Product overview
KL2692
9
Version: 2.0.0
2.2
Technical data
Technical data
KL2692
Number of outputs
2 potential-free relay outputs (make contacts)
Rated load voltage of the outputs
230 V
AC
/ 30 V
DC
Ohmic switching current
5 A
AC
/ 5 A
DC
Inductive switching current
2 A
AC
/ 2 A
DC
Minimum permitted load
10 mA at 5 V
DC
Number of inputs
2 digital inputs (24 V)
Rated voltage of the inputs
24 V
DC
(-15% / +20%)
Signal voltage "0"
-3 V ... 5 V (EN 61131-3, type 1)
Signal voltage "1"
15 V ... 30V (EN 61131-3, Type 1)
Input filter
3.0 ms
Input current
typically 5 mA
Electrical isolation
500 V (K-bus/field voltage)
Power supply for the electronics
via the K-bus
Current consumption from K-bus
typically 165 mA
Bit width in the input process image
2 x 8 bit data, 1 x 8 bit status
Bit width in the output process image
2 x 8 bit data, 1 x 8 bit control
Mechanical switching cycles
minimum 2 x 10
7
Electrical switching cycles
minimum 1 x 10
5
(5 A / 30 V
DC
)
Configuration
via the Bus Coupler or the controller
Weight
approx. 60 g
Permissible ambient temperature range during
operation
0 °C ... + 55 °C
Permissible ambient temperature range during storage -25°C ... + 85 °C
Permissible relative air humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm
Mounting
on 35 mm mounting rail conforms to EN 60715
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
2.3
Basic function principles
Pulse sequence monitoring (cycle)
1. Monitoring is enabled with a falling edge at
Input 1
.
2. If the pulse sequence is too slow (cycle time t
P
too long), the output relays switch off for a minimum
switch-off time t
Amin
. The minimum switch-off time can be specified in register
.
3. If a pulse sequence (1 cycle) was recognized as correct, the output relays will only switch on again
once monitoring is enabled again. This switching mode ensures that triggering of the watchdog re-
mains recognizable.
4. The two output contacts are looped into the control circuit of the switch-off relay.
Automatic self-start is prevented, since the switch-off function block has to be reset through an explicit
manual intervention (monitoring enable).