Beijer Electronics Frequency Inverter BFI-P2 

                         

KI00306B           2020-03 

 

 

 

 

www.beijer.se  www.beijer.no  www.beijer.dk

  

www.beijerelectronics.com  www.beijerelectronics.de   www.beijerelektronik.com.tr       

28 (31) 

    

 

7  General specification 

 

BFI-P2  

Over Current 

200% of rated current for 2,0 s; 150 % for 1 min  

Output Voltage  

3-phase, 0 V to Supply voltage 

Output Frequency 

0 – 500 Hz 

Input Voltage [VAC] 

1-phase, 200 – 240   

3-phase, 380-480  

Voltage Fluctuations 

180 – 264 VAC 

 

342 – 528 VAC 

Input Frequency 

48-62 Hz 

Internal Braketransitor 

Built-in Braking Transistor  

Switching Frequency 

4, 8, 12, 16, 24 or 32 kHz 

Control Methods 

V/F, Energy Optimised, Sensorless & Closed Loop Vector, Open Loop Permanent Magnet, BLDC 

Start Methods 

Digital, Push button Fwd/Rev/Stop, Keypad, Modbus RTU, CANopen and Fieldbuses  

Frequency Setpoint 

Digital Preset speed, Digital motorpotentiometer, analogt 4 – 20 mA, 0 –10 V, Scaling of digital setpoint 
Keypad, Modbus RTU, Canopen and Fieldbuses 

Digital Input 

3 x Programmable Digital Input and 2 x User-selectable Digital or Analog Inputs 

Analog Input 

2 x User-selectable Digital or Analog Inputs. 4-20 mA or 0-10 V or -10 to 10. 12 bit  

Relay Output 

2 x Progammable Relay (single pole and 2-pole ), Maximum load 6,0 A with 230 V or 5A with 30 VDC 

Digital Output Signals 

Drive enabled, Drive healthy, At Target Frequency, Output Frequency > 0.0 Hz, Output Frequency >= Limit, 
Output Current >= Limit, Output Torque >= Limit, Analog Input 2 Signal Level >= Limit 

Analog Output 

2 x User-selectable Digital or Analog Output, 0-10 V DC. Maximum current 20 mA. 10 bit 

Analog Output Signals 

Output Frequency, Output  motor current, Motor torque or Output motor power 

Safety Inputs 

One with sink logic and one with source output 

Communication 

Modbus RTU and CANopen onboard  
Profibus DP, CC-Link, DeviceNet, Ethernet IP, Modbus TCP, Profinet, EtherCat by optionboard 

Acc/Deceration Time 

0 to 6000 sec,  2:nd deceleration ramp, 
S2 & S3 : 5.0 Seconds Default Setting, 0.01 sec Resolution, 0.0-600.0 sec 
S4 – S7 : 10.0 Seconds Default Setting, 0.1 sec Resolution, 0-6000 sec 

Stop Mode 

Ramping / Fast stop / Coasting / DC-brake Zero speed holding time  

Motor Overload 
Protection 

Internal control of output current in combination with motor current setting. Input and output loss phase 
detection. Digital or analog overload signal from motor as standard. Trip level is resistance >2,5 kOhm 

General Functions 

PID-control, Built-in plc, Spin start, Automatic restart, Skip frequency, Stop method at Voltage 
interruption,  Energy Optimizer, Parameter access lock, Master/slave  

Protection Class 

IP20, IP55 or IP66 

Ambient Temperature 

IP20: -10 ºC to +50 ºC, IP66: -10 ºC to +40 ºC,  Storage temperature is -40 ºC to +60 ºC  

Maximum Humidity 

Max. 95 % non-condensing 

Environment

 

No airborne dust, corrosive gases or liquids, conductive contaminants (such as condensation, carbon 
dust, and metallic particles), high moisture, salt or chemical content environments  

Maximum Altitude 

2000 meter above sea level, Derate above 1000 m: 1 %/100m 

Vibrations 

IEC 60068-2-29,  IEC 60068-2-64, IEC 60068-2-6

 

Safety Functions  

IEC 61608, IEC 61800-5-2 (SIL2, PFHd= 1,23E-09 1/h, SFF=50), IEC 62061 (SILCL 2),                    ISO 13849-1 (PL d)

 

EMC 

Use shielded motor cable. Built-in EMC-filter,  
- EN61800-3:2004, 1*230 VAC: Class C1, C2, C3 and C4 
- EN61800-3:2004, 3*400 VAC: Class C2, C3 and C4  

Approvals 

CE, cUL, UL, RoHS, Carbon Trust,

 

 

Max Motorcable Length 

100 meter 

 

BFI-P2 (1x 230 V)    

BFI-P2 (3 x 400 V) 

Drive Model 

043 

070 

105    022 

041 

058 

095 

140 

180 

240 

300 

390 

460 

Output Power, kW 

0,75 

1,5 

2,2    0,75 

1,5 

2,2 

4,0 

5,5 

7,5 

11 

15 

18,5 

22 

Rated Output Current, A 

4,3 

7,0 

10,5    2,2 

4,1 

5,8 

9,5 

14 

18 

24 

30 

39 

46 

Frame Size IP20 

 

Weight IP20 [kg] 

1,8 

 

1,8 

3,5 

9,2 

Frame Size IP55/66 

IP66 Size 2 

 

IP66 Size 2 

IP66 Size 3 

IP55 Size 4 

Weight IP55/66 [kg] 

4,8 

 

4,8 

8,5 

12 

 

BFI-P2 (3 x 400 V) 

Drive Model 

610 

720 

900 

1100 

1500 

1800 

2020 

2400 

3020 

3700 

4500 

Output Power, [kW] 

30 

37 

45 

55 

75 

90 

110 

132 

160 

200 

250 

Rated Output Current, A 

61 

72 

90 

110 

150 

180 

202 

240 

302 

370 

450 

Frame Size IP20 

Size 5 

Size 6A 

Size 6B 

 

Weight IP20 [kg] 

18,1 

32 

43 

No 

130 

Frame Size IP55 

IP55 Size 5 

IP55 Size 6 

IP55 Size 7 

No 

Weight IP55 [kg] 

23 

50 

80 

No 

Содержание BFI-P2

Страница 1: ...and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fau...

Страница 2: ...VECTOR CONTROL 20 6 1 VECTOR CONTROL 21 6 2 ENCODER 21 6 3 PM MOTOR 22 6 4 PLC 22 6 5 KEYPAD 22 6 6 DRIVE OPERATING DISPLAY OLED KEYPAD IP55 AND IP66 23 6 7 ACCESSING AND CHANGING PARAMETER VALUES OL...

Страница 3: ...IP66 Rating Drive BFI P2 IP66 Drive size A Height mm B mm D mm E mm F Depth mm G Width mm H mm I mm J mm Weight kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0095...

Страница 4: ...W 0043 0105 0 75 2 2kW 0022 0095 0 75 4 0 kW 2 221 207 137 209 5 3 185 110 63 1 8 None 0180 0240 4 0 5 5kW 0140 0240 5 5 11 kW 3 261 246 247 6 205 131 80 3 5 0390 0460 7 5 11 kW 0300 0460 15 22 kW 4 4...

Страница 5: ...240 0460 11 22 kW 4 450 428 433 8 252 171 110 8 5 15 12 0610 0720 15 18 5 kW 0610 0900 30 45 kW 5 540 515 520 8 270 235 175 8 5 15 23 0900 1800 22 45 kW 1100 2020 55 110 kW 6 865 830 840 10 330 330 20...

Страница 6: ...2x70 240 2 70 100 3900 6 160 3020 308 400 2x185 2x95 302 2x95 100 4800 6 200 3700 522 600 370 2x95 100 3400 2 200 394 500 250 4500 634 800 450 2x150 100 4250 2 250 478 600 NOTE Operation with single p...

Страница 7: ...Level Without Derating Derate by Maximum Permissible IP20 IP55 and IP66 1000m 3281ft 1 per 100m 328 ft 4000m 13123 ft Derating for Switching frequency Example of Applying Derating Factors A 4kW IP66 d...

Страница 8: ...CY FKKJ EMC or similar Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal...

Страница 9: ...removed if when required OD BR100 BFI is mounted inside an IP20 Size2 and 3 drives and with a resistance of 100 and continuous power of 200 W OD BRES4 BFI is mounted inside IP55 Size4 and 5 drives wit...

Страница 10: ...of EMC filter for BFI P2 IP55 and IP66 must be carried out by Beijer Electronics Size 2 and 3 Size 4 Size 5 Size 6A and 6B Disconnect EMC filter by removing the marked screw or screws 4 10IP66 Integra...

Страница 11: ...VAC is off This is done by an external 24VDC supply to terminal 1 and 0 VDC to terminal 7 This must be a 24 VDC power supply only used for BFI s and no other units Do not mix external 24 VDC supply wi...

Страница 12: ...P1 10 Motor Rated Speed 0 Rpm If not 0 all speed related parameters will be displayed in rpm Setting of rated motor speed enables the slip compensation function Setting of rated motor synchronus speed...

Страница 13: ...xed Preset speeds Start in two directions and up to 8 fixed speeds If only 4 fixed speeds are to be used AIN2 terminal 10 can be excluded If only 2 fixed speeds are to be used AIN1 terminal 6 can be e...

Страница 14: ...from the motor cable Otherwise an external PTC relay might be needed due to disturbances Para meter Name Default setting Function P2 11 Analog Output 1 Function 8 Digital Output Mode Logic 1 24VDC 0...

Страница 15: ...Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 2 10 Mbs Ethercat ESI_BFI_ECT_V_1_09_2 0190507_XML Set by master Set by master DeviceNet 005...

Страница 16: ...decimal places 405 4 05kW 2 Digital Input Status Bit 0 Digital input 1 status Bit 1 Digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heat sink Temperature in C 5 U...

Страница 17: ...P1 14 Parameter Access 0 201 Get access to parameter group 5 P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate 115 2 9 6 19 2 38 4 57 6 or 115 2 k...

Страница 18: ...on included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitte...

Страница 19: ...P1 14 must be set to 201 to access all parameters in the drive The BFI Smartstick must also be unlocked to write parameters See manual BFI Smartstick on www beijerelectronics com BFI Smartstick can be...

Страница 20: ...Set Up procedure Check System criteria effecting auto tune have not change See step 3 in standard set up procedure If any of these setting have changed then the Auto tune procedure must be repeated To...

Страница 21: ...the drive will attempt to ramp and then maintain the motor speed in relation to the reference Available torque on the motor shaft can be limited in parameter P4 07 Maximum motoring Torque limit Motor...

Страница 22: ...manent Magnet Motor Control 6 4 PLC BFI Tools is a PC based commissioning and programming software that can be used with all drives in the BFI series With multi drive support and PLC programming possi...

Страница 23: ...are open Displayed when the drive power is applied motor stopped Drive operating display showing output information Drive trip display showing trip condition ML on left side of the display indicated...

Страница 24: ...r 2s The display shows P Def Drive is returned to factory settings Press the Stop key Note Parameters cannot be defaulted whilst P2 39 1 parameter set locked Parameters can also be put to origin User...

Страница 25: ...0 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 Adjusting individual digits within a parameter value Maximum Speed Limit Maximum Speed Limit 50 0Hz 50 0Hz P1 01 200 0 0 0 P1 01 200 0 0 0 6 11IP20 Changing param...

Страница 26: ...drive will decrease speed until is released The rate of deceleration is limited by the setting in P1 04 Press the key The drive will decelerate to rest at the rate set in P1 04 The display will finall...

Страница 27: ...d reset to 0 P0 27 MWh meter 0 to 65535 Displays the amount of energy consumed by the drive P0 28 Software Version I O version I O Checksum DSP version DSP checksum P0 29 Drive Type Frame size Power r...

Страница 28: ...0 600 0 sec S4 S7 10 0 Seconds Default Setting 0 1 sec Resolution 0 6000 sec Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload Protection Internal control of output...

Страница 29: ...limit specified for the relevant drive Ensure the motor nameplate parameters are correctly in P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and...

Страница 30: ...tput torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time U tor9 25 Output torque too low Minimum torque limit exceeded Active only wh...

Страница 31: ...Beijer Electronics Frequency Inverter BFI P2 KI00306B 2020 03 www beijer se www beijer no www beijer dk www beijerelectronics com www beijerelectronics de www beijerelektronik com tr 31 31...

Отзывы: