3.2 Electrical installation
The installation of the EMS-8x is limited to the connection of the main power supply and the
switched outputs according to the connection survey:
CAUTION :
Arrange that the mounting is accomplished by an authorized electric company. The
electrical connection must be performed by an electrically skilled person !
Electrically skilled and qualified personnel must be able to read and understand
electric circuit diagrams, to commission and maintain electrical systems, to wire
switch and control cabinets, to install controlling software, to ensure proper
functioning of electrical components and to identify possible hazards in the work
with electric and electronic systems.
Since this is a stationary device with a fixed main power supply, an RCBO must be
installed on the installation side!
Requirements:
•
main power supply is power-less
•
RCBO is switched off
Connection principle
Eccentric-top
Insulation stripping length
9,00 mm
Connection data Single wire (solid)
2,50 mm²
Connection data Stranded wire (flexible)
2,50 mm²
Connection data Stranded wire (with ferrules)
2,50 mm²
Rated torque/Screw size
0,5 Nm/M2,5
Page 6
Figure 2:
Connection diagram