Parameterization and commissioning
EL6751
153
Version: 3.5
Index F120 Diagnostic Data
Index (hex) Name
Meaning
Data type
Flags
Default
F120:0
Diagnostic Data
This object contains additional measured times for the
CAN cycle that are not contained in the Sync Manager
parameter objects
/
UINT8
RO
F120:01
Cycle Time
current cycle time of the CAN cycle (equivalent to
0xF101:14) in 1/9 µs
UINT32
RO
F120:03
Maximum Cycle Time maximum cycle time of the CAN cycle (in 1/9 µs)
UINT32
RO
F120:04
Bus Load
CAN bus load in %
UINT16
RO
F120:05
16-bit gap
F120:09
Sync RxPDOs fin-
ished Time (T3)
current time after the start of the CAN cycle at which all
synchronous RxPDOs were sent (in 1/9 µs)
UINT32
RO
F120:0B
Sync RxPDOs fin-
ished Maximum Time
(max T3)
maximum time after the start of the CAN cycle when all
synchronous RxPDOs have been sent (in 1/9 µs)
UINT32
RO
F120:0C
Preparing of PDOs
finished Time (T2)
current time after the start of the CAN cycle at which the
sending of the synchronous RxPDOs begins
UINT32
RO
F120:0E
Preparing of PDOs
finished Maximum
Time (max T2)
maximum time after the start of the CAN cycle at which
the sending of the synchronous RxPDOs begins
UINT32
RO
F120:0F
Output Calc and Copy
Time (T1)
current time after the start of the CAN cycle at which the
SYNC message can be sent
UINT32
RO
F120:11
Ouput Calc and Copy
Maximum Time (max
T1)
maximum time after the start of the CAN cycle at which
the SYNC message can be sent
UINT32
RO
F120:12
Input Calc and Copy
Time (T5)
current time still required after the input shift time
(
:03) until the EtherCAT input data have
been completely written
UINT32
RO
F120:14
Input Calc and Copy
Maximum Time (max
T5)
maximum time still required after the input shift time
(
:03) until the EtherCAT input data have
been completely written
UINT32
RO
F120:15
Output Failed Counter Number of cycles in which the EtherCAT output data
were not adopted
UINT16
RO
F120:16
Input Failed Counter
Number of cycles in which the EtherCAT input data were
not collected
UINT16
RO
F120:17
Send sync RxPDO
Failed Counter
Number of CAN cycles that were omitted because the
previous CAN cycle was not ended in time
UINT16
RO
F120:18
RX Error Counter
Rx error counter (cumulative errors from
UINT16
RO
F120:19
TX Error Counter
Tx error counter (cumulative errors from
UINT16
RO
F120:1A
reserved for extensions
16-bit gap
RO
Index F200 Control
Index (hex) Name
Meaning
Data type
Flags
Default
F200:0
Control
The object contains the control data that are mapped in
RxPDO 134 (index
)
UINT8
RO
F200:01
CAN Controller Auto
Reset when BUS-
OFF
In the case of a CAN bus-off, this allows the EL6751 to
be switched again to bus-on via the process data.
BOOLEAN
RO