Product overview
C6017
16
Version: 2.1
• the TwinCAT status
• the hard disk activity
PWR
TC
HDD
Fig. 9: Status LEDs
3.4.1
PWR LED
The PWR (power) LED indicates the status of the power controller. The colors and flashing intervals have
the following meanings:
Table 11: Meaning of the PWR LED
Color
Flashing interval
Meaning
None
Steadily lit
PC is off
White
Steadily lit
VCC power fail
Magenta
Steadily lit
S UPS active (if existent)
Yellow
Steadily lit
Windows shut down, supply
voltage still present
Green
Steadily lit
Normal operation
Red
Steadily lit
Reset/power fail
Green/yellow
Flashing
Bootloader running without error
Red/yellow
Flashing
Bootloader is starting (start
sequence is being run through)
Magenta
Flashing (0.5 s)
S UPS capacitance test (if S UPS
exists)
Red/magenta
Flashing
Checksum error during the I2C
transmission in the bootloader
Cyan
Flashing (2 s)
contact Beckhoff Service