6.1  Monitoring from Keypad 

Put P14=201 to access monitor values in parameter group P0.  

Par 

Description 

Display range  Explanation 

 P0-01 

1st Analog Input Value 

0 … 100% 

100% = max input voltage 

 P0-02 

2nd Analog Input Value 

0 … 100% 

100% = max input voltage 

 P0-03 

Speed Reference Input 

-P-01 … P-01 

Displayed in Hz if P-10 = 0, otherwise displayed in RPM 

 P0-04 

Digital Input Status 

Binary value 

Drive digital input status 

 P0-05 

User PI output (%) 

0 … 100% 

User PI output (%) 

 P0-06 

DC bus ripple (V) 

0 … 100% 

DC bus ripple (V) 

 P0-07 

Applied Motor Voltage 

0 … 600V AC 

Value of RMS voltage applied to motor 

 P0-08 

DC Bus Voltage 

0 … 1000V dc 

Internal DC bus voltage 

 P0-09 

Heatsink temperature  

-20 … 120 °C 

Temperature of heatsink in ᵒC 

 P0-10 

Hours Run Meter 

0 to 99 999 hours 

Not affected by resetting factory default parameters 

 P0-11 

Run Time Since Last Trip1 

0 to 99 999 hours 

Run-time clock stopped by drive disable or trip. 

 P0-12 

Run Time Since Last Trip2 

0 to 99 999 hours 

Run-time clock stopped by drive disable or trip. Not reseted  
by power down / power up cycling. 

 P0-13 

Trip Log 

0 to 99 999 hours 

Displays most recent 4 trips with time stamp 

 P0-15 

DC Bus Voltage Log 

0 … 1000V 

8 most recent values prior to trip, updated every 256ms 

 P0-16 

Heatsink Temperature Log 

-20 … 120 °C 

8 most recent values prior to trip, updated every 30s 

 P0-17 

Motor Current 

0 to 2x rated current  8 most recent values prior to trip, updated every 256ms 

 P0-18 

DC bus ripple log (V) 

0 … 100% 

8 most recent values prior to trip, 22ms sample time 

 P0-19 

Internal drive temperature log  

-20 … 120 °C 

8 most recent values prior to trip, 30 s sample time 

 P0-20 

Internal drive temperature  

-20 … 120 °C 

Actual internal ambient temperature in ᵒC 

 P0-23 

Temperature log cooling fin 

Hours:min 

Total time of operation above heatsink temp of 85ᵒC 

 P0-24 

Temperatur log internally 

Hours:min 

Total time of operation with drive internal temperatur above 
80ᵒC 

 P0-25 

Estimated rotor speed  

0 … 500 Hz 

In vector control modes, estimated rotor speed in Hz 

 P0-26 

kWh meter / MWh meter 

0.0 kWh / 0 MWh 

Total number of kWh / MWh consumed by the drive.   

 P0-27 

Total run time of drive fans 

Hours:min:sec 

First value displays time in hrs, press up to display mm:ss. 

 P0-28 

Software version  

e.g.  “1.00”,  “47AE” 

“1”: Indicates I/O processor, “2“ : Indicates power stage 

 P0-29 

Drive type identifier 

 

BFI type, Drive rating, input phases, voltage, firmware  

 P0-30 

Drive serial number 

xxxxxx / yy / zzz 

Unique drive serial number 

 P0-31 

Motor current Id / Iq 

0 to 2x rated current  Displays magnetising current (Id) and torque current (Iq).  

 P0-32 

Actual PWM switching 
frequency (kHz) 

4 to 32 kHz 

Actual switching frequency used by drive 

 P0-33 

Critical fault counter – O-I 

Number of times 

Number of trips due to overcurrent 

 P0-34 

Critical fault counter – O-Volts 

Number of times 

Number of trips due to over voltage 

 P0-35 

Critical fault counter – U-Volts 

Number of times 

Number of trips due to under voltage 

 P0-36 

Critical fault counter – O-temp  

Number of times 

Number of trips due to over temperature heatsink 

 P0-38 

Error counter – O-hEAt 

Number of times 

Number of trips due to internal over temperature 

 P0-39 

Error counter – Modbus 

Number of times 

Number of trips due to Modbus error 

 P0-47 

Fire mode running Hours 

Hours 

Number of Hours in Fire mode 

 P0-48 

Scope channel 1 & 2 

 

Displays value for Scope channel 1 & 2 

 P0-49 

Scope channel 3 & 4 

 

Displays value for Scope channel 3 & 4 

 P0-50 

Bootloader and motor control 

 

Internal value 

Содержание BFI-E3 IP20 Series

Страница 1: ...connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current...

Страница 2: ...URRENT LIMIT CONTROL 13 5 13 TUNING OF PM MOTOR 13 5 14 MODBUS RTU 14 5 15 CANOPEN 15 5 16 PI CONTROL 16 5 17 ENERGY OPTIMIZATION FUNCTION 16 5 18 SPIN START 17 5 19 BFI SMARTSTICK 17 6 KEYPAD 18 6 1...

Страница 3: ...0 109 162 5 123 83 50 5 5 10 1 0 0070 0105 1 5 2 2 kW 0041 0095 1 5 4 0 kW 2 221 207 137 209 5 3 150 110 63 1 7 0153 4 0 kW 0140 0240 5 5 11kW 3 261 246 247 6 175 131 80 3 2 No 0300 0460 15 22kW 4 420...

Страница 4: ...300 33 4 275 240 9 5 NOTE 1x230 V BFI E3 0070 and 3x400 V BFI E3 0041 are without brake transistor for Size 1 and Size2 with Mounting bolts for Size1 to Size 3 are 4xM4 and 4xM8 for Size 4 Control Ter...

Страница 5: ...Max Motor Cable Length Power losses Amps Amps mm2 Amps Amps mm2 m W 0 75 0022 3 5 6 1 5 1 5 2 2 1 5 100 22 5 1 5 0041 5 6 6 1 5 1 5 4 1 1 5 100 50 2 2 0058 7 5 10 1 5 1 5 5 8 1 5 100 50 4 0095 11 5 1...

Страница 6: ...Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal in the drive itself For...

Страница 7: ...be used together with a slow external overload protection and P34 2 Table shows setting current of the external overload protection Drive model Minimum resistance when regenerated power is equal with...

Страница 8: ...f the BFI is being used Picture below shows an overview of control signals for the drive and factory set functionality when an external 24 VDC is being used 2 3 4 5 6 7 1 DI1 Start signal DI2 Fwd or R...

Страница 9: ...110 overload Spin start variable torque P 14 Parameter Access 0 201 Normally only parameters P 01 to P 14 are accessable All other parameters are accessable with this P14 201 P 17 Switching Frequency...

Страница 10: ...10 VDC Sign decides rotationdirection t 4 20 4 to 20mA Trip if signal level 3mA r 4 20 4 to 20mA Stop and Trip if signal level 3mA t 20 4 20 to 4mA Trip if signal level falls 3mA P 20 Preset Speed 1 5...

Страница 11: ...pad function 1 2 Motor accelerete to minimal frequency P 02 at start 3 Motor accelerete to latest speed before stop 5 5 Start stop by individual signals Start is done by a pulse on one terminal and st...

Страница 12: ...to P 08 A 10 Motor Power 0 to 200 0 10V 0 to Rated inverter power kW 11 Load current 0 200 0 10V 0 till P 08 Current used producing torque on motor shaft Parameter Default setting Function P 18 Relay...

Страница 13: ...ning is done measured values are stored in parameter P 55 P 56 and P 57 Auto tuning only needs to be done once If motor creates strange sound weak torque performance and speed is not stable change Gai...

Страница 14: ...n of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network connection OPT 2 RJTRM BFI RJ45 with a 110 ohm resistor To be put in the last BFI splitter Para meter Name Default se...

Страница 15: ...m resistor for bus termination included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be...

Страница 16: ...d gives decreased feedback signal P 44 PI Digital Setpoint 0 0 Digital Preset PI Setpoint in P 45 1 Analog Input 1 Terminal 6 PI setpoint P 45 PI Digital Setpoint 0 0 When P 44 0 PI setpoint for PI Co...

Страница 17: ...ed 1 Enabled 2 Activ on Trip Brown out and Coast stop 5 19 BFI Smartstick Communication between BFI Drive and PC software BFI Tools or app BFI Tools Mobile is done by Bluetooth through BFI Smartstick...

Страница 18: ...and hold the Navigate key 2 seconds P dEF To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show P dEf H 50 0 Drive is...

Страница 19: ...l drive temperature log 20 120 C 8 most recent values prior to trip 30 s sample time P0 20 Internal drive temperature 20 120 C Actual internal ambient temperature in C P0 23 Temperature log cooling fi...

Страница 20: ...led from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1 In Speed Control the speed is controlled from...

Страница 21: ...0 A with 230 V or 5A with 30 VDC Analog output 1 x User selectable Digital or Analog Output 0 10 V DC Maximum current 20 mA 10 bit Communication Modbus RTU or CANopen Acc Deceration time 0 to 600 sec...

Страница 22: ...O Uolt 6 Over voltage on DC bus Check the supply voltage is within the allowed tolerance If the fault occurs on deceleration or stopping increase the deceleration time in P 04 or install a suitable b...

Страница 23: ...d through the auto tune are not correct Check the motor cable and connections for continuity Check all three phases of the motor are present and balanced Check motor rated data put into parameters AtF...