Para-
meter
Name
Default
settng
To be
set
Function
P1-13
Digital Inputs Function
1
1
Must be put to 1
P2-01 Preset Speed 1
5 Hz
Can be set between 0 to P1-01 setting (Maximum Speed)
P2-30
Analog Input 1 Format
0
Type of
analog
input
0: 0 to 10 VDC; 3: 0 to 20mA
4: 4 to 20mA. Trip if signal level < 3mA
5: 4 to 20mA, Ramp to Preset speed 4 if signal level < 3mA
P2-31
Analog Input 1 Scaling
100 %
Defines scaling of analog input 1 at maximum analog input value towards
maximum speed in P1-01.
Output frequency= (Analog input value)/100 * (P2-31)/100 * P1-01 [Hz]
P2-32
Analog Input 1 Offset
0 %
P2-32 defines an offset in % of full range for analog input 1.
A positive offset is deducted from the incoming analog signal and a negative
offset is added.
Example, if P2-30=0–10V and P2-32=10.0%, then 1 volt (10% of 10V) will be
deducted from incoming analog reference prior to it being applied.
5.2 Digital start signal in 2 directions and 8 fixed Preset speeds
Start in two directions and up to 8 fixed speeds. If only 4 fixed speeds are to be used, AIN2 terminal
10, can be excluded. If only 2 fixed speeds are to be used, AIN1 terminal 6, can be excluded.
Table below shows what parameters needs to be set to get 2,4 or 8 fixed speeds.
Para-
meter
Name
Default
settng
To be set
if 2 fixed
speeds
To be set
if 4 fixed
speeds
To be set
if 8 fixed
speeds
Function
P1-12
Command Source
0
0
0= Control by digital and/or analog signals
P1-13
Digital Inputs Func
1
2
2= 8 Preset Speeds, Run and Direction Control
P2-01
Preset Speed 1
5 Hz
Can be set between 0 Hz to P1-01 setting
(Maximum speed)
P2-02 PresetSpeed 2
10 Hz
P2-03 PresetSpeed 3
25 Hz Not used
P2-04 PresetSpeed 4
50 Hz Not used
P2-05 PresetSpeed 5
0
Not used Not used
P2-06 PresetSpeed 6
0
Not used Not used
P2-07 PresetSpeed 7
0
Not used Not used
P2-08 PresetSpeed 8
0
Not used Not used
Status inputs
Action
AIN2 AIN1 DIN3
0
0
0
Preset speed 1, P2-01
0
0
1
Preset speed 2, P2-02
0
1
0
Preset speed 3, P2-03
0
1
1
Preset speed 4, P2-04
1
0
0
Preset speed 5, P2-05
1
0
1
Preset speed 6, P2-06
1
1
0
Preset speed 7, P2-07
1
1
1
Preset speed 8, P2-08
DIN2:
Fwd or Rev
2
3
4
6
1
DIN1:
Start signal
0 VDC
+24 VDC
AIN1
:
Preset speed
Use internal or external 24 VDC
7
DIN3:
Preset speed
AIN2
:
Preset speed