linear  variables  to  be
displayed  by  the  indicator  in  linear
engineering units.  Use of the lineariser is
described in section 7 of this instruction
manual.

6.3

Resolution:  

rE5n

This  function  defines  the  resolution  of  the  least
significant  display  digit.    Decreasing  the  display
resolution can improve the  readability  of a noisy
signal.    Select  

rE5n

  from  the  menu  and  press

(

 which will reveal the current display resolution.

To  change  the  resolution  press  the  

&

 or  

*

button to select 

1

2

5

 or 

10

 digits, followed by the

)

 button to enter the selection and return to the

configuration menu.

6.4

Position of the decimal point:  

dP

A dummy decimal point can be positioned between
any of the digits or it may be absent.  To position
the  decimal  point  select  

dP

  from  the  menu  and

press  

(

.   The decimal point can be moved by

pressing the  

&

 or  

*

 push button.  If a decimal

point is not required it should be positioned beyond
the  most  or  least  significant  digit.      When
positioned as required press the 

)

 button to enter

the selection and return to the configuration menu.

6.5

Calibration using an external
current source:  

CAL

This  function  enables  the  zero  and  span  of  the
indicator  to  be  adjusted  using  an  external
calibrated  current  source.    When  used  with  an
accurate  traceable  current  source  this  is  the
preferred method of calibration.

Zero is the indicator display with 4mA input
Span is the indicator display with 20mA input

To  calibrate  the  indicator  select  

CAL

 from  the

configuration menu and press  

(

.  The indicator

will display 

2Ero

 which is a request for a 4mA input

current.   Adjust  the  external  current calibrator  to
4.000mA and again press 

(

 which will reveal the

current  zero  display.    The  flashing  digit  of  the
indicator display can be changed by pressing the

&

 or  

*

 buttons, when set as required pressing

(

 will transfer control to the next digit.  When all

the digits have been adjusted, press  

)

 to enter

the new zero and return to the 

2Ero

 prompt .

Pressing the  

*

 button will cause the indicator to

display  

5PAn

 which is a request for a 20mA input

current.   Adjust  the  external  current calibrator  to
20.000mA and  again  press  

(

  which  will  reveal

the existing span display.   The flashing digit of the
indicator display can be changed by pressing the

&

 or 

*

 buttons, when set s required pressing 

(

will transfer control to the next digit.  When all the
digits have been adjusted press  

)

 to enter the

new span and return to the  

5PAn

 prompt.  Finally

press 

)

 again to return to the configuration menu.

Notes:

a. The indicator input current must be adjusted to

the  required  value  before  the  zero  and  span
functions  are  entered  by  pressing  the

(

 button.

b. Indicators may be calibrated at currents other

than  4  and  20mA,  withiin  the  range  3.8  to
21.0mA providing  the  difference  between  the
two  currents  is  greater  than  4mA.    If  these
conditions are not complied with, the indicator
displays 

FaiL

 and aborts the calibration.

c. If  the  zero  current  is  greater  than  the  span

current the instrument will be reverse acting i.e.
an  increasing  input  current  will  cause  the
display to decrease.

Содержание BA304NG

Страница 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Страница 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Страница 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Страница 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Страница 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Страница 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Страница 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Страница 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Страница 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Страница 10: ...10...

Страница 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Страница 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Страница 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Страница 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Страница 15: ...15...

Страница 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Страница 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Страница 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Страница 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Страница 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Страница 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Страница 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Страница 23: ...23...

Страница 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Страница 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Страница 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Страница 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Страница 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Страница 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Отзывы: