background image

                    

 75.1041.08 LO21U 20150708 

 

Page 4 of 5 

SET-UP 
INSTRUCTIONS 

 
 
 

The  following  instructions  pertain  to  the  setup  procedures  and  the  related  indications  that  should  be  observed. 

Immediately following each step, is a corrective action to perform if the step does not pass: 
 
1. 

Set the On-Off-Hold Open switch to the OFF position. If a switch is not available, unplug the activating device for 
the door. 

 
2. 

To  begin  the  set-up,  apply  power  to  the  door  system,  to  the  LO-21U  module,  and  to  the  Bodyguard.  The 
Bodyguard shall immediately begin flashing green to indicate a setup for the closed door position.  

q

  If the Bodyguard does not begin flashing green, check to insure it is receiving the correct power at inputs 

1 & 2 at the 7-position terminal at the left side of the Bodyguard. Correct as necessary. 

 
3. 

Do not enter into the field of detection while the Bodyguard is setting up. After approximately 6 seconds, the green 
LED will expire. 

 
4. 

Activate the door to the open position with the On-Off-Hold Open switch, or by jumpering the activate circuit. The 
Bodyguard shall begin flashing green again while it is learning the “door open” set-up. Again, approx. 6 seconds of 
un-interruption  will  allow  a  setup  to  complete.  Once  complete,  the  door  should  begin  to  close  if  activation  is 
removed. Place the On-Off-Hold Open switch to the On position. Normal operation thereafter. 

q

  If the Bodyguard does not begin flashing green when the door reaches full open, improper voltage may 

exist on terminals 6 & 7 of the Bodyguard. Perform following: 

Ø

  Using  a  BEA  remote  control,  and  with  the  door  in  the  open  position,  unlock  the  Bodyguard,  then 

press the Magic Wand key and then the number 2. This will force a setup for the open door position. 
If the green LED does not begin flashing, unplug the 7-position connector at the Bodyguard.  

Ø

  Use a multi-meter (set to a DC voltage scale) to test the voltage at terminal 6 & 7. Place the positive 

probe on terminal 7 and the negative probe on terminal 6. There should be approximately 12 Volts 
DC. If voltage is 0 volts, check the white and red/white striped wires from the connector back to the 
LO-21U for any breaks.  

Ø

  If wiring is good, check the voltage at the red and black wires on the LO-21U. Using a multi-meter, 

place the positive probe on the red wire, and the negative probe on the black wire. Voltage should 
not be less than 6 volts DC. If it is less, try increasing the stall voltage at the door control. If voltage 
is 0 volts, make sure there is a good connection on the red and black wires. Also make sure the LO-
21U has the proper input voltage at the orange and brown wires. 

 

5. 

Once the Bodyguard is functioning correctly with regard to the open and closed door setup, walk testing may begin. 

q

  Do NOT proceed with walk-test until the Bodyguard is functioning correctly. 

 

6. 

The LO-21U has two LED’s to indicate what function it is performing.  When the door is closed and someone steps 
into the detection zone of the Bodyguard, the illumination of the 

red LED

 on the LO-21U will indicate that the LO-

21U is triggering the 

safety circuit

.  Therefore, the door will remain closed until the Bodyguard zone is clear. The 

red LED will expire on the LO-21U and on the Bodyguard will shut off when the detection zone is clear.  With the 
door  in  the  closed  position,  stand  in  the  Bodyguard  detection  field  and  have  someone  activate  the  door  (Eagle, 
push  plate,  etc.).  The  door  should  not  open.  Clear  the  detection  field  of  the  Bodyguard,  while  keeping  the  door 
activated. The door should open thereafter. 

q

  If the red led comes on at the Bodyguard, but not at the LO-21U, check to insure good wiring on the gray 

and violet wires between the Bodyguard and the LO-21U. 

q

  If the red LED comes on at the Bodyguard and the LO-21U, but the door has no safety, check the green 

and yellow wires between the LO-21U and the door control. If connections are good, jumper the common 
and safety terminals at the door control, then activate the door to insure that the safety function is ok. 

 
7. 

Once the Bodyguard zone is clear and the door has been activated, it will open and remain open as long as there 
is activation, or until door control and sensor hold-times have expired.  If someone steps into the Bodyguard zone 
when the door is open, the illumination of the

 green LED

 will indicate that the LO-21U is triggering the 

activation 

circuitry

 of the door, thus holding the door open for as long as someone is in the Bodyguard detection pattern. 

q

  If the red led comes on at the Bodyguard, but not at the LO-21U, check to insure good wiring on the gray 

and violet wires between the Bodyguard and the LO-21U. 

q

  If the red LED comes on at the Bodyguard and the green LED comes on at the LO-21U, but the door 

does not hold open when the Bodyguard is in detection, check the blue and green wires between the LO-
21U and the door controls activation circuit.  

q

  Reverse the red and black wires at the LO-21U and try Step 7 again. 

q

  If all steps are Ok, LO-21U may be faulty. Replace as necessary. 

 
 

 
RED LED 
Bodyguard’s output is 
Applied to the safety circuit 
 
GREEN LED 
Bodyguard’s output is  
Applied to the activation circuit

 

Set the dipswitches according to the chart 
below  to  achieve  the  desired  lock  out 
time delay.   

 
 

OBSOLETE

Содержание LO-21U

Страница 1: ... 24 VDC Operating frequency 4 MHz Microprocessor Power consumption 10 mA at rest 50 mA Maximum Output 2 SPST Relays Maximum voltage Relay contacts 60 VDC 120 VAC Maximum current Relay contacts 2A DC 0 5 A AC Shut off all power going to the header before attempting any wiring procedures Maintain a clean safe environment when working in public areas Constantly be aware of pedestrian traffic around t...

Страница 2: ... DC Green Door Control Common Blue Door Control Activate Yellow Door Control Safety 1 The dipswitches are located at the end of the LO 21U opposite of the wire connection terminal There are 8 positions available Dipswitch designations are as follows BLANK 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 BLANK 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 115 VAC BODYGUARD ...

Страница 3: ... 0 seconds 1 second 2 Time Delay 2 sec value 0 seconds 2 second 3 Time Delay 4 sec value 0 seconds 4 second 4 Time Delay 8 sec value 0 seconds 8 second 5 Time Delay 16 sec value 0 seconds 16 second 6 Voltage switching device Voltage source is other than motor Motor Voltage 7 Safety circuit logic used with DS 8 7 OFF 8 ON N O Safety Circuit 8 Safety circuit logic used with DS 7 7 ON 8 OFF N C Safet...

Страница 4: ...wires Also make sure the LO 21U has the proper input voltage at the orange and brown wires 5 Once the Bodyguard is functioning correctly with regard to the open and closed door setup walk testing may begin q Do NOT proceed with walk test until the Bodyguard is functioning correctly 6 The LO 21U has two LED s to indicate what function it is performing When the door is closed and someone steps into ...

Страница 5: ...62 from 7am 5pm For after hours call East Coast 1 866 836 1863 or 1 800 407 4545 Mid West 1 888 308 8843 West Coast 1 888 419 2564 DO NOT leave any problem unresolved If you must wait for the following workday to call B E A leave the door inoperable until satisfactory repairs can be made NEVER sacrifice the safe operation of the automatic door or gate for an incomplete solution Web www beasensors ...

Отзывы: