www.becker-international.com
52
Parameter /
KT level
Setting / description / comment
205
2 Deactivation delay
(virtual output)
0...99 s
[1]
218-237 3 Technology parameters
(11-30)
-32768...
32768
[0]
separately documented dependent on firmware version
1011
1012
1013
1014
2 Error group 1
Error group 2
Error group 3
Error group 4
0...32768
see chapter 6.2 (error messages)
1038
2 Operating hours
0...32768
hours
1039
2 Power ON counter
0...32768
1040
2 Consumption
0... kWh
Table 13: Parameter overview
5.2 Diagnostic parameters
The following diagnostic parameters can be read via the KombiTool.
Parameter
number
Unit
KombiTool name
► Diagnosis
Description
1000
Hz
f actual
Actual frequency
1001
V
u motor
Motor voltage
1002
A
i motor
Motor current
1003
°C
hybrid temperature
1004
V
ud intermediate circuit
Intermediate circuit voltage
1005
Hz
f target controller
Target frequency of the current
controller
1006
V
u mains
Mains voltage
1007
A
id intermediate circuit
intermediate circuit current
1008
°C
Internal temperature
1011
1
Error group 1
Chapter 6.2
1012
1
Error group 2
Chapter 6.2
1013
1
Error group 3
Chapter 6.2
1014
1
Error group 4
Chapter 6.2
1015
1
Digital IN all
Status of all digital inputs
1016
V
Analogue IN1
Analogue input 1
1017
V
Analogue IN2
Analogue input 2