background image

 

 

 

 

Page 7 of 24

 

5.1

 

Connecting the Beacon Master Station 

To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical 

interference in the system wiring, the use of fire-resistant screened cables is recommended throughout 

the installation. 

 

All wiring should come into the enclosure via the knockouts provided and be fixed tidily to the relevant 

terminals.  

 

Note that correct cable glanding is essential.  Due regard should be paid to any system specifications 

which demand a certain cable type, providing it meets the appropriate national wiring regulations.

  

 

5.2

 

Planning the Wiring 

All system wiring should be installed to meet the appropriate parts of BS5839 Part9:2021 and BS 7671 

(Wiring Regulations).  Other national standards of installation should be adhered to where applicable. 

 

Do not test wiring using an insulation tester (Megger) with any 

equipment connected, as the 500 Volt test voltage will destroy 

these devices. 

 

You must observe local wiring regulations.  Do not run SELV and LV cables in the same enclosure 

without adequate insulation between them. 

 

5.3

 

Cable and Wiring Guidance 

5.3.1

 

Fire Telephone system 

Any system using Type A outstations must use enhanced grade cabling throughout for all wiring, 

including the mains supply to the Beacon Master Station

5.3.2

 

Disabled Refuge EVC System 

For buildings less than 30m in height, or any building with sprinklers fitted, standard grade fire resistant 

cable may be used to wire Type B outstation and the mains supply to the Master Controller; as long as 

the planned evacuation will be completed in 30 minutes.  

If the building is over 30m in height without sprinklers, or where the evacuation will take place over 

multiple stages exceeding 30 minutes, then enhanced grade cables must be used.  

5.3.3

 

Combined Systems 

For systems containing Type A, Type B or Type C outstations, shared cable such as network cables 

must be enhanced grade.   

Cabling to Type A or Type C outstations must be in enhanced grade fire resistant cabling.   

Individual spurs to Type B outstations can be wired in standard grade fire resistant cabling in 

accordance with the wiring guidelines already set out for disabled refuge systems. 

5.3.4

 

“Assist Call” Emergency Assistance Alarm Systems 

All installations must conform to Building Regulations Approved Document M.  The “Assist Call” is wired 

using 2 core cable, and the “Assist Call” plates can be wired in any order. 

5.4

 

Cabling methods 

There are 3 cabling methods available: 

 

Connection to a Type A or Type C outstation: use 2 core enhanced grade fire resistant cable 

when extending a firefighting telephone system. 

 

Connection to a Type B outstation: use 2 core standard grade fire resistant cable when 

extending a disabled refuge system. 

 

Connection to an “Assist Call” system on a dedicated line requires 2 core 1mm CSA or above 

PVC sheathed. 

 

 

 

 

 

Содержание BM2

Страница 1: ...Installation and Commissioning Manual Beacon BM2 4 8 Master Station...

Страница 2: ...ocedure 12 5 10 Powering down procedure 12 6 Set up procedure 13 6 1 Beacon Master Station Display PCB Dipswitch Settings 13 6 2 Adding a Line Card 14 6 3 Removing a Line card 14 6 4 Adding a Beacon R...

Страница 3: ...Telephones and Disabled Refuge Points are required 1 2 Suitability Fire telephone systems are recommended for all public buildings and multi story buildings over four floors by BS9999 Disabled Refuge...

Страница 4: ...g to a breaker clearly marked EVCS DO NOT TURN OFF If the Beacon Master Station and the Beacon Repeater Station are distributed around a site it is essential that both Beacon Stations are on the same...

Страница 5: ...1 number 2 5mm AF Hex Key o 1 number door handle key o End of Line EoL Resistors 2 per line card Use the 2 5mm AF Hex Key supplied to open the right hand front cover Verify the following items are pre...

Страница 6: ...slotted entries with a dedicated mains supply entry at the rear If a knockout is removed by mistake fill the hole with a good quality cable gland Unused knockouts must be left unopened to comply with...

Страница 7: ...ge EVC System For buildings less than 30m in height or any building with sprinklers fitted standard grade fire resistant cable may be used to wire Type B outstation and the mains supply to the Master...

Страница 8: ...Page 8 of 24 5 4 1 Beacon Master Station The wiring for a Beacon Master Station is shown in the schematic below...

Страница 9: ...stem has to be wired as a ring with each outstation connected via a radial circuit to either the Master Station or Repeater Station as shown in the schematic below This ensures that the any single cab...

Страница 10: ...g batteries Power Up Procedure Always apply mains power before connecting batteries When connecting batteries always connect the Positive Red terminal first Power Down Procedure Disconnect the batteri...

Страница 11: ...terminal block in the controller and the earth connection in the metal back box if a plastic back box is used cut the earth back and insulate at the outstation 5 7 3 ACA Accessible Toilet Kit The BAKI...

Страница 12: ...Type B outstations automatically time out after approximately 30 minutes It is advised that this feature is not used as the system should always be available not just during an evacuation If the feat...

Страница 13: ...B 6 1 BM2 4 8 Master Station Display PCB Dipswitch Settings 1 2 3 4 5 6 7 8 Line 1 2 Line 3 4 Line 5 6 Line 7 8 Net In Net Out Network Reserved Remarks Line card 1 fitted Line card 1 2 fitted Line car...

Страница 14: ...ne Card from Exchange PCB 4 Set the dipswitch on the Display PCB see 6 1 to disable Line Card monitoring Once the Line Card has been removed the Beacon Master Station may be powered see 5 9 6 4 Adding...

Страница 15: ...0 1 4 0 0 1 0 0 0 36 0 0 1 0 0 1 5 1 0 1 0 0 0 37 1 0 1 0 0 1 6 0 1 1 0 0 0 38 0 1 1 0 0 1 7 1 1 1 0 0 0 39 1 1 1 0 0 1 8 0 0 0 1 0 0 40 0 0 0 1 0 1 9 1 0 0 1 0 0 41 1 0 0 1 0 1 10 0 1 0 1 0 0 42 0 1...

Страница 16: ...In not configured Green Solid Net In healthy Yellow Flashing Net In fault 6 Blank Net Out not configured Green Solid Net Out healthy Yellow Flashing Net Out fault 7 Green Solid Display Processor Heal...

Страница 17: ...is fitted and tested Line 3 Red Blue to indicate a type B outstation and an Assist Call system are fitted and tested Line 4 Solid Magenta to indicate that no outstation has been tested Press zone butt...

Страница 18: ...line is now connected and a conversation can take place 8 2 Making a call To make a call lift the Master handset receiver and the User LED will illuminate red Press the zone button for the required ou...

Страница 19: ...during the acknowledge phase indicates to the WC user that help is on the way 8 7 Accepting Faults Before accepting faults the fault must be noted in the log book along with the time the fault was re...

Страница 20: ...d Flashing Red Green Call on hold Solid Yellow Master handset short circuit Solid White Call connected on remote master station 9 4 Zone indicator summary Zone Indicator Status User Indicator Status B...

Страница 21: ...tify feature has been included Select line identify mode and visit each outstation and listen for the corresponding number of rings This should correspond with the line number i e 2 rings would be lin...

Страница 22: ...ated in the centre above the display PCB the outstation zone template can be inserted here The template is in Word format and can be down loaded at www espuk com This can be completed printed out and...

Страница 23: ...Page 23 of 24 Notes...

Страница 24: ...In use volt free 30Vdc 1A Controls Number and type 8 push button zone keys Indication Number and type 8x RGB Line indicators 3x PSU Status Indicators 1 x CPU Fault Indicators 1x General Fault Indicat...

Отзывы: