background image

10

B. Pump Maintenance

General Pump Information

Important information - Long or oversized inlet lines may 
require the pump to operate dry during initial bleeding 
period. In such cases, the priming may be assisted 
by injecting fuel oil in the pump gear set. Under lift 
conditions, lines and 

fi

 ttings must be air tight. To assure 

this, “Pipe Dope” may be applied to both the used and 
unused inlet and return 

fi

 ttings. 

Do NOT use Te

fl

 on tape 

or compression 

fi

 ttings

Mounting Position

Beckett CleanCut pump may be mounted in any position 
(except upside-down in a  single pipe installation).

Vacuum Check

A Vacuum Gauge may be installed in either of the 1/4” 
NPT inlet ports.

Pressure Check

When a pressure check is made use the nozzle port. If 
the bleed port is used, the reading on the gauge should 
be approximately 5 psig higher than the pressure reading 
on the nozzle port. See 

Figure 9

.

Cutoff Check

To check cutoff pressure dead head a pressure gauge 
in the nozzle port. Run the burner for a short period of 
time. Shut the burner off. The pressure will drop and hold 
above zero. Pressurized or gravity feed installations must 
not exceed 3 psi on inlet line or return line at the pump 
per NFPA 31. A pressure greater than 10 psi may cause 
damage to the shaft seal.

Pressurized or Gravity Feed Installations

Must not exceed 3 psi on inlet line or return line at the 
pump per NFPA 31.  A pressure greater than 10 psi may 
cause damage to the shaft seal.

C. Solenoid Valve Testing

To check solenoid operation, perform the following.

1. Check for oil 

fl

 ow and operating pressure by 

removing the copper tubing from the nozzle line 
and installing a pressure gauge in the line. With 
the motor running and the coil energized, check the 
gauge. The pressure should read 100 psig unless 
otherwise stated.

2.  To check the solenoid valve cutoff function, deadhead 

the pressure gauge onto the copper connector tube 
attached to the nozzle port. Run the burner for a 
short period of time. Shut the burner off. The solenoid 
valve should close and the pressure should drop and 
hold.

3.  Replace the solenoid valve if it does not pass the 

steps above. 

Start Up Burner & Set 

Combustion

A. Basic Burner Operation

Typical Constant Duty Ignition Con

fi

 guration

With this  Beckett ADC oil burner con

fi

 guration, the motor 

and igniter operate continuously while the valve that 
controls oil 

fl

 ow is cycled by the switches on the power 

washer. The motor is used to drive the blower and pump. 
The rotational speed of the motor is determined by the 
voltage supplied and the load placed on the motor. Pump 
pressure and air settings are the main factors affecting 
the motor load. The igniter converts battery DC voltage 
into a high voltage spark to ignite the oil. The igniter is 
capable of running continuously as long as the blower 
wheel is circulating air across the igniter base. The pump 
and solenoid valve are used to control the 

fl

 ow of oil from 

the reservoir to the nozzle. 

Igniter With Interrupted Duty Ignition

This optional control circuit is available to reduce current 
draw on the charging system by turning the igniter off after 

fl

 ame has been established. This option controls igniter 

operation based on a signal from a light sensing cad cell. 
When light hits the cell the control will sense a decrease 
in resistance across the sensor. A few seconds delay will 
occur prior to the igniter switching off. As long as suf

fi

 cient 

light is reaching the cell eye, the igniter will remain off. If 
light is removed from the sensor, the igniter will turn on 
until light is again sensed by the cad cell. 

With 7556 Primary Safety Control

The 7556 control provides the same bene

fi

 ts as described 

above, as well as added safety, convenience, and 
performance features. It adds a valve on delay and motor-
off delay to the burner’s operation sequence that promote 
clean burner operation. It has a lock-out function that shuts 
the burner down if it is not operating properly. The control 
adds fusing at the burner to protect against component 
failures. The control also has redundant motor relays that 
are checked for proper operation every heat cycle. 

Variations to the burner circuits may 
occur due to optional temperature, 

pressure, and vacuum switches that control burner 
operation. Note that when external switches are used to 
control motor operation they must be sized correctly for 
the rated current or a relay should be installed to isolate 
the switches from the motor’s full load current. 

Section: Start Up Burner & Set Combustion

Содержание 12Vdc SDC

Страница 1: ...art up or service work y READ THESE INSTRUCTIONS AND SAVE FOR REFERENCE Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property...

Страница 2: ...Coupling Replacement 9 B Pump Maintenance 10 C Solenoid Valve Testing 10 Start Up Burner Set Combustion 10 A Basic Burner Operation 10 B Combustion Set up 11 C Set Combustion with Instruments 11 Main...

Страница 3: ...this burner y Never restrict the air inlet openings to the burner or the combustion air ventilation openings in the room Impaired Burner Performance and Fire Hazard Do NOT operate the burner beyond s...

Страница 4: ...Information Nozzle Assembly Maintenance Adequate Voltage Required A low or erratic power supply could result in impaired burner operation severe delayed ignition or an explosion inside the heat excha...

Страница 5: ...mple A 1 00 gph nozzle at 140 psig 1 18 gph Securely tighten the nozzle 90 torque inch pounds For typical nozzle flow rates at various pressures refer to Table 2 Use care when removing or installing a...

Страница 6: ...while handling To ease removal of short assemblies it may be necessary to loosen the escutcheon plate Reset to the edge of the label 5 To replace the nozzle line assembly reverse the above steps E Ch...

Страница 7: ...urner installed on equipment Refer to appliance manufacturer s wiring diagram for electrical connections B Burner Replacement Burner wiring may vary depending on the actual primary control and furnish...

Страница 8: ...to be sized to prevent a voltage drop between battery and burner with burner running at full load 2 Motor runs continuously in normal confi guration 3 Hard wire burner ground to battery DO NOT USE CH...

Страница 9: ...rner and perform the combustion test described previously in this manual Figure 7 Blower Wheel Section Drive Component Maintenance CENTER WHEEL FOR EQUAL DISTANCE FROM HOUSING SIDES Figure 6C Typical...

Страница 10: ...ion A Basic Burner Operation Typical Constant Duty Ignition Configuration With this Beckett ADC oil burner configuration the motor and igniter operate continuously while the valve that controls oil fl...

Страница 11: ...ustment of oil burners using combustion test instruments The installation must strictly comply with all applicable codes authorities having jurisdiction and the latest revision of the National Fire Pr...

Страница 12: ...triction Clean the equipment thoroughly according to the manufacturer s recommendations Check the burner performance using test instruments It is good practice to make a record of the service performe...

Страница 13: ...l in the tank In addition to normal mechanics tools it is recommended to have the following equipment on hand Meter capable of measuring volts ohms and amps ignition transformer tester smoke pump test...

Страница 14: ...ibilities 1 Check voltage at the motor to insure that switches and relays in line with the motor are operating properly Refer to section Burner Wiring 2 Check pump and motor shaft operation They shoul...

Страница 15: ...4 9 Oil Valve Specify 10 Brass Elbow 2256 11 Cord Set Valve 21807 12 Splined Nut 3666 Illustration Description Part 13 Escutcheon Plate 3493 14 Electrode Kit over 3 5 8 578731 15 Cad Cell Detector 700...

Страница 16: ...copy of warranty form 61545 please choose one of the following options 1 Visit our website at www beckettcorp com warranty 2 Email your request to rwb customer service beckettcorp com 3 Write to R W...

Отзывы: