Parameterization and commissioning
EL6751
151
Version: 3.5
Index F101 Extended Diag
Index (hex) Name
Meaning
Data type
Flags
Default
F101:0
Extended Diag
This object contains the diagnosis of the EL6751, which
is mapped into TxPDO 133 (Index
)
UINT8
RO
F101:01
reserved for extensions
8-bit gap
F101:09
reserved for extensions
3-bit gap
F101:0C
SYNC Toggle
toggles with each transmission of the SYNC message
BOOLEAN
RO
F101:0D
Device Diag
reserved for extensions
BOOLEAN
RO
F101:0E
Sync Error
reserved for extensions
BOOLEAN
RO
F101:0F
PDO Toggle
The bit toggles if the EtherCAT input data has been up-
dated since the previous EtherCAT input update
BOOLEAN
RO
F101:10
PDO State
This bit is set if at least one configured CANopen slave
has a node state that is not equal to 0
BOOLEAN
RO
F101:11
Cycle Counter
This counter is incremented after each CAN cycle (if at
least one CANopen slave has been configured)
UINT16
RO
F101:12
Slave Status Counter This byte contains the number of
UINT8
RO
F101:13
reserved for extensions
8-bit gap
F101:14
Cycle Time
This entry contains the required cycle time of the CAN
cycle in 1/9 µs
UINT16
RO
Index F102 Node State
Index (hex) Name
Meaning
Data type
Flags
Default
F102:0
Node State
There is a node state for each CANopen slave config-
ured in n*16. The node states are mapped in Tx-
PDO 132 (Index
UINT8
RO
F102:01
Node state of the first configured CANopen slave
UINT8
RO
0
No error
1
CANopen slave has not been restarted follow-
ing an error, because entry 0x8yy0:27 has
been configured for manual restart or because
the CANopen slave was stopped with AoE
2
CANopen slave does not respond
4
Length of the data at a StartUp SDO upload is
incorrect or StartUp SDO download has failed
5
Value of the data at a StartUp SDO upload is
incorrect
8
CANopen slave is in boot-up (StartUp SDOs
are being transmitted, so far no error)
11
CAN controller is in bus-off
12
CANopen slave has left OPERATIONAL (auto-
matically or on request by AoE)
14
Guarding has not toggled
18
CANopen slave was started, all CAN TxPDOs
were received, but no EtherCAT process data
has been exchanged yet
20
CAN TxPDO with incorrect length received
22
synchronous or event-timer-triggered CAN Tx-
PDO was not received in time
23
at least one CAN TxPDO has not yet been re-
ceived after the Start Node
24
TX FIFO overflow (e.g. if no CAN acknowledge
is detected)
40
CAN TxPDO with type 1 transmission was not
received in this CAN cycle
...
F102:7F
Node state of the 127
th
configured CANopen slave
UINT8
RO