Error handling and diagnostics
CXxxxx-M930/B930
41
Version: 1.1
Number
Text
Description
Remedial action / rea-
son
0
No error
No error
No error
1
PROFINET Device state
machine is in boot mode
PROFINET Device State
Machine is still in the
start-up phase
Not an error, wait
2
Device not found
Device does not reply to
the Identify Request
Check connection, device
connected, was the
device called by its correct
name?
3
The stationname is not
unique
The station name is not
unique
There are two or more
devices in the network
with the same PROFINET
name. A correct
identification cannot take
place.
4
IP could not set
IP address could not be
set.
The PROFINET device
has rejected the IP
settings for some reason.
Check whether the IP
settings are correct.
5
IP conflict
An IP conflict has
occurred in the network.
A possible cause is that
several devices have the
same IP address.
6
DCP set was not
successful
There was no reply or an
erroneous reply to a DCP
Set.
Check connection, device
connected, was the
device called by its correct
name?
7
Watchdog error
The connection was
broken off with a
Watchdog error.
Check the cycle time,
check the connection, if
necessary increase the
Watchdog factor.
8
Datahold error
The connection was
broken off with a Datahold
error.
Frame Data status was
invalid for the length of the
DataHoldTimer. Restart
the device if necessary.
9
RTC3: Sync signal could
not be started
For IRT only: the Sync
signal could not be
started.
Is EtherCAT Sync signal
correct or has Sync0
started?
10
PROFINET Controller has
a link error
The PROFINET controller
has no link.
Check cable and
connection.
11
The aliasname is not
unique
The alias name is not
unique
There are two or more
devices in the network
with the same alias name.
This is made up of the
neighborhood information
(PortId.ChassisId). A
correct identification
cannot take place.
12
The automatic name
assignement isn't possible
- wrong device type
The automatic name
assignment is not
possible.
The expected PROFINET
device is not in the
projected position
(VendorId or DeviceId
does not correspond).
Hence, no automatic
naming and thus no
device start is possible.