www.becker-international.com
53
1019
Hz
f target input
Target frequency of the setpoint
origin
1020
%
PID actual
Actual value process controller
1021
%
PID target
Process controller setpoint
1022
V
Analogue OUT1
Analogue output 1
1023
W
P intermediate circuit
Intermediate circuit power
1024
V
Analogue IN3
Analogue input 3
1025
V
Analogue IN4
Analogue input 4
1026
V
Analogue OUT2
Analogue output 2
1027
W
P temp. limit
max. power of the temperature
limitation
1028
s
Temp. limit counter
Temperature limitation counter
1030
rpm
n mech. motor
Motor speed
1031
Nm
M motor
Motor torque
1032
W
P motor
Motor rating
1035
W
Ptarget int. calc.
calculated power for the internal
pressure control
1038
hours
Operating hours
1039
1
Power ON counter
1040
kWh
Consumption
1041
1
Status Rel.1 Rel.2
Status of relay 1 and 2
Table 14: Diagnostic parameters
6.
Error detection and removal
DANGER
Mortal danger from to electric shock!
Death or serious injury!
Disconnect the equipment from the voltage supply and protect it against re-activation.
If damaged parts or components need replacing, only replace with original parts.
2 mim
Danger from electric shock and electrical discharge. Wait two minutes (discharge time of the
capacitors) after shut-down
6.1 List of errors and system faults
In case of an error the frequency converter shuts down. The corresponding error numbers can be found in
the flashing code table below (chapter 6.2) or in the PC tool.
i
IMPORTANT INFORMATION
Error messages can only be acknowledged once the error has been remedied!
Error messages can be acknowledged as follows:
digital input (programmable)
via the KombiTool (P1011...1014)
via the MMI (manual control unit)
automatic acknowledgement
switch equipment off and back on
via field bus (CANOpen, Profibus DP, EtherCAT)