28
–
2-relay seq door position
AVAILABLE PARAMETERS:
h1
- relay 1 hold time
h2
- relay 2 hold time
d1
- delay between relays 1 & 2
h1
must be greater than
d1
when using an electric lock
1. Trigger INPUT 1 or 'WET'.
• RELAY 1 will close and
hold for time
h1
.
• RELAY 2 will close after
time delay
d1
and hold
for time
h2
.
FUNCTION
28
NOTE: INPUT 2
allows the delay to run when the
contact is open but triggers RELAY
2 immediately when the contact
is closed.
AVAILABLE PARAMETERS:
h1
- relay 1 hold time
h2
- relay 2 hold time
d1
- delay between relays 1 & 2
rL
- reverse logic
h1
must be greater than
d1
when using an electric lock
1. Trigger INPUT 1 or 'WET'.
• RELAY 1 will close and
hold for time
h1
.
• RELAY 2 will close after
time delay
d1
and hold
for time
h2
.
29
–
deactivation timer
FUNCTION
29
NOTE:
INPUT 2 deactivates RELAY 1
once INPUT 2 is opened (and
after the sequence has run).
INPUT 2 allows the delay to run
when the contact is open, but
triggers RELAY 2 immediately
when the contact is closed.
INPUT 3 disables the sequence.
PROGRAMMING PARAMETERS (cont)