TwinCAT tabs
CXxxxx-M930/B930
18
Version: 1.1
4.2.3
Settings
The
Settings
tab contains settings that directly concern the PROFINET controller.
1
2
3
4
No.
Description
1
At this point you can configure the network settings for PROFINET. By
default, values for IP address, subnet and gateway are already entered, but
you can change these.
Press the
Set IP settings
button to apply your changes.
The selection of the address range need not correspond to the network card
settings. The PROFINET communication spreads its own net, which can be
selected here. If you change the subnet or gateway, the settings are also
applied to configured devices.
2
At this point you can set the name for the PROFINET controller. A name is
entered by default.
Press the
Set System name
button to apply your changes.
3
At this point you can read the VendorID and DeviceID of the controller. You
can also set the server and client UDP ports here. However, the default
settings are adequate in most cases.
4
If you activate this option, a new PROFINET controller is automatically
assigned the name of the previous controller when a device is replaced.
This allows you to easily replace a PROFINET controller in the event of a
fault.