KS2000 Configuration Software
KL2692
24
Version: 2.0.0
4.4
Settings
The dialog mask for the parameterization of the KL2692 can be found under
Settings
.
Fig. 17: Settings via KS2000
Watchdog time (R
)
This can be used for setting the watchdog time (default: 4 ms). Within the watchdog time, an edge change
must occur on the toggle bit of the control bytes (
), in order to prevent the drop-out of the output
relays.
This can be used for setting the minimum time (default: 50 ms) for which the relays remain switched off after
the watchdog has been triggered, even if, after a subsequent monitoring activation, the following pulse
sequence is recognized as correct.
4.5
Process data
The Status byte (Status), the Control byte (Ctrl) and the process data (Data) are displayed in a tree structure
under
ProcData
.
Fig. 18: ProcData
The reading glasses mark the data that are currently graphically displayed in the
History
field.