AtF-01
40
Auto tune Fault
The motor parameters measured through the auto tune are not correct.
Check the motor cable and connections for continuity.
Check all three phases of the motor are present and balanced.
Check motor rated data put into parameters.
AtF-02
41
AtF-03
42
AtF-04
43
AtF-05
44
SC-F01
50
Modbus comms fault
Check the incoming communication connection cable. Check that at least one
register is being polled cyclically within the limit set in P-36 Index 3
SC-F02
51
CANopen comms fault