Hardware Replacement
8
Hardware Replacement
This section contains instructions on how to replace operator panel hardware.
Only components included in the latest bill of material and spare parts list are
allowed. See
Available Spare Parts for iX Panel K100
.
8.1 Mode Switches
The iX Panel K100 has four mode switches (DIP switches) located on the rear side
of the operator panel.
1
24V DC
CF CARD
COM 1
RS422
RS485
COM 2
RS232
10/100
EXP
ANSION
BUSY
MODE
1 2 3 4
ON DIP
MODE
1 2 3 4
ON DIP
Warning:
The modes below are to be used with caution.
The mode switches have the following functions: 1=ON, 0=OFF
Each letter in “MODE” has a corresponding mode switch.
MODE
Description
0000
“Run mode” - boots CE, normal operation.
0010
System Restore, resets the file system and registry,
reinstalls the system program (OPsys_bxxx.CAB). Restores
the operator panel to factory settings.
Warning!
Information can easily accidently be lost.
0100
Image Load mode (Sysload) allows upgrading of the
firmware in the operator panel.
Note:
All files including the file system in the operator
panel will be deleted when upgrading with Image Loader.
1000
Service Menu mode, the service menu for the system
program is shown. Allows the user to set IP configuration,
erase the project, calibrate the touch screen etc. See
section
for details.
Beijer Electronics, MAEN003
21