200646_01 

 

 

Push the firebox in to place and seal into the fireplace opening using the double-sided tape 
supplied or alternatively a water based mastic sealant. 

 

NOTE:  If  installing  without  the  fireplace  in  position  when  determining  the  length  of  flue  spigot 

required allowance must be made for the depth of infill panel being used. 

 

 

IMPORTANT:  WHERE  THE  FLUE  DUCT  PASSES  THROUGH  A  CAVITY  WALL,  IT  IS 
RECOMMENDED  THAT  IT  SHOULD  BE  INSULATED  ALL  ROUND WITH  A  MATERIAL 
SUCH  AS  ROCKWOOL.  THIS  WILL  PREVENT  ANY  EXISTING  WALL  INSULATION 
MATERIAL FROM COMING IN TO CONTACT WITH THE FLUE DUCT. (SEE FIGURE 4)  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

 

4

THE GAS SUPPLY. 

1. 

The gas supply should be routed from the meter or cylinder and reduced to 8mm-diameter 
pipe as close to the appliance as possible. 

2. 

Route the 8mm pipe into the fire recess and through the knock out at the rear of the 
firebox. Care should be taken to sleeve the pipe when passing through masonry. 

3. 

Connect the pipe to the burner at the isolation/pressure test elbow using the nut and olive 
provided.  

When routing the gas supply pipe to the burner unit , soldered fittings must not be used 
under the burner tray. 

5

INSTALLING THE FAN BOX - RECESSED UNIT 

Cut  a  rectangular  hole  in  the  external  leaf  of  the  brick  wall  to  the  dimensions  shown  in 
Figure 5.  Use the pilot hole drilled earlier (Para. 3.2) as the centre position of the flue duct. 

Remove the fan box cover.  Remove the 2 lower self tapping screws and loosen the 2 pan 
head screws located in the key hole slots (See Figure 6) which hold the fan carrier to the 
wall box and lift away the fan carrier assembly, together with it's gasket and place to one 
side. 

Feed  the  fan  cable  through  the  hole  in  the  brickwork  and  leave  a  short  length  of  cable 
'hanging' in the opening made for the fan unit. 

  

NOTE:  CARE  MUST  BE  TAKEN  NOT  TO  DAMAGE  THE  TWO  PLASTIC 
CONNECTORS  FITTED  TO  THE  CABLE  WHEN  PULLING  THEM  THROUGH  THE 

 

FIGURE 4 

Содержание EARDF16NG

Страница 1: ...TE GARDE Radiant HE Power flue gas fire MODEL NUMBERS EARDF16NG EARDF16P INSTALLATION SERVICING AND USER INSTRUCTIONS THESE INSTRUCTIONS MUST REMAIN WITH THE USER 0120 THIS APPLIANCE MEETS THE REQUIRE...

Страница 2: ...your fire 16 28 Assembling the fire and laying ceramic coals pebbles 17 Guarantee 17 Installation Service Record 19 Important Notes Please read before undertaking the installation 1 This is not a Do i...

Страница 3: ...in a separate box which is inside the adapter box carton Any extra ducting elbows and fitting components will be packed in a separate carton 1 APPLIANCE DATA EARDF16NG EARDF16P GAS TYPE NATURAL GAS P...

Страница 4: ...lage test there is no requirement for purpose made ventilation into the room containing the appliance See Section 14 5 FLUE TERMINAL POSITION The minimum distances permissible from the flue terminal t...

Страница 5: ...ed the floor of the recess to the level of the hearth to allow accurate fitting of the firebox 4 Cut a hole through the cavity wall to accept the flue duct The centre line for the duct is 483mm 19 abo...

Страница 6: ...Care should be taken to sleeve the pipe when passing through masonry 3 Connect the pipe to the burner at the isolation pressure test elbow using the nut and olive provided 4 When routing the gas supp...

Страница 7: ...oint where the edge of the gasket is level with the inner flue duct 7 Secure the cable gland to its bracket on the fan carrier See Figure 7 and then connect the power cable using the Molex snap connec...

Страница 8: ...ce the spacer against the wall ensuring it is correctly aligned with the flue duct and mark the position of the four fixing holes on the wall See Figure 7 Drill and plug the wall at these positions Ch...

Страница 9: ...the underside of the burner unit to the mating plug on the switch panel of the fire See Figure 9 4 Place the burner tray in position within the firebox The tabs on either side of the rear of the burne...

Страница 10: ...itch 2 Connect the electrical mains supply to the appliance turn on the gas supply and switch on the fire 3 From outside block the flue opening on the fan unit Initially the fan should be heard to spe...

Страница 11: ...est firmly against the rear ceramic ROW C Place five large pebbles along the top of the raised slotted part of the base ceramic at the front of the burner These pebbles should be positioned so that th...

Страница 12: ...he controller will shut down the whole system In this event the fire will go out and will only relight if the ON switch on the switch panel is pressed When first switched on the fan may pulse between...

Страница 13: ...ft brush 4 Badly damaged coals pebbles should be replaced Replacement fuel pieces are available from our stockists 5 Check that there is no impairment to the electrode spark or pilot burner 6 Check th...

Страница 14: ...ith an electronic control unit that monitors the behaviour of the fan during the start up procedure and in the event of high gusts of wind When the fan is switched on the controller will set it to run...

Страница 15: ...liance is fitted with a flue blockage device that will shut off the appliance in the event of abnormal flue conditions This device is NOT a substitute for an independently mounted carbon monoxide dete...

Страница 16: ...uld light the pilot burner If the pilot does not light try again after a few seconds The pilot may not light at the first attempt Waiting a few seconds gives the spark generator time to recover 5 Once...

Страница 17: ...IRE AND LAYING CERAMICS COALS PEBBLES When laying the ceramics coals pebbles on the burner closely follow the instructions found on pages 11 12 of these instructions Failure to do so will possibly cau...

Страница 18: ...e Signed Comments RECORD OF 4th SERVICE Serviced by CORGI No Service Date Signed Comments RECORD OF 5th SERVICE Serviced by CORGI No Service Date Signed Comments RECORD OF 6th SERVICE Serviced by CORG...

Страница 19: ...19 Be Modern Limited WESTERN APPROACH SOUTH SHIELDS TYNE WEAR NE33 5QZ TEL 0191 4553571 FAX 0191 4565556 Web site www bemodern com Email sales bemodern com THIS BOOKLET CONTAINS 20 PAGES HEPF BM 0606...

Отзывы: