Safety
6
Operating range for heat exchanger:
Type A for fresh water
Chloridkonzentration
< 400 mg/l
Chlorine concentration
permanent:
0,8 mg/l
transient
1,2 mg/l
Type B for sea water
Chloride concentration
< 5000 mg/l
Chloride concentration
permanent:
0,8 mg/l
transient
1,2 mg/l
Operating point
Volumetric flow rate
Heating
2000 l/h
Pool water
10000 l/h
Thermal output/flow temperature
(at pool water inlet temperature of 20°C)
47,5 KW / 90°C
40,7 KW / 80°C
33,9 KW / 70°C
Conversion and modification of the heat exchanger is prohibited
for safety reasons
1.4 Potential
hazards
The heat exchanger may be damaged.
The heat exchanger may start to leak if the maximum operating overpressure of
2.5 bar on the pool water side or 6 bar on the heating water side is exceeded.
There is a risk of fire.
Connections on the heating water side of the heat exchanger may reach tempe-
ratures of as high as 100°C.
The heat exchanger may heat up to the flow temperature of the heating water if
pool water is not flowing through it.