Parameterization and Commissioning
BC8050 und BC8150
27
Version: 3.0.0
◦ TwinCAT 2.9 build 946
(
NOTE:
with PROFIBUS cards from Hilscher only one ADS communication is permitted, i.e.
either System Manager or PLC Control)
CANopen: (BC5150, BX5100)
◦ PC with FC510x from version 1.76 TwinCAT build 1030
DeviceNet: (BC5250, BX5200)
◦ on request
Ethernet: (BC9050, BC9020, BC9120, BX9000)
◦ PC with TwinCAT 2.10 build 1322
• Via the serial ADS TwinCAT 2.9 build 1010
◦ BX3100 version 1.00
◦ BX5100 version 1.00
◦ BX5200 version 1.10
◦ BX8000 version 1.00
◦ BC3150, BC5150, BC5250, BC9050, BC9020, BC9120 from firmware B0
◦ For BC8150 from TwinCAT 2.10 build 1243
BCxx50 and BXxx00 can be parameterized via the System Manager of the TwinCAT program.
• Variable I/O mapping
• Type-specific PROFIBUS data (BC3150 and BX3100 only)
• RTC (real-time clock) (BX series only)
• SSB (Smart System Bus) (BX series only)
• PLC settings
• K-Bus settings
The configuration can be transferred to the BCxx50 or BXxx00 via fieldbus ADS protocol or serial ADS
protocol.
The TwinCAT configuration can be used to link variables, I/Os and data. The following is possible:
• PLC - K-BUS
• PLC fieldbus (e.g. PROFIBUS slave interface to PLC)
• K-bus fieldbus (only for BX controllers)
• Support for TwinSAFE terminals (only BX controllers from firmware 1.17)
In addition, the TwinCAT configuration can be used to parameterize special behavior, for example whether
data are preserved or set to "0" in the event of a fieldbus error.
The real-time clock can be set via a tab in the system manager.
Work steps
1. Setting the fieldbus address
2. Open the System Manager and create a TC file
3. Configure fieldbus data in the TC file
4. Save the TC file
5. Opening a new system manager, creating a PC file and reading in saved TX file
6. Creating a link to a PLC task
7. Saving the configuration
8. Starting the TwinCAT system
9. Open the TC file in the System Manager, complete the configuration and transfer it to the BCxx50,
BCxx20 or BXxx00
10. Transfer the program to BCxx50, BCxx20 or BXxx00
11. Creating a boot project