Error handling and diagnosis
BK9053, BK9103
41
Version: 2.3.0
LEDs for PROFINET diagnostics
PROFINET diagnosis
PN Err (red) PN Run (green)
DIAG E (red)
DIAG R (green)
IP Address OK
off
0,5 s
x
x
No IP valid Address (Dip Switch 9,10 ->
on)
0,1 sec
off
x
x
Online
off
on
x
x
Offline PLC Stop
off
0,1 s
x
x
TimeOut
0,5 s
off
x
x
IP address configuration fault
on
off
x
x
Alternate flashing (triggered by a
Profinet tool)
0.5 sec
0.5 sec
x
x
Configuration Diagnose
PN Err (red) PN Run (green)
DIAG E (red)
DIAG R (green)
OK
x
x
off
on
Wrong module
x
x
Slot number
1
Missing module (physical)
x
x
Slot number
2
Missing module (in the configuration)
x
x
Slot number
3
No PROFINET name assigned
x
x
0
4
Substitute
x
x
Slot number
5
x: The status of the LED is not relevant for this diagnosis.
Note:
• In the event of several errors the last faulty module is displayed.
• Substitute is set for incorrectly configured modules that are nevertheless executable (example: KL2xx2
was configured but KL2xx4 was inserted in the slot)
Sample
You have configured a KL2xx4 for the fifth slot, but in fact only four modules are inserted.
• Start Error Code: Red DIAG E LED flickers rapidly, green DIAG R LED is off
• Red DIAG E LED is on, green LED shows the error code and flashes twice (0.5 sec)
• Red and green LED off
• Red DIAG E LED shows the error argument and flashes 5 times (0.5 sec, in this case the slot number),
green LED is off
Fig. 24: Example for Error Code and Error Argument