www.becker-international.com
20
Power connections (VAU 11-22/3)
Fig. 9: Power connections 2
VAU 11-22/3
X1 mains /
X4 motor
The terminals for the supply cable are located inside the frequency converter. The con-
figuration may vary depending on the version.
Wire end sleeves with plastic collars and lugs are recommended.
Torque min. 2.5 Nm / max. 4.5 Nm
Conductor cross section:
rigid min. 0.5 mm² / rigid max. 35 mm²
Conductor cross section, flexible:
min. 0.5 mm² / max. 25 mm²
Conductor cross section, flexible with wire
end sleeves with plastic collar
min. 1 mm²
max. 25 mm²
Conductor cross section, flexible with wire
end sleeves with plastic collar
min. 1.5 mm²
max. 25 mm²
Conductor cross section AWG / kcmil
min 20
max. 2
2 conductors of identical cross section,
rigid
min. 0.5 mm²
max. 6 mm²
2 conductors of identical cross section,
flexible
min. 0.5 mm²
max. 6 mm²
2 conductors of identical cross section,
flexible with AEH without plastic collar
min. 0.5 mm²
max. 4 mm²
2 conductors of identical cross section,
flexible with TWINAEH with plastic collar
min. 0.5 mm²
max. 6 mm²
Length of stripped insulation:
18 mm
AWG according to UL/CUL
min. 20
max. 2
Table 4: Connection X1 and X 4 (VAU 11-22/3)