6.0 Technical Data
LED voltage range
12...690V AC/DC
LED resolution
±12, 24, 50, 120, 230, 400, 690V
Tolerance
complying to DIN VDE 0682, Part 401
LCD voltage range*
12V...690V AC/DC
LCD resolution*
1V
Tolerance*
±(3% rdg. + 5 digits)
Voltage detection
automatic
Acoustic signal
(AC voltage) yes
Polarity detection
full range
Range detection
automatic
Response time
<0.1s LED / <2s LCD
Frequency range
0...400Hz
Automatic load (RCD)
yes
Internal basic load
approx. 2.1 W at 690V
Peak current
Is <0.3 A / Is(5s) < 3.5mA
Operation time
ED (DT) = 30s
Recovery time
10min
Auto Power On
<12 V AC/DC
Single-pole Phase Test
Voltage range
100...690V AC
Frequency range
50...400Hz
Resistance Measurement**
Resistance range
0...1999
Ω
/1
Ω
Tolerance
±(3% v.M. + 10 Digit)
Test current
<300µA
Overvoltage protection
690V AC/DC
Continuity Test
Resistance range
0...400k
Ω
Accuracy
RN +50%
Test current
5µA
Overvoltage protection
690V AC/DC
Rotary Field Indication
Voltage range (LEDs)
100...690V
Frequency range
50...60Hz
Measurement principle
double-pole and contact electrode
Power supply
2 x 1.5 V Micro IEC LR03
Power consumption
max. 30mA / approx. 250mW
Temperature range
-10°C...55°C
Humidity
max. 85% relative humidity
Height above sea level
up to 2000m
Overvoltage class
CAT IV / 600V
Degree of contamination 2
Type of protection
IP65
Safety complying to
DIN EN 61243-3, DIN VDE 0682
Part 401 (first DIN VDE 0680 Part 5,
EN 61010, IEC 61010)
Weight
180g (incl. batteries)
Dimensions (HxWxD)
240 x 56 x 24mm
* only UNITEST beta and gamma / ** only UNITEST 2000 gamma
18
PTDB67410017-04.qxd 30.09.2005 12:08 Uhr Seite