5.6 Relay outputs
5.7 Fieldbus control settings
The drive can be controlled by fieldbus or Ethernet. Following settings must be done:
P1-12=4, Start/stop/frequency setpoint command by bus
P1-14=201, make access to parameters in group 5 mentioned below
Terminal 2 must be connected to 24 V and safety inputs(STO+/STO-) correctly connected.
Specific details
Station-
number
Fieldbus
ramp action
P5-07
Communication
Speed/Baud rate Timeout [sec] P5-05 Loss action
P5-06
ProfiNet
GSDML-V2.25-HMS-
ABCC-PRT2P-
201110111.xml
Set by
master
0: Disabled
1: Enabled
Set by master
Drive behaviour if a
communication
command is not
received within time
specified in this
parameter. Type of
reaction decided in
P5-06.
0: Trip
1: Ramp to
stop and
trip
2: Ramp to
stop and
no trip
3: Preset
speed 8
(P2-08)
Profibus DP
HMSB1811.gsd
P5-01
EtherNet/IP
IPaddress
Modbus TCP
CC-Link
Ver1, Remote device
station, Exclusive station
2
P5-01
P5-03:
9,6= 156 kbs
19,2= 625 kbs
38,4= 2,5 Mbs
57,6= 5 Mbs
115,2= 10 Mbs
Ethercat
ESI_BFI_ECT_V_1_09_2
0190507_XML
Set by
master
Set by master
DeviceNet
005A000000620200.eds
P5-01
P5-03
Parameter Default
setting
Function
P2-15:
Relay
output 1
function
terminal
15 and 16
1
0:
Drive Enabled (Running)
When the Drive is enabled
1
Drive Healthy
. Power is applied to the drive and no fault
exists
2:
At Target Frequency
. Output frequency matches the set
frequency
3:
Output Frequency >0 Hz
When the motor runs above zero
speed
4:
Output Frequency >= Limit
. Output frequency > P2-16
(Relay1) or P2-19(Relay2)
5:
Output Current >= Limit
. Motor current > P2-16 (Relay1) or
P2-19(Relay2)
6:
Output Torque >= Limit.
Motor torque > P2-16 (Relay1) or
P2-19(Relay2)
7:
Analog input 2 > Limit
. Analog input 2 > P2-16 (Relay1) or
P2-19 (Only Relay2)
8:
Hoist Brake Control.
Relay can be used to control the
motor holding brake on a hoist (Only Relay2)
P2-18:
Relay
output 2
function
terminal 18
0
10:
Maintenance Due
11:
Drive available- Ready to run
12:
Drive Tripped and in a fault condition
13:
Safe Torque off (STO) status
14:
PID Error ≥ Limit
The PID Error ≥ Programmed limit
Relay Output 2
Default Drive
Enabled
17
18
Relay Output 1
Default Drive
Healthy
14
15