background image

7

12Vdc SDC 

Burner Manual

Fuel Supply

A. Connect Fuel Lines

For oil supply system speci

fi

 cations for tanks not mounted 

on machines, carefully follow the pump manufacturer’s 
literature and the latest edition of the National Fire 
Protection Association (NFPA) 31 standard.  

The burner may be equipped with a single stage pump. If 
a one-pipe system is installed, insure that a bypass plug 
is not installed in the pump, then connect the fuel supply 
to the burner with a single supply line Note that manual 
bleeding of the pump is required on initial start-up or when 
the equipment runs out of fuel. When connecting a two-
pipe fuel system, install the pump by-pass plug.

C. Fuel Supply Below Level of Burner

When the fuel supply is more than eight feet below the level 
of the burner, a two-pipe fuel supply system is required. 
Depending on the fuel line diameter and the horizontal 
and vertical length, the installation may also require a 
two-stage pump. Consult the fuel unit manufacturer’s 
literature for lift and vacuum capability. 

D. Fuel Line Replacement (Remote Tank Only)

When replacing fuel lines, continuous lengths of heavy 
wall copper tubing is recommended. To ensure a tight 
seal, always use 

fl

 are 

fi

 ttings. Never use compression 

fi

 ttings. Always install 

fi

 ttings in an accessible location. To 

avoid vibration noise,  fuel lines should not run against the 
appliance or the ceiling joists.

E.  Fuel Line Valve and Filter

Shutoff valves should be located in the oil supply line. Do 
not install valves in the return line.

Burner Wiring

B. Fuel Supply Level with or Above Burner

Pumps with automatic bypass do 
not require a bypass plug. Verify by 

referring to the pump manufacturer’s instructions.

A. Burner installed on equipment

Refer to appliance manufacturer’s wiring diagram for 
electrical connections. 

B. Burner Replacement

Burner wiring may vary, depending on the actual
primary control and furnished options. Refer to Figure 
6 for typical burner wiring, showing cad cell primary 
controls. Note that the relay and control, shown in the 
wiring diagram are optional features.

Section: Fuel Supply & Burner Wiring

Do Not Install Bypass Plug 
with 1-Pipe System

Failure to comply could cause Immediate pump seal 

failure, pressurized oil leakage and the potential for a 

fi

 re and injury hazard. 

 

y

The burner is shipped without the by-pass plug 
installed.

 

y

Install the bypass plug in two-pipe oil supply systems 
ONLY. 

Oil Supply Pressure 
Control Required

Damage to the 

fi

 lter or pump seals could cause oil 

leakage and a 

fi

 re hazard.

 

y

The oil supply inlet pressure to the burner 

cannot 

exceed 3 psig

.  

 

y

Insure that a pressure limiting device is installed in 

accordance with the latest edition of NFPA 31. 

 

y

Do NOT install valves in the return line.

 (NFPA 31, 

Chapter 8.)

 

y

Gravity Feed Systems:

 Always install an anti-siphon 

valve in the oil supply line or a solenoid valve (RWB 
Part # 21441U) in the pump/nozzle discharge tubing 
to provide backup oil 

fl

 ow cut-off protection. 

Do Not Use Te

fl

 on Tape

Damage to the pump could cause impaired burner 

operation, oil leakage and appliance soot-up.

 

y

Never use Te

fl

 on tape on fuel oil 

fi

 ttings. 

 

y

Tape fragments can lodge in fuel line components 

and fuel unit, damaging the equipment and preventing 

proper operation.

 

y

Use oil-resistant pipe sealant compounds.

Electrical Shock Hazard

Electrical shock can cause severe personal injury or 

death.

 

y

Disconnect electrical power before installing or 

servicing the burner.

 

y

Provide ground wiring to the burner, metal control 

enclosures and accessories. (This may also be 

required to aid proper control system operation.)

Содержание 12Vdc SDC

Страница 1: ...art up or service work y READ THESE INSTRUCTIONS AND SAVE FOR REFERENCE Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property...

Страница 2: ...Coupling Replacement 9 B Pump Maintenance 10 C Solenoid Valve Testing 10 Start Up Burner Set Combustion 10 A Basic Burner Operation 10 B Combustion Set up 11 C Set Combustion with Instruments 11 Main...

Страница 3: ...this burner y Never restrict the air inlet openings to the burner or the combustion air ventilation openings in the room Impaired Burner Performance and Fire Hazard Do NOT operate the burner beyond s...

Страница 4: ...Information Nozzle Assembly Maintenance Adequate Voltage Required A low or erratic power supply could result in impaired burner operation severe delayed ignition or an explosion inside the heat excha...

Страница 5: ...mple A 1 00 gph nozzle at 140 psig 1 18 gph Securely tighten the nozzle 90 torque inch pounds For typical nozzle flow rates at various pressures refer to Table 2 Use care when removing or installing a...

Страница 6: ...while handling To ease removal of short assemblies it may be necessary to loosen the escutcheon plate Reset to the edge of the label 5 To replace the nozzle line assembly reverse the above steps E Ch...

Страница 7: ...urner installed on equipment Refer to appliance manufacturer s wiring diagram for electrical connections B Burner Replacement Burner wiring may vary depending on the actual primary control and furnish...

Страница 8: ...to be sized to prevent a voltage drop between battery and burner with burner running at full load 2 Motor runs continuously in normal confi guration 3 Hard wire burner ground to battery DO NOT USE CH...

Страница 9: ...rner and perform the combustion test described previously in this manual Figure 7 Blower Wheel Section Drive Component Maintenance CENTER WHEEL FOR EQUAL DISTANCE FROM HOUSING SIDES Figure 6C Typical...

Страница 10: ...ion A Basic Burner Operation Typical Constant Duty Ignition Configuration With this Beckett ADC oil burner configuration the motor and igniter operate continuously while the valve that controls oil fl...

Страница 11: ...ustment of oil burners using combustion test instruments The installation must strictly comply with all applicable codes authorities having jurisdiction and the latest revision of the National Fire Pr...

Страница 12: ...triction Clean the equipment thoroughly according to the manufacturer s recommendations Check the burner performance using test instruments It is good practice to make a record of the service performe...

Страница 13: ...l in the tank In addition to normal mechanics tools it is recommended to have the following equipment on hand Meter capable of measuring volts ohms and amps ignition transformer tester smoke pump test...

Страница 14: ...ibilities 1 Check voltage at the motor to insure that switches and relays in line with the motor are operating properly Refer to section Burner Wiring 2 Check pump and motor shaft operation They shoul...

Страница 15: ...4 9 Oil Valve Specify 10 Brass Elbow 2256 11 Cord Set Valve 21807 12 Splined Nut 3666 Illustration Description Part 13 Escutcheon Plate 3493 14 Electrode Kit over 3 5 8 578731 15 Cad Cell Detector 700...

Страница 16: ...copy of warranty form 61545 please choose one of the following options 1 Visit our website at www beckettcorp com warranty 2 Email your request to rwb customer service beckettcorp com 3 Write to R W...

Отзывы: