Additional Installation Tips

6.3 To Achieve Better EMC Protection

Initially, use the original cabling from Beijer Electronics primarily.

Use shielded cables for RS232 communication.

Use twisted pair and shielded cabling for RS422 and RS485.

Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.

Install and connect according to applicable specifications for the relevant bus
standard.

Use shielded cabling for Ethernet, preferably with foil + braided shield.

D-sub covers should be shielded, and the shield should be connected to the
cover 360 ° where the cable comes in.

Connect the shield at both ends.

Shielded cable

Not same potential

Ground plane 1

Ground plane 2

Ground plate

Ground plate
in another building

0.1 uF/250 V

5352

With longer distances, there is a risk that the ground potential may be different.
In that case, the shield should only be connected at one end. A good alternative
is to connect the other end of the shield to the ground via a 0.1 uF/250 V plastic
capacitor. Both ends are then connected to the ground in terms of HF, but only
connected to the ground at one end in terms of LF, thus avoiding the 50 Hz
grounding loops.

Metal cabinet

Metal cabinet

Terminal or connector

Terminal or connector

EMC cable gland

Plastic cable gland

Shielded cable

Shielded cable

Short distance

Cable clamp
in steel

5353

1. Use an EMC cable gland or regular plastic cable gland, remove the outer jacket

and connect the shield to the installation plate with a 360 ° metal cable clamp.

2. Place the 24 V DC and communications cabling in one cable trunk/cable duct

and 230/380 V AC in another. If the cables need to be crossed, cross them at
90 ° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.

Ferrite cores that are snapped onto the shielded cabling may remove minor
disturbances. Large ferrite pieces that are snapped onto unshielded cabling and
where the wires go 2-4 times around the cores are approximately 5-25 times more
efficient.

Beijer Electronics, MAEN015A

19

Содержание iX Panel T4A

Страница 1: ...iX Panel T4A Installation Manual English MAEN015A 2011 05...

Страница 2: ...updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipmen...

Страница 3: ...a 10 4 ChemicalResistance 12 4 1 MetalCasing 12 4 2 Touch Screen and Overlay 13 4 2 1 Autotex F157 207 13 4 2 2 Touch Screen Surface 14 4 2 3 Auto ex EB 14 5 Operator Panel Drawings 15 5 1 Communicati...

Страница 4: ...of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserves an illustrative purpose Be...

Страница 5: ...cleaningormaintenance operations disconnect the equipment from the electrical supply Clean the display and surroundingfront cover with asoft cloth and mild detergent Replacingthe battery incorrectly...

Страница 6: ...installation plate thickness 11 mm Space requirements when installingthe operatorpanel 100 mm 100 mm 145 mm 104 mm 50 mm 50 mm 43 mm 100 mm Caution The openings on the enclosure are for airconvection...

Страница 7: ...ing it or letting itfall may cause damage 2 Use the cut out dimensions thatare included on the outline drawingto cut acorrectopeningin the cabinet A separate cut out drawingisavailable for download fr...

Страница 8: ...shielded communication cables Separate high voltage cables from signal and supply cables 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Connect cable A Connect cable B usingan M5 sc...

Страница 9: ...rator panelto the controller please refer to the help le for the driverin question 2 2 2 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe applicati...

Страница 10: ...port for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS422 RTS chassis mounted female with standard locking screws 4 40 UNC Ethernet 1 x 10 Base T 100 Base T shielded RJ 45 USB 1 x USB H...

Страница 11: ...ature 20 to 85 C depending on display Relative humidity 95 non condensed Approvals and certifications Information is available on the web site www beijerelectronics com See section ChemicalResistance...

Страница 12: ...llowing chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above c...

Страница 13: ...acid 50 Gumption1 SBP 60 951 Ariel powderin solution1 Hydrochloric acid 36 Sulfuric acid 10 Bleach1 Linseed oil Tomato ketchup Castoroil Methanol Trichloroacetic acid 50 Causticsoda 40 1 Nitric acid...

Страница 14: ...4 2 3 Autoflex EB It is recommended to use the Auto ex EB touch display protection lm thatcan be ordered from BeijerElectronics Solvent Resistance Auto ex EBwithstands exposure to the same chemicalsa...

Страница 15: ...port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 TX RS485 TX RX RS422 TX RS485 TX RX 2 RS232 RX RS232 RX 3 RS232 TX RS232 TX 4 RS422 RX RS422 RX 5 GND GND GND GND 6 RS422 TX RS485 TX RX RS422 TX RS4...

Страница 16: ...iX PanelT4A Outline 7 max 11 mm material thickness 43 145 104 87 9 9 128 9 9 USB host SD memory card slot COM3 RS 232 COM4 RS422 RS485 COM1 RS232 COM2 RS422 RS485 Ethernet 24 V DC Expansion port Beij...

Страница 17: ...assis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 Twist the cables onto the 2...

Страница 18: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur U...

Страница 19: ...s to connect the otherend of the shield to the ground via a 0 1 uF 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms...

Страница 20: ...ted average temperature in the cabinet as wellas a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Inst...

Страница 21: ...LV accordingtoEN 60950 protectionagainst electric shock and UL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay co...

Страница 22: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial ris...

Страница 23: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120...

Страница 24: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: