background image

 

 

 

Page 24 of 24

 

13.

 

Technical Specification 

Product Code 

BM2/4/8 

Power Supply and Charger 

 

 

AC Input 

- 10% 50/60Hz 

 

Internal power supply 

12Vdc nominal 

 

Supply and battery 

Monitored open, Short, Fuses 

 

Protection 

Deep discharge, Short, Thermals 

 

Temperature compensation 

Yes 

 

Battery information 

Space for Up to 1x 12V 7AH VRSLA 

 

Mains fuse 

1A HRC(T) 

 

Battery fuse 

Self Resetting PTC 

 

Max charge current 

500mA 

Inputs 

 

 

Number of lines 

Between 2 and 8 

 

Remote enable 

Short to use 

 

End of line monitoring 

10K

Ω

 0.6watt resistor 

Relay outputs 

 

 

Number and type 

2: Fault and In use, volt free 30Vdc 1A 

Controls 

 

 

Number and type 

8 push button zone keys 

Indication 

 

 

Number and type 

8x RGB Line indicators 

3x PSU Status Indicators 

1 x CPU Fault Indicators 

1x General Fault Indicator 

1x RGB Mode Indicator 

1x User Status Indicator 

Enclosure Details 

 

 

Back box finish 

RAL 7035 Grey 

 

Dimensions 

350 x 300 x 95 

 

Entries 

14 knockouts top, 2x rear slots 

 

Flush Cutout 

352 x 302 x 85 deep 

 

 

 

 

 

 

 

For more product information please visit www.espuk.com

E&OE - Errors and omissions excepted.K21

Elite Security Products UK, Unit 7 Target Park, Shawbank Road, Lakeside, Redditch, Worcestershire, B98 8YN 

Tel +44(0)1527 515 150, Fax +44(0)1527 150 143; Email [email protected]

Registered in England Number Company Registration No: 02769392, VAT Registration GB614686525

Содержание BM2

Страница 1: ...Installation and Commissioning Manual Beacon BM2 4 8 Master Station...

Страница 2: ...ocedure 12 5 10 Powering down procedure 12 6 Set up procedure 13 6 1 Beacon Master Station Display PCB Dipswitch Settings 13 6 2 Adding a Line Card 14 6 3 Removing a Line card 14 6 4 Adding a Beacon R...

Страница 3: ...Telephones and Disabled Refuge Points are required 1 2 Suitability Fire telephone systems are recommended for all public buildings and multi story buildings over four floors by BS9999 Disabled Refuge...

Страница 4: ...g to a breaker clearly marked EVCS DO NOT TURN OFF If the Beacon Master Station and the Beacon Repeater Station are distributed around a site it is essential that both Beacon Stations are on the same...

Страница 5: ...1 number 2 5mm AF Hex Key o 1 number door handle key o End of Line EoL Resistors 2 per line card Use the 2 5mm AF Hex Key supplied to open the right hand front cover Verify the following items are pre...

Страница 6: ...slotted entries with a dedicated mains supply entry at the rear If a knockout is removed by mistake fill the hole with a good quality cable gland Unused knockouts must be left unopened to comply with...

Страница 7: ...ge EVC System For buildings less than 30m in height or any building with sprinklers fitted standard grade fire resistant cable may be used to wire Type B outstation and the mains supply to the Master...

Страница 8: ...Page 8 of 24 5 4 1 Beacon Master Station The wiring for a Beacon Master Station is shown in the schematic below...

Страница 9: ...stem has to be wired as a ring with each outstation connected via a radial circuit to either the Master Station or Repeater Station as shown in the schematic below This ensures that the any single cab...

Страница 10: ...g batteries Power Up Procedure Always apply mains power before connecting batteries When connecting batteries always connect the Positive Red terminal first Power Down Procedure Disconnect the batteri...

Страница 11: ...terminal block in the controller and the earth connection in the metal back box if a plastic back box is used cut the earth back and insulate at the outstation 5 7 3 ACA Accessible Toilet Kit The BAKI...

Страница 12: ...Type B outstations automatically time out after approximately 30 minutes It is advised that this feature is not used as the system should always be available not just during an evacuation If the feat...

Страница 13: ...B 6 1 BM2 4 8 Master Station Display PCB Dipswitch Settings 1 2 3 4 5 6 7 8 Line 1 2 Line 3 4 Line 5 6 Line 7 8 Net In Net Out Network Reserved Remarks Line card 1 fitted Line card 1 2 fitted Line car...

Страница 14: ...ne Card from Exchange PCB 4 Set the dipswitch on the Display PCB see 6 1 to disable Line Card monitoring Once the Line Card has been removed the Beacon Master Station may be powered see 5 9 6 4 Adding...

Страница 15: ...0 1 4 0 0 1 0 0 0 36 0 0 1 0 0 1 5 1 0 1 0 0 0 37 1 0 1 0 0 1 6 0 1 1 0 0 0 38 0 1 1 0 0 1 7 1 1 1 0 0 0 39 1 1 1 0 0 1 8 0 0 0 1 0 0 40 0 0 0 1 0 1 9 1 0 0 1 0 0 41 1 0 0 1 0 1 10 0 1 0 1 0 0 42 0 1...

Страница 16: ...In not configured Green Solid Net In healthy Yellow Flashing Net In fault 6 Blank Net Out not configured Green Solid Net Out healthy Yellow Flashing Net Out fault 7 Green Solid Display Processor Heal...

Страница 17: ...is fitted and tested Line 3 Red Blue to indicate a type B outstation and an Assist Call system are fitted and tested Line 4 Solid Magenta to indicate that no outstation has been tested Press zone butt...

Страница 18: ...line is now connected and a conversation can take place 8 2 Making a call To make a call lift the Master handset receiver and the User LED will illuminate red Press the zone button for the required ou...

Страница 19: ...during the acknowledge phase indicates to the WC user that help is on the way 8 7 Accepting Faults Before accepting faults the fault must be noted in the log book along with the time the fault was re...

Страница 20: ...d Flashing Red Green Call on hold Solid Yellow Master handset short circuit Solid White Call connected on remote master station 9 4 Zone indicator summary Zone Indicator Status User Indicator Status B...

Страница 21: ...tify feature has been included Select line identify mode and visit each outstation and listen for the corresponding number of rings This should correspond with the line number i e 2 rings would be lin...

Страница 22: ...ated in the centre above the display PCB the outstation zone template can be inserted here The template is in Word format and can be down loaded at www espuk com This can be completed printed out and...

Страница 23: ...Page 23 of 24 Notes...

Страница 24: ...In use volt free 30Vdc 1A Controls Number and type 8 push button zone keys Indication Number and type 8x RGB Line indicators 3x PSU Status Indicators 1 x CPU Fault Indicators 1x General Fault Indicat...

Отзывы: