background image

Notes on the documentation

CP6606

5

Version: 2.0

1

Notes on the documentation

This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.

The following instructions and explanations must be followed during installation and commissioning of the
components. The responsible staff must ensure that the application or use of the products described satisfy
all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.

Disclaimer

The documentation has been prepared with care. The products described are, however, constantly under
development. For that reason the documentation is not in every case checked for consistency with
performance data, standards or other characteristics. In the event that it contains technical or editorial errors,
we retain the right to make alterations at any time and without warning. No claims for the modification of
products that have already been supplied may be made on the basis of the data, diagrams, and descriptions
in this documentation. All illustrations shown are only examples. The configurations depicted may deviate
from the standard.

Trademarks

Beckhoff

®

, TwinCAT

®

, TwinCAT/BSD

®

, TC/BSD

 ®

, EtherCAT

®

, EtherCAT G

®

, EtherCAT G10

®

, EtherCAT P

®

,

Safety over EtherCAT

®

, TwinSAFE

®

, XFC

®

, XTS

®

 and XPlanar

®

 are registered and licensed trademarks of

Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own
purposes could violate the rights of the owners.

Patents

The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 and similar applications and
registrations in several other countries.

Copyright

© Beckhoff Automation GmbH & Co. KG. Publication of this document on websites other than ours is
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the
grant of a patent, utility model or design.

Delivery state

All the components are supplied in particular hardware and software configurations appropriate for the
application. Changes to the hardware or software configuration are permitted, provided they are within the
specified limits for power consumption and power loss (please refer to the respective data sheet).

Delivery conditions

In addition, the general delivery conditions of the company Beckhoff Automation GmbH & Co. KG apply.

Содержание CP6606

Страница 1: ...Manual EN CP6606 Panel PC 2 17 2022 Version 2 0...

Страница 2: ......

Страница 3: ...Transport and storage 17 4 2 Control cabinet installation 17 4 2 1 Dimensions 18 4 2 2 Installation in the control cabinet 19 4 2 3 Wall installation with wall mounting frame 20 4 3 Connecting the Pa...

Страница 4: ...Table of contents CP6606 4 Version 2 0...

Страница 5: ...The configurations depicted may deviate from the standard Trademarks Beckhoff TwinCAT TwinCAT BSD TC BSD EtherCAT EtherCAT G EtherCAT G10 EtherCAT P Safety over EtherCAT TwinSAFE XFC XTS and XPlanar a...

Страница 6: ...uries CAUTION Disregarding the safety notice may lead to minor injuries Warning of damage to property NOTE Disregarding the notice may lead to damage to property 2 2 Intended use The Panel PC is desig...

Страница 7: ...fer to the respective data sheet Ensure that only trained specialists with a control and automation engineering background operate the device Use by unauthorized persons can lead to damage to property...

Страница 8: ...rks The latter should be connected to the corporate network or the Internet only if appropriate protective measures have been set up In addition the recommendations from Beckhoff regarding appropriate...

Страница 9: ...PC has the following features ARM processor 1 x 10 100BASE T port on board 1 x EtherCAT on board MicroSD 2 x USB 1 x RS232 Push button extension You have the possibility to order the Panel PC with th...

Страница 10: ...ig 2 CP6606_Structure Table 1 Key C6606 structure No Component Description 1 Clamping lever Mounting the Panel PC in the panel of the control cabinet 2 Display and touch screen glass Operation of the...

Страница 11: ...d UPS does not serve to back up the operating system X101 1 2 3 4 5 Fig 3 CP6606_voltage socket pin numbering Table 2 Voltage socket pin assignment Pin Signal Description 1 NC not connected 2 NC not c...

Страница 12: ...ed pair cables is used The maximum length of the cable connection is 100 m X103 X102 LAN1 EtherCAT 8 1 8 1 Fig 4 CP6606_Ethernet interface pin numbering Table 3 Ethernet interface pin assignment Pin S...

Страница 13: ...nals comply with the RS232 standard 1 5 6 9 X107 Fig 6 CP6606_RS232 interface pin numbering Table 5 RS232 pin assignment Pin Signal Description 1 DCD Data Carrier Detect 2 RxD Receive Data 3 TxD Trans...

Страница 14: ...g of the TC LED Color Flashing interval Meaning Red Steadily lit TwinCAT Stop Green Steadily lit TwinCAT Run Mode Blue Steadily lit TwinCAT Config Mode TwinCAT not started LED PWR The lower PWR power...

Страница 15: ...Product overview CP6606 15 Version 2 0 3 4 Name plate The name plate provides information about the Panel PC equipment 1 2 3 4 5 6 12 7 8 9 10 11 13 14 15 17 20 21 22 18 19 16 Fig 8 CP6606_name plate...

Страница 16: ...interfaces 12 RS232 interface X107 13 Battery and MicroSD 14 USB interfaces X104 X105 15 EtherCAT interface X103 16 Ethernet interface X102 17 Status LEDs 18 Connection of the power supply and protec...

Страница 17: ...ppropriate packaging of the Panel PC in particular the original packaging can improve the vibration resistance during transport NOTE Hardware damage due to condensation Unfavorable weather conditions...

Страница 18: ...5 mm After installation be sure to check the tightness between the Panel PC and the built in wall All dimensions are in mm Figure 9 shows the dimensions of the Panel PC without push button extension 4...

Страница 19: ...as possible For the correct installation height use the position of the screen for guidance This should always be optimally visible to the user Do not expose the Panel PC to direct sunlight Installati...

Страница 20: ...d underneath the device see Fig The installation frame must not protrude beyond the wall plaster and must be no more than 5 mm deeper You must mount the mounting frame horizontally You cannot subseque...

Страница 21: ...Commissioning CP6606 21 Version 2 0 A B C D Fig 12 CP6606_Wall installation with wall mounting frame...

Страница 22: ...ply must have the same potential for the PE and 0 V conductors as the Panel PC no potential difference 4 3 1 Assembly of the supply cable Install the cable for the power supply of the Panel PC using t...

Страница 23: ...n relief housing To remove the strain relief housing proceed as follows 1 Use your fingers to bend the latching lugs on the lower part slightly outward see Fig 14 2 Lever the upper part off the lower...

Страница 24: ...ge connection to avoid dangerous touch voltages There is a pin in the voltage socket for the protective earth PE EMC NOTE Hardware damage due to electromagnetic interference The use of the Panel PC wi...

Страница 25: ...d then plug in all data transmission lines Connecting the power supply Cables with a maximum cable cross section of 1 5 mm2 can be used for connecting the power supply For long supply lines use 1 5 mm...

Страница 26: ...re for the additional hardware you have connected and for the devices in the PC yourself Please follow the instructions in the documentation for the operating system and the additional devices Switchi...

Страница 27: ...to electric shock Never disconnect the cables from the device during thunderstorms Before you remove the Panel PC from the control cabinet you must follow the following steps 1 Shut down the operating...

Страница 28: ...net front follow the steps shown in Fig 16 1 Loosen the clamping levers with a 2 5 mm Allen key sections A and B 2 Fold the clamping levers back by 90 onto the housing section C You can now remove the...

Страница 29: ...erve the following points when cleaning the PC Keep to the boundary conditions of protection rating IP65 Never use compressed air to clean the PC Maintain an ambient temperature range of 0 C to 55 C N...

Страница 30: ...iability in the event of possible damage occurring during maintenance work In order to avoid damage caused by electrostatic discharge when replacing device components protective measures are recommend...

Страница 31: ...use fire or explosion Only replace the battery with a replacement battery from Beckhoff Service When replacing the battery make sure that the polarity is correct NOTE Battery damage Incorrect handling...

Страница 32: ...em You can then restore the images created in this way The BST is available on a bootable BST USB flash drive This includes Windows and a backup software Select the size of the BST USB flash drive acc...

Страница 33: ...ect the cable 2 Call Beckhoff Service Panel PC boots software starts but controller does not work properly The cause of the error is the software or plant parts outside of the Panel PC Call the machin...

Страница 34: ...tance shock EN 60068 2 27 5 G 50 m s2 duration 30 ms EMC interference immunity conforms to EN 61000 6 2 EMC interference emission conforms to EN 61000 6 4 Permissible ambient temperature Operation 0 C...

Страница 35: ...an be found on the name plate Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide...

Страница 36: ...ainst adverse interference if the device is used in a commercial environment This device generates uses and may emit radio frequency energy and may cause adverse interference with radio communications...

Страница 37: ...me plate 15 Fig 9 CP6606_dimensions 18 Fig 10 CP6606_dimensions push button extension 18 Fig 11 CP6606_control cabinet installation 19 Fig 12 CP6606_Wall installation with wall mounting frame 21 Fig 1...

Страница 38: ...ace pin assignment 12 Table 4 USB interface pin assignment 12 Table 5 RS232 pin assignment 13 Table 6 Meaning of the TC LED 14 Table 7 Meaning of the PWR LED 14 Table 8 Key name plate CP6606 16 Table...

Страница 39: ......

Страница 40: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com CP6606...

Отзывы: