Additional Installation Tips

6.4 Ambient Temperature

The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the panel’s electronics.

Operator
panel

Power

Power

Power

30 °C outside

Top
50 °C inside

Bottom
40 °C inside

Middle
45 °C inside

Airflow

Axial fan
120 x 120 mm

5354

In most cases, the ambient temperature for the operator panel is significantly
higher than the device cabinet’s ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet will be considerably higher than the
theoretical temperature increase that would be expected. All electronics are
sensitive to heat. The lifespan of an electrolytic capacitor is cut in half with an 8-10
° increase in temperature. A 15-20 ° temperature increase results in a quarter of the
lifespan etc.
Rittal has a good program for estimating the anticipated average temperature in
the cabinet as well as a large program for controlling the temperature in the device
cabinet.
An enamel-coated steel cabinet has a radiant heat value of 5.5 W/m

2

and degrees

C.
Installing a fan inside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a 120 x 120 mm
axial fan, available in 24 V DC, 115 and 230 V AC.
Install the fan so that it sits in the cooler area and will blow cold air against the
operator panel. If the fan is mounted at the top and sucks air upwards, the fan’s
ambient temperature will be higher = shorter lifespan.
A good fan with a ball-bearing mounting has an expected lifespan of at least
40,000 hours (not a guaranteed lifespan) at 40 °C. This corresponds to at least 4
years of continuous use. If a thermostat is installed, the fan only needs to come
on when needed.
Large graphic terminals draw only one fifth of the current when the background
lighting is off. The loss effect drops from e.g. 25 W to only 5 W.
The operator panel’s loss effect = supply voltage x current. Virtually no power goes
to external users and no loss effects due to inputs.

Beijer Electronics, MAEN015A

20

Содержание iX Panel T4A

Страница 1: ...iX Panel T4A Installation Manual English MAEN015A 2011 05...

Страница 2: ...updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipmen...

Страница 3: ...a 10 4 ChemicalResistance 12 4 1 MetalCasing 12 4 2 Touch Screen and Overlay 13 4 2 1 Autotex F157 207 13 4 2 2 Touch Screen Surface 14 4 2 3 Auto ex EB 14 5 Operator Panel Drawings 15 5 1 Communicati...

Страница 4: ...of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserves an illustrative purpose Be...

Страница 5: ...cleaningormaintenance operations disconnect the equipment from the electrical supply Clean the display and surroundingfront cover with asoft cloth and mild detergent Replacingthe battery incorrectly...

Страница 6: ...installation plate thickness 11 mm Space requirements when installingthe operatorpanel 100 mm 100 mm 145 mm 104 mm 50 mm 50 mm 43 mm 100 mm Caution The openings on the enclosure are for airconvection...

Страница 7: ...ing it or letting itfall may cause damage 2 Use the cut out dimensions thatare included on the outline drawingto cut acorrectopeningin the cabinet A separate cut out drawingisavailable for download fr...

Страница 8: ...shielded communication cables Separate high voltage cables from signal and supply cables 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Connect cable A Connect cable B usingan M5 sc...

Страница 9: ...rator panelto the controller please refer to the help le for the driverin question 2 2 2 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe applicati...

Страница 10: ...port for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS422 RTS chassis mounted female with standard locking screws 4 40 UNC Ethernet 1 x 10 Base T 100 Base T shielded RJ 45 USB 1 x USB H...

Страница 11: ...ature 20 to 85 C depending on display Relative humidity 95 non condensed Approvals and certifications Information is available on the web site www beijerelectronics com See section ChemicalResistance...

Страница 12: ...llowing chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above c...

Страница 13: ...acid 50 Gumption1 SBP 60 951 Ariel powderin solution1 Hydrochloric acid 36 Sulfuric acid 10 Bleach1 Linseed oil Tomato ketchup Castoroil Methanol Trichloroacetic acid 50 Causticsoda 40 1 Nitric acid...

Страница 14: ...4 2 3 Autoflex EB It is recommended to use the Auto ex EB touch display protection lm thatcan be ordered from BeijerElectronics Solvent Resistance Auto ex EBwithstands exposure to the same chemicalsa...

Страница 15: ...port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 TX RS485 TX RX RS422 TX RS485 TX RX 2 RS232 RX RS232 RX 3 RS232 TX RS232 TX 4 RS422 RX RS422 RX 5 GND GND GND GND 6 RS422 TX RS485 TX RX RS422 TX RS4...

Страница 16: ...iX PanelT4A Outline 7 max 11 mm material thickness 43 145 104 87 9 9 128 9 9 USB host SD memory card slot COM3 RS 232 COM4 RS422 RS485 COM1 RS232 COM2 RS422 RS485 Ethernet 24 V DC Expansion port Beij...

Страница 17: ...assis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 Twist the cables onto the 2...

Страница 18: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur U...

Страница 19: ...s to connect the otherend of the shield to the ground via a 0 1 uF 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms...

Страница 20: ...ted average temperature in the cabinet as wellas a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Inst...

Страница 21: ...LV accordingtoEN 60950 protectionagainst electric shock and UL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay co...

Страница 22: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial ris...

Страница 23: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120...

Страница 24: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: