Parameter /
KT level
Setting / description / comment
156/ 157 2 Function
(digital input 2 / digital input 3)
0...10
[0]
Additional functions for digital inputs 2 and 3
Caution
: Digital inputs 2 and 3 must
not be parametrised with an identical function!
Switching level
: Low < 5V / High > 15V
0 = additional function disabled
1 = change to setpoint origin 2 (P154) + start/stop origin 2 (P155)
2 = change to pressure (0V) / vacuum (24)
3 = Control change (according to P008) (0V) / speed-controlled operation (24V)
4 = change to fixed frequency operating mode
5 = change to emergency operation
Setpoint origin internal potentiometer, release of digital input 1 and speed-controlled
operation
6 = alarm 1
24V: Alarm trigger
FC enters fault, fault indication
7 = alarm 2
24V: Alarm trigger
FC enters fault, fault indication
8 = stop via ramp
9 = immediate stop (zero current)
10 = value from BECKERfunction
158/ 160 2 Input type
(analogue input 3 / analogue input 4)
1; 2
[1]
Change of the analogue inputs between voltage or current input:
1 = voltage input
2 = current input
159/ 161 2 % min. value
(analogue input 3 / analogue input 4)
0...100 %
[0]
Specifies the minimum value of the analogue inputs 3+4 as a percentage of the range
Example:
0
…10V or
0
…20mA
0%
…100%
2
…10V or
4
…20mA
20%
…100%
Note
: % max. value: 100% with 10V / 20mA (z.B. 10V at A
in
stepoint f
max
100Hz)
162
2
Function
(analogue output 2)
P042
163
2
Minimum value
(analogue output 2)
P043
164
2
Maximum value
(analogue output 2)
P080
165/ 171 2 Limit value analogue input 2: Act
ivation threshold
(relay 1 / relay 2)
0...10000
[0]
Activation threshold related to the selected process variable
(specify value in physical units : mA, V (0…20mA / 0…10V))
see parameters 62 / 65 relay function: 54
166/ 172 2 Limit value analogue input 2: De
activation threshold
(relay 1 / relay 2)
0...10000
[0]
Deactivation threshold related to the selected process variable
(specify value in physical units : mA, V (0…20mA / 0…10V))
see parameters 62 / 65 relay function: 54