Technical data, mounting, wiring
PS1011-2420-0000
14
Version: 1.0
3.5
Hold-up time
The hold-up time is the time during which the output voltage of a power supply remains within the
specification after a loss of input power. The hold-up time depends on the output load.
At no load the hold-up time can be up to several seconds. During this time, the green DC OK lamp also lights
up.
AC 100V
AC 120V
AC 230V
Hold-up time
typ.
54ms
54ms
54ms
At 24V, 10A, see Fig.
Hold-up time over
input voltage
Min.
44ms
44ms
44ms
At 24V, 10A, see Fig.
Hold-up time over
input voltage
typ.
27ms
27ms
27ms
At 24V, 20A, see Fig.
Hold-up time over
input voltage
Min.
22ms
22ms
22ms
At 24V, 20A, see Fig.
Hold-up time over
input voltage
Fig. 6: Hold-up time over input voltage; switch-off behavior, definitions