background image

6

C. Igniter Maintenance

The igniter assembly does not require any adjustments 
beyond making sure the springs and the burner electrode 
rods make solid contact when the igniter is in the closed 
position. The sealing surfaces of the gaskets should be 
checked and replaced at the 

fi

 rst signs of any damage or 

deterioration. Clean any dirt or residue from the porcelain 
bushings, springs, and baseplate.

The simplest way to check igniter operation is by supplying 
voltage to the input and checking to see whether an arc 
is produced. Check by either looking or listening to see if 
there is an arc across the electrodes while the burner is 
running and the igniter is energized.

The igniter must be grounded to the burner before 
checking the following. To check the igniter, ensure all 
power to the burner is off and use an ohmmeter to check 
the resistance between the two springs.  The meter should 
read between 480 - 580 ohms.

The igniter should be replaced if the meter indicates an 
open circuit, or the spring-to-spring resistance exceeds 
the 480 - 580 ohms range by more than 10%.

D. Servicing Nozzle Line Assembly

Before proceeding, turn off power to the burner.

1.  Disconnect the oil connector tube from the nozzle 

line.

2.  Referring to Figure 4, loosen the two screws securing 

the igniter retaining clips and rotate both clips to 
release the igniter baseplate. Then tilt the igniter 
back on its hinge.

3.  Remove the splined nut.
4.  Remove the nozzle line assembly from the burner, 

being careful not to damage the electrodes or 

insulators while handling. To ease removal of short 
assemblies, it may be necessary to loosen the 
escutcheon plate. Reset to the edge of the label.

5.  To replace the nozzle line assembly, reverse the 

above steps.

E. Check/Adjust “Z” Dimension

Refer to 

Figure 5

. The critical “Z” dimension is the 

distance from the face of the nozzle to the 

fl

 at face of 

the head. This distance for F heads is 1-1/8”. The “Z” 
dimension is factory set for burners shipped with the air 
tube installed but should always be veri

fi

 ed during service 

and installation. If the “Z” dimension is out of adjustment, 
perform the following steps.

Before proceeding, turn off power to the burner.

1.  Disconnect the oil connector tube from the nozzle 

line.

2. Referring to 

Figure 4

, loosen the splined nut 

(a) 

from the nozzle line. Loosen the hex head screw 

(b)

 securing the escutcheon plate to the burner 

housing.

3.  A Beckett T650 gauge should be used to set the Z 

dimension.  See 

Figure 5

.

4.  Place the end of a ruler at the face of the nozzle and, 

using a straight edge across the head, measure the 
distance to the face of the head.

5. Slide the nozzle line forward or back until this 

dimension for F heads is 1-1/8”.

6.  Tighten the hex head screw to secure the escutcheon 

plate to the burner chassis. Then tighten the splined 
nut and attach the oil connector tube.

7. Recheck the “Z” dimension periodically when 

servicing to ensure the escutcheon plate has not 
shifted. You will need to reset the “Z” dimension if 
you replace the air tube or nozzle line assembly.

The Beckett Z gauge (part number Z-

2000) is available to permit checking 

the F head “Z” dimension without removing the burner.

Figure 4. Igniter Retainer Screws

Figure 5. ‘Z’ Dimensions Using Gauge

SK9787

Section: Nozzle Assembly Maintenance

a

b

Содержание 12Vdc SDC

Страница 1: ...art up or service work y READ THESE INSTRUCTIONS AND SAVE FOR REFERENCE Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property...

Страница 2: ...Coupling Replacement 9 B Pump Maintenance 10 C Solenoid Valve Testing 10 Start Up Burner Set Combustion 10 A Basic Burner Operation 10 B Combustion Set up 11 C Set Combustion with Instruments 11 Main...

Страница 3: ...this burner y Never restrict the air inlet openings to the burner or the combustion air ventilation openings in the room Impaired Burner Performance and Fire Hazard Do NOT operate the burner beyond s...

Страница 4: ...Information Nozzle Assembly Maintenance Adequate Voltage Required A low or erratic power supply could result in impaired burner operation severe delayed ignition or an explosion inside the heat excha...

Страница 5: ...mple A 1 00 gph nozzle at 140 psig 1 18 gph Securely tighten the nozzle 90 torque inch pounds For typical nozzle flow rates at various pressures refer to Table 2 Use care when removing or installing a...

Страница 6: ...while handling To ease removal of short assemblies it may be necessary to loosen the escutcheon plate Reset to the edge of the label 5 To replace the nozzle line assembly reverse the above steps E Ch...

Страница 7: ...urner installed on equipment Refer to appliance manufacturer s wiring diagram for electrical connections B Burner Replacement Burner wiring may vary depending on the actual primary control and furnish...

Страница 8: ...to be sized to prevent a voltage drop between battery and burner with burner running at full load 2 Motor runs continuously in normal confi guration 3 Hard wire burner ground to battery DO NOT USE CH...

Страница 9: ...rner and perform the combustion test described previously in this manual Figure 7 Blower Wheel Section Drive Component Maintenance CENTER WHEEL FOR EQUAL DISTANCE FROM HOUSING SIDES Figure 6C Typical...

Страница 10: ...ion A Basic Burner Operation Typical Constant Duty Ignition Configuration With this Beckett ADC oil burner configuration the motor and igniter operate continuously while the valve that controls oil fl...

Страница 11: ...ustment of oil burners using combustion test instruments The installation must strictly comply with all applicable codes authorities having jurisdiction and the latest revision of the National Fire Pr...

Страница 12: ...triction Clean the equipment thoroughly according to the manufacturer s recommendations Check the burner performance using test instruments It is good practice to make a record of the service performe...

Страница 13: ...l in the tank In addition to normal mechanics tools it is recommended to have the following equipment on hand Meter capable of measuring volts ohms and amps ignition transformer tester smoke pump test...

Страница 14: ...ibilities 1 Check voltage at the motor to insure that switches and relays in line with the motor are operating properly Refer to section Burner Wiring 2 Check pump and motor shaft operation They shoul...

Страница 15: ...4 9 Oil Valve Specify 10 Brass Elbow 2256 11 Cord Set Valve 21807 12 Splined Nut 3666 Illustration Description Part 13 Escutcheon Plate 3493 14 Electrode Kit over 3 5 8 578731 15 Cad Cell Detector 700...

Страница 16: ...copy of warranty form 61545 please choose one of the following options 1 Visit our website at www beckettcorp com warranty 2 Email your request to rwb customer service beckettcorp com 3 Write to R W...

Отзывы: