Additional Installation Tips

6.7 Cable and Bus Termination RS485

Use shielded and twisted pair cable. The pair capacitance may not exceed 52.5
pF/m and area at least 0.25 mm

2

(AWG 24), if you want to use the maximum

transfer distance and maximum transfer speed.

0 V, the reference voltage for communication should be included in
the cabling. With two-way communication use two pairs; one pair for
communication and one pair for 0 V.

The shield must be grounded at one end. The other end is usually grounded,
but with longer distances or when there is a difference in the ground potential,
the shield should be connected to the ground via 0.1 uF/250 V plastic
capacitor to prevent ground current in the braided shield. A number of
manufacturers recommend that the shield be grounded at each node. Various
manufacturers have different systems for bus termination. The RS485
standard does not describe how the “Fail Safe” function would be carried out,
just that the system should be able to handle the error.

Depending on the recipients’ design, the bus wires may be on the same level or
require pull-up or pull-down to ensure that no faulty signals are detected when the
bus is in resting mode (all transmitters are disconnected).

1

2

3

4

+5 V

0 V

1 K

1 K

120 ohm

120 ohm

120 ohm

+5 V

+5 V

0 V
0 V

0 V

0 V

0 V

0 V

1 K

1 K

1 K

1 K

VCC

VCC

(120 ohm)

Inside operator panel

Operator
panel
RS422

CAB8

CAB8

Bus
RS485

Shield

Bus termination

5358

2

14

15

6

19

7
8

1
2

3
4

5
6

7

8

2
15

3
16

17
4

14

8

7

55

50

17

1  2  3  4   5  6  7  8

Some (older) operator panels had pull-up and pull-down resistance except for
the actual bus termination at 120 ohm, similar to Westermo and Profibus. See 1
in drawing above.
Newer panels have another type of recipient, so-called built-in “Fail Safe”, where
simple bus termination resistance is sufficient. See 2 in drawing above.
If other nodes on the RS485 network require pull-up and pull-down and the
operator panel is at one end of the loop, one of the following procedures can be
carried out:

Connect two 1k/0.25 W resistors in the 25-pole D-sub contact. See 3 in
drawing above. Set jumper pins 6-19.

Use CAB8. It offers the option of bus termination with pull-up/-down. It
is also easy to connect the bus cable via the screw terminal block. See 4 in
drawing above.

Beijer Electronics, MAEN015A

23

Содержание iX Panel T4A

Страница 1: ...iX Panel T4A Installation Manual English MAEN015A 2011 05...

Страница 2: ...updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipmen...

Страница 3: ...a 10 4 ChemicalResistance 12 4 1 MetalCasing 12 4 2 Touch Screen and Overlay 13 4 2 1 Autotex F157 207 13 4 2 2 Touch Screen Surface 14 4 2 3 Auto ex EB 14 5 Operator Panel Drawings 15 5 1 Communicati...

Страница 4: ...of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserves an illustrative purpose Be...

Страница 5: ...cleaningormaintenance operations disconnect the equipment from the electrical supply Clean the display and surroundingfront cover with asoft cloth and mild detergent Replacingthe battery incorrectly...

Страница 6: ...installation plate thickness 11 mm Space requirements when installingthe operatorpanel 100 mm 100 mm 145 mm 104 mm 50 mm 50 mm 43 mm 100 mm Caution The openings on the enclosure are for airconvection...

Страница 7: ...ing it or letting itfall may cause damage 2 Use the cut out dimensions thatare included on the outline drawingto cut acorrectopeningin the cabinet A separate cut out drawingisavailable for download fr...

Страница 8: ...shielded communication cables Separate high voltage cables from signal and supply cables 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Connect cable A Connect cable B usingan M5 sc...

Страница 9: ...rator panelto the controller please refer to the help le for the driverin question 2 2 2 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe applicati...

Страница 10: ...port for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS422 RTS chassis mounted female with standard locking screws 4 40 UNC Ethernet 1 x 10 Base T 100 Base T shielded RJ 45 USB 1 x USB H...

Страница 11: ...ature 20 to 85 C depending on display Relative humidity 95 non condensed Approvals and certifications Information is available on the web site www beijerelectronics com See section ChemicalResistance...

Страница 12: ...llowing chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above c...

Страница 13: ...acid 50 Gumption1 SBP 60 951 Ariel powderin solution1 Hydrochloric acid 36 Sulfuric acid 10 Bleach1 Linseed oil Tomato ketchup Castoroil Methanol Trichloroacetic acid 50 Causticsoda 40 1 Nitric acid...

Страница 14: ...4 2 3 Autoflex EB It is recommended to use the Auto ex EB touch display protection lm thatcan be ordered from BeijerElectronics Solvent Resistance Auto ex EBwithstands exposure to the same chemicalsa...

Страница 15: ...port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 TX RS485 TX RX RS422 TX RS485 TX RX 2 RS232 RX RS232 RX 3 RS232 TX RS232 TX 4 RS422 RX RS422 RX 5 GND GND GND GND 6 RS422 TX RS485 TX RX RS422 TX RS4...

Страница 16: ...iX PanelT4A Outline 7 max 11 mm material thickness 43 145 104 87 9 9 128 9 9 USB host SD memory card slot COM3 RS 232 COM4 RS422 RS485 COM1 RS232 COM2 RS422 RS485 Ethernet 24 V DC Expansion port Beij...

Страница 17: ...assis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 Twist the cables onto the 2...

Страница 18: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur U...

Страница 19: ...s to connect the otherend of the shield to the ground via a 0 1 uF 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms...

Страница 20: ...ted average temperature in the cabinet as wellas a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Inst...

Страница 21: ...LV accordingtoEN 60950 protectionagainst electric shock and UL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay co...

Страница 22: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial ris...

Страница 23: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120...

Страница 24: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: