Installation
10
3.3 Installation
The heat exchanger should only be installed in frost-free, dry premises with a
non-aggressive atmosphere. Dripping water can damage the heat exchanger.
Ensure easy access for assembly/disassembly.
The heat exchanger can be fitted above or below water level.
Typ A for fresh water
Chloride concentration
< 400 mg/l
Chloride concentration
permanent:
0,8 mg/l
transiet
1,2 mg/l
Typ B for sea water
Chloride concentration
< 5000 mg/l
Chloride concentration
permanent:
0,8 mg/l
transiet
1,2 mg/l
Operating point
Volumetric flow rate
Heating
2000 l/h
Pool water
10000 l/h
Thermal output/flow temperature
(at pool water inlet temperature of 20°C)
47,5 KW / 90°C
40,7 KW / 80°C
33,9 KW / 70°C
Important
When the heating circuit is in operation, the pool water side of the heat exchan-
ger must be prevented from running dry.