Technical data
EK1110
EK1110-0008
Task in the EtherCAT system
Conversion of the E-bus signals to 100BASE-TX Ethernet for extension
of the EtherCAT network
Transmission medium
Ethernet CAT 5 cable (shielded)
Cable length between two Bus
Couplers
max. 100 m (100BASE-TX)
Protocol / Baud rate
any EtherCAT protocol / 100 Mbaud
Delay
approx. 1 µs
Configuration
no address and configuration settings required
Bus connection
1 x RJ45
1 x M8, shielded, screw type
Power supply
from E-bus
Current consumption
typ. 130 mA
Dielectric strength
500 V (supply voltage/EtherCAT)
Dimensions (W x H x D)
approx. 44 mm x 100 mm x 68 mm
Weight
approx. 50 g
Permissible ambient temperature
range during operation
-25°C ... +60°C
(extended temperature range)
0°C ... +55°C
Permissible ambient temperature
range during storage
-40°C ... + 85°C
-25°C ... + 85°C
Permissible relative humidity
95%, no condensation
Mounting [
}
22]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN
60068-2-27,
see also
installation instructions
[
}
25]
for enhanced mechanical
load capacity
conforms to EN 60068-2-6 / EN
60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
33]
cULus [
}
34]
CE
ATEX [
}
32]
cULus [
}
34]
2.3
Start
For commissioning:
• mount the EK1110 as described in the chapter
Mounting and wiring [
}
20]
• configure the EK1110 in TwinCAT as described in chapter
Parameterization and commissioning
[
}
36]
.