background image

Commissioning

C6017

24

Version: 2.1

4.2.2

Dimensions

The dimensions of the Industrial PC and the mounting plates are used to prepare the control cabinet and to
mount the device correctly in the control cabinet.

All dimensions are in mm.

Fig. 16 gives an example of the dimensions using the mounting option via the rear of the device with
mounting plate 1.

 

4,2mm

8

8

43,8

81,9

90

+/-

9

6

90,9

8

2

3,5

65,9

Fig. 16: C6017 _Mounting plate narrow side

Fig. 17 shows the dimensions using the mounting option with the connections pointing to the right with
mounting plate 2 as an example.

1

0

0

8

9

,5

72

8

2

82

 

4,5mm

90

+

/-

69,3

Fig. 17: C6017 _Mounting plate side panel

Fig. 18 illustrates the dimensions using the mounting options via the rear of the device with mounting plate 3
with DIN rail adapter as an example.

3

4

,2

30

32,3

8

2

102

6

8

81,9

3,5

65,9

47

,

3

90

+/-

 

 
 

 

 

 

 

 

 

 

 

 

Fig. 18: C6017 _Mounting plate DIN rail adapter

Содержание C6015-0010

Страница 1: ...Manual EN C6017 Industrial PC 01 22 2021 Version 2 1...

Страница 2: ......

Страница 3: ...15 3 4 1 PWR LED 16 3 4 2 HDD LED 17 3 4 3 TC LED 17 3 5 Name plate 18 3 6 1 second UPS 19 4 Commissioning 20 4 1 Transport and unpacking 20 4 2 Installation in the control cabinet 21 4 2 1 Mounting...

Страница 4: ...Table of contents C6017 4 Version 2 1 8 Troubleshooting 42 9 Technical data 43 10 Appendix 44 10 1 Service and support 44 10 2 Approvals 45...

Страница 5: ...erCAT EtherCAT P Safety over EtherCAT TwinSAFE XFC and XTS are registered and licensed brands of Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by thi...

Страница 6: ...ious injuries WARNING Disregarding the safety notice may lead to death or serious injuries CAUTION Disregarding the safety notice may lead to minor injuries Warning of damage to property NOTE Disregar...

Страница 7: ...tion and power dissipation please refer to the respective data sheet Ensure that only trained specialists with a control and automation technology background operate the Industrial PC Use by unauthori...

Страница 8: ...applications among others diverse automation and visualization tasks axis control wide range of IoT tasks for example when used as an IoT gateway simple HMI applications short cycle times high volume...

Страница 9: ...2 0 interfaces X203 X204 Connection of peripheral devices USB 2 0 standard supported 6 USB interface X106 Connection of peripheral devices 7 USB interface X105 Connection of peripheral devices 8 Displ...

Страница 10: ...ndustrial PC The main supply voltage is applied between PIN 3 0 V and PIN 4 24 V of the socket X101 1 2 3 4 Fig 2 C6017_Power socket pin numbering Table 2 Power socket pin assignment Pin Signal Descri...

Страница 11: ...rations Generation Controller C6017 0010 Intel i210 for LAN1 and LAN2 C6017 0020 Intel i210 for LAN1 and LAN2 X102 X103 8 1 1 8 LAN1 LAN2 Fig 3 C6017_Ethernet interface pin numbering Table 4 Ethernet...

Страница 12: ...7 0010 1x USB 2 0 X105 1x USB 3 0 X106 C6017 0020 2x USB 3 0 X105 X106 The two USB interfaces each supply up to 500 mA current and are electronically protected For USB 2 0 only the first four pin assi...

Страница 13: ...rt signals are led out via the interface by default With the use of a level shifter cable the board switches the DisplayPort specification automatically to HDMI signals 1 2 19 20 X104 Fig 5 C6017_Disp...

Страница 14: ...ect peripheral devices with USB interfaces 1 2 3 4 4 3 2 1 Fig 6 C6017_USB interface pin numbering Table 8 USB interface pin assignment Pin Connection Typical assignment 1 VBUS Red 2 D White 3 D Green...

Страница 15: ...the LED is not lit At 100 Mbit s the LED lights up orange at 1000 Mbit s it lights up green 3 3 3 RS232 The additional RS232 interfaces include two electrically isolated 9 pin D Sub sockets The interf...

Страница 16: ...White Steadily lit VCC power fail Magenta Steadily lit S UPS active if existent Yellow Steadily lit Windows shut down supply voltage still present Green Steadily lit Normal operation Red Steadily lit...

Страница 17: ...he HDD LED Color Flashing interval Meaning Red Flashing Activity access to storage medium 3 4 3 TC LED The TC LED indicates the TwinCAT status The colors and flashing intervals have the following mean...

Страница 18: ...y C6017 name plate No Description 1 Manufacturer including address 2 Model The last four digits indicate the device generation 3 Serial number BTN 4 Date of manufacture 5 Mainboard 6 CPU 7 Main memory...

Страница 19: ...factory by specifying the order identifier C9900 U215 The capacitive 1 second UPS continues to supply the processor with power if the power supply fails During this period persistent data can be save...

Страница 20: ...iate packaging of the Industrial PC in particular the original packaging can improve the vibration resistance during transport NOTE Hardware damage due to condensation Unfavorable weather conditions d...

Страница 21: ...ox 0 5 Nm You can turn all mounting plates before fastening them such that the PC can be mounted in the desired orientation for the cable entry in the control cabinet see Chapter 4 2 1 Mounting option...

Страница 22: ...ounting plate 1 you can mount the Industrial PC in the control cabinet using the narrow sides You have the following mounting options which are shown in Fig 13 Mounting via the rear of the device A Mo...

Страница 23: ...e Industrial PC on the DIN rail in the control cabinet via the narrow sides You have the following mounting options which are shown in Fig 15 Mounting via the rear of the device A Mounting via the top...

Страница 24: ...ing plate 1 4 2mm 88 43 8 81 9 9 0 96 90 9 82 3 5 65 9 Fig 16 C6017 _Mounting plate narrow side Fig 17 shows the dimensions using the mounting option with the connections pointing to the right with mo...

Страница 25: ...C see Chapter 4 2 2 Dimensions 24 You need M4 screws for mounting After you have drilled the holes for the fastening screws in the control cabinet you can mount the Industrial PC in the control cabine...

Страница 26: ...e of the adapter into the DIN rail A 2 Push the device upwards so that the spring contacts of the adapter are pressed in B 3 Keep the device pressed upwards and also hook the upper side of the adapter...

Страница 27: ...supply An external power supply unit is required to supply 24 V DC 15 20 for operating the device Wire the Industrial PC in the control cabinet in accordance with the EN 60204 1 2006 standard on Prot...

Страница 28: ...ive earthing of the Industrial PC and thus avoid dangerous touch voltages EMC NOTE Hardware damage due to electromagnetic interference Using the Industrial PC without functional earthing can lead to h...

Страница 29: ...Connecting the power supply Cables with a maximum cable cross section of 1 5 mm2 must be used for connecting the power supply To achieve the lowest possible voltage drop on the supply cable we recomm...

Страница 30: ...e PC If you have ordered the PC without an operating system you must install this and the driver software for the additional hardware you have connected and for the devices in the PC yourself Please f...

Страница 31: ...using the Beckhoff Device Manager to configure the Industrial PC remotely via a web browser More detailed information is available in the Beckhoff Device Manager manual First start Beckhoff Device Ma...

Страница 32: ...passwords Strong passwords are an important prerequisite for a secure system Beckhoff supplies the device images with standard user names and standard passwords for the operating system It is imperati...

Страница 33: ...moresecure Abbreviate words or remove all vowels Cmplxpsswrdsrmrscr Insert numbers and special characters to extend the password Cmplxpsswrdsrmrscr 529954 The following passwords are not secure Words...

Страница 34: ...c shock Never disconnect the cables of the Industrial PC during a thunderstorm Before you remove the Industrial PC from the control cabinet you must follow the following steps 1 Shut down the Industri...

Страница 35: ...e PC until the fastening screws slide into the keyholes see Fig 25 3 Remove the PC from the control cabinet You have successfully disassembled the PC Fig 25 C6017 _Position of the fastening screws Dis...

Страница 36: ...er to dispose of the device it must be removed and fully dismantled Dispose of the components in the following way Send plastic parts polycarbonate polyamide PA6 6 for plastics recycling Take metal pa...

Страница 37: ...and the replacement of other device components contribute to this Repair Only the manufacturer may repair the device If a repair should be necessary contact Beckhoff Service see Chapter 10 1 Service...

Страница 38: ...ponent Recommendation for replacement intervals years UPS battery pack 5 years 2 5 inch hard disk 5 years or after 20 000 operating hours at more than 40 C or after 30 000 operating hours at less than...

Страница 39: ...still protect the device against ESD damage The following means can be used for this purpose Wrist grounding strap Conductive mats connected to the ground potential for temporary storage of component...

Страница 40: ...oard If the battery is depleted or missing the date and time are displayed incorrectly Replacement batteries should only be obtained from Beckhoff Service see Chapter 10 1 Service and support Table 18...

Страница 41: ...sponding documentation If your SSD is defective and no backup copy of the data is available Beckhoff Service will provide you with a fresh Windows image In this case the applications must be reinstall...

Страница 42: ...PC Other cause Check the power supply cable Call Beckhoff Service The Industrial PC does not boot fully Setup settings are incorrect Other cause Check the setup settings Call Beckhoff Service Computer...

Страница 43: ...EN 60068 2 6 10 to 58 Hz 0 035 mm 58 to 500 Hz 0 5 G approx 5 m s2 Shock resistance shock EN 60068 2 27 5 G approx 50 m s2 duration 30 ms EMC interference immunity conforms to EN 61000 6 2 EMC interf...

Страница 44: ...PC which can be found on the name plate Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with...

Страница 45: ...to provide adequate protection against adverse interference if the device is used in a commercial environment This device generates uses and may emit radio frequency energy and may cause adverse inte...

Страница 46: ...ounting options for mounting plate 2 22 Fig 15 Mounting options for mounting plate 3 23 Fig 16 C6017 _Mounting plate narrow side 24 Fig 17 C6017 _Mounting plate side panel 24 Fig 18 C6017 _Mounting pl...

Страница 47: ...ment of DisplayPort 13 Table 8 USB interface pin assignment 14 Table 9 Ethernet interface pin assignment 15 Table 10 RS232 pin assignment 15 Table 11 Meaning of the PWR LED 16 Table 12 Meaning of the...

Страница 48: ......

Страница 49: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com C6017...