background image

 

Beijer Electronics Frequency Inverter BFI-E3

               

KI00369B  2019-09 

 

 

 

 

www.beijer.se www.beijer.no

 

www.beijer.dk

 

www.beijerelectronics.de  www.beijerelectronics.com www.beijerelektronik.com.tr

       

22 (24)

 

8  Warning and Alarm codes 

Drive Display

Fault Code 

Fault 

Number 

Description 

Corrective Action 

Stop 

Drive is healthy and in stop condition. Motor is not energized. No enable signal is present to start drive 

OI-b 

Brake resistor over 
current  

Check cabling to the brake resistor and the brake resistor for short circuits.  
Ensure the resistance of the brake resistor is > minimum allowed value.  

OL-br 

Brake resistor thermal 
overload. 

Only occurs if P-34 = 1. The internal brake transistor software protection is 
activated to prevent damage to the brake resistor.  

If a standard braking resistor is being used, P-34 MUST be 1 

Increase deceleration time in P-04, decrease load or speed 

For Other Brake Resistors 

Ensure the resistance of the brake resistor is > 

minimum allowed value. Use an external thermal protection and set P-34=2. 

O-I



Instantaneous Over 
current on the drive 
output.  
Excess load or shock 
load on the motor. 

Fault occurs immediately on drive enable or run command 

Check the output wiring connections to the motor and the motor for short 
circuits phase to phase and phase to earth. 

Fault occurs during motor starting then check 

 

Motor is free to rotate and there are no mechanical blockages. 

 

If the motor has a brake fitted, check the brake is releasing correctly. 

 

Increase the acceleration time in P-03. Reduce the motor boost voltage P-11 

Fault occurs when motor operating at constant speed 

Investigate overload or malfunction.  

I_trP

Motor thermal overload 
protection trip. The 
drive has tripped after 
delivering >100% of 
value in P-08 for a 
period of time 

 

Ensure the correct motor nameplate current value is entered in P-08. 

 

Check for correct Star or Delta wiring. 

 

Check if decimal points are flashing (which indicates the output current > P-
08 value). Increase acceleration ramp (P-03) or decrease motor load.  Check 
the total motor cable length is within the drive specification. Check the load 
mechanically to ensure that no jams, blockages or mechanical faults exist. 

PS-trP

 

Hardware Over Current 

Check the wiring to motor for phase to phase and phase to earth short circuits. 
Disconnect motor and cable. Retest. If the drive trips with no motor 
connected, replace drive. Test for insulation failure. 

O-Uolt

 

Over voltage on DC 
bus 

Check the supply voltage is within the allowed tolerance. If the fault occurs on 
deceleration or stopping, increase the deceleration time in P-04 or install a 
suitable brake resistor and activate the dynamic braking function with P-34. 

U-Uolt 

Under voltage on DC 
bus 

Incoming supply voltage is too low. This trip occurs routinely when power is 
removed from the drive. If it occurs during running, check the incoming 
power supply voltage and all components in the power feed line to the drive. 

O-t 

Heat sink over 
temperature 

The drive is too hot. Check that ambient temperature around the drive is 
within the specification. Ensure sufficient cooling air is free to circulate 
around the drive. Increase the panel ventilation if required. Ensure sufficient 
cooling air can enter the drive, and that the bottom entry and top exit vents are 
not blocked. 

U-t 

Under temperature 

Trip occurs when ambient temperature is less than -20°C.  Temperature must 
be raised over -20°C in order to start the drive. 

P-dEf 

10 

Factory Default  done  

Press the STOP key, drive is ready to configure for particular application 

E-trip 

11 

External trip  
 

E-trip requested on digital input 3.  Normally closed contact has opened for 
some reason. If motor thermistor is connected check if the motor is too hot. 

SC-trp 

12 

Comms loss trip 

Check communication link between drive and external devices. Make sure 
each drive in the network has its unique address. 

FLt-dc 

13

 

DC bus ripple too high 

Check incoming supply phases are all present and balanced 

P-LOSS 

14 

Input phase loss trip 

Drive intended for use with a 3 phase supply has lost one input phase. 

h O-I 

15 

Output Over Current 

Check for short circuits on the motor and connection cable 

Th-FlT 

16 

Temperature too high 

Heat sink temperature too high, check adequate cooling air is provided 

dAtA F 

17 

Internal memory fault. 

Parameters not saved correct, defaults reloaded. Try again. 

4-20 F 

18 

Analog input error 

Analog input out of range. Check input current in range defined by P-16. 

dAtA-E 

19 

Internal memory fault  

DSP fault. Press the stop key. If the fault persists, consult you supplier. 

F-Ptc 

21 

Motor  thermistor trip  

Connected motor thermistor over temperature, check wiring and motor 

FAN-F 

22 

Cooling Fan Fault 

Check / replace the cooling fan. Only IP66 drives 

O-hEAt 

23 

Temperature too high 

Drive ambient temperature too high, check adequate cooling air is provided 

OUt-F 

26

 

Fel efter utgångssteget 

Internt fel i utgångssteg, en fas till motorn saknas, strömmen i alla tre faserna 
till motorn ojämn. Kontrollera installation från U, V och W på BFI.

 

Содержание BFI-E3 IP20 Series

Страница 1: ...connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current...

Страница 2: ...URRENT LIMIT CONTROL 13 5 13 TUNING OF PM MOTOR 13 5 14 MODBUS RTU 14 5 15 CANOPEN 15 5 16 PI CONTROL 16 5 17 ENERGY OPTIMIZATION FUNCTION 16 5 18 SPIN START 17 5 19 BFI SMARTSTICK 17 6 KEYPAD 18 6 1...

Страница 3: ...0 109 162 5 123 83 50 5 5 10 1 0 0070 0105 1 5 2 2 kW 0041 0095 1 5 4 0 kW 2 221 207 137 209 5 3 150 110 63 1 7 0153 4 0 kW 0140 0240 5 5 11kW 3 261 246 247 6 175 131 80 3 2 No 0300 0460 15 22kW 4 420...

Страница 4: ...300 33 4 275 240 9 5 NOTE 1x230 V BFI E3 0070 and 3x400 V BFI E3 0041 are without brake transistor for Size 1 and Size2 with Mounting bolts for Size1 to Size 3 are 4xM4 and 4xM8 for Size 4 Control Ter...

Страница 5: ...Max Motor Cable Length Power losses Amps Amps mm2 Amps Amps mm2 m W 0 75 0022 3 5 6 1 5 1 5 2 2 1 5 100 22 5 1 5 0041 5 6 6 1 5 1 5 4 1 1 5 100 50 2 2 0058 7 5 10 1 5 1 5 5 8 1 5 100 50 4 0095 11 5 1...

Страница 6: ...Shield of the motor cable should be connected to ground earth in both ends On motor side an EMC gland is to be used Shield of motor cable is to be connected to ground terminal in the drive itself For...

Страница 7: ...be used together with a slow external overload protection and P34 2 Table shows setting current of the external overload protection Drive model Minimum resistance when regenerated power is equal with...

Страница 8: ...f the BFI is being used Picture below shows an overview of control signals for the drive and factory set functionality when an external 24 VDC is being used 2 3 4 5 6 7 1 DI1 Start signal DI2 Fwd or R...

Страница 9: ...110 overload Spin start variable torque P 14 Parameter Access 0 201 Normally only parameters P 01 to P 14 are accessable All other parameters are accessable with this P14 201 P 17 Switching Frequency...

Страница 10: ...10 VDC Sign decides rotationdirection t 4 20 4 to 20mA Trip if signal level 3mA r 4 20 4 to 20mA Stop and Trip if signal level 3mA t 20 4 20 to 4mA Trip if signal level falls 3mA P 20 Preset Speed 1 5...

Страница 11: ...pad function 1 2 Motor accelerete to minimal frequency P 02 at start 3 Motor accelerete to latest speed before stop 5 5 Start stop by individual signals Start is done by a pulse on one terminal and st...

Страница 12: ...to P 08 A 10 Motor Power 0 to 200 0 10V 0 to Rated inverter power kW 11 Load current 0 200 0 10V 0 till P 08 Current used producing torque on motor shaft Parameter Default setting Function P 18 Relay...

Страница 13: ...ning is done measured values are stored in parameter P 55 P 56 and P 57 Auto tuning only needs to be done once If motor creates strange sound weak torque performance and speed is not stable change Gai...

Страница 14: ...n of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network connection OPT 2 RJTRM BFI RJ45 with a 110 ohm resistor To be put in the last BFI splitter Para meter Name Default se...

Страница 15: ...m resistor for bus termination included OPT 2 J45SP BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be...

Страница 16: ...d gives decreased feedback signal P 44 PI Digital Setpoint 0 0 Digital Preset PI Setpoint in P 45 1 Analog Input 1 Terminal 6 PI setpoint P 45 PI Digital Setpoint 0 0 When P 44 0 PI setpoint for PI Co...

Страница 17: ...ed 1 Enabled 2 Activ on Trip Brown out and Coast stop 5 19 BFI Smartstick Communication between BFI Drive and PC software BFI Tools or app BFI Tools Mobile is done by Bluetooth through BFI Smartstick...

Страница 18: ...and hold the Navigate key 2 seconds P dEF To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show P dEf H 50 0 Drive is...

Страница 19: ...l drive temperature log 20 120 C 8 most recent values prior to trip 30 s sample time P0 20 Internal drive temperature 20 120 C Actual internal ambient temperature in C P0 23 Temperature log cooling fi...

Страница 20: ...led from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1 In Speed Control the speed is controlled from...

Страница 21: ...0 A with 230 V or 5A with 30 VDC Analog output 1 x User selectable Digital or Analog Output 0 10 V DC Maximum current 20 mA 10 bit Communication Modbus RTU or CANopen Acc Deceration time 0 to 600 sec...

Страница 22: ...O Uolt 6 Over voltage on DC bus Check the supply voltage is within the allowed tolerance If the fault occurs on deceleration or stopping increase the deceleration time in P 04 or install a suitable b...

Страница 23: ...d through the auto tune are not correct Check the motor cable and connections for continuity Check all three phases of the motor are present and balanced Check motor rated data put into parameters AtF...

Страница 24: ...Beijer Electronics Frequency Inverter BFI E3 KI00369B 2019 09 www beijer se www beijer no www beijer dk www beijerelectronics de www beijerelectronics com www beijerelektronik com tr 24 24...

Отзывы: