background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

Commission the Fire – Page 5

Check the gas pressure

 (Figs 7 and 11)

(a)

Remove the packing securing the coal bed as follows:

(i)

Slide the glass front panel retaining clamps
sideways.

(ii)

Lift the glass front panel bottom edge out of the
locating channel and carefully remove the glass
front panel.

(iii)

Remove the packing securing the coal bed.

(iv) Carefully remove the coal bed and withdraw it

from the plastic bag.

(v)

Replace the coal bed and glass front panel.

(b)

Remove the pressure test point sealing screw from the
control tap and connect a pressure gauge.

(c)

To light the fire burner:

 Push in and turn the fire

control knob anti-clockwise to the positive stop. The
pilot which can be seen through the lower right hand
gap between the coal should now light. If it fails to light
turn the control knob to the ‘OFF’ position and repeat
until lighting occurs. Continue to hold in the control
knob for a further 15 seconds. Release slowly and the
pilot should stay alight.

CAUTION:  If the pilot does not light or stay alight or if
the pilot flame goes out for any reason turn the control
knob to the ‘OFF’ position and wait for 3 minutes before
attempting to light the pilot again.

(d)

Push in the control knob and turn fully anti-clockwise.
Check that the ignition is satisfactory.

(e)

Check the fire pressure with the control knob turned
fully anti-clockwise. The pressure should be 12.5mbar ±
1.0mbar (5.0 in wg ± 0.4 in wg). No adjustment is
provided on the fire. Turn the control knob to the ‘OFF’
(

) position. Remove the pressure gauge and refit the

pressure test point sealing screw. Turn the fire on full
again and check for gas soundness using a suitable
leak detection fluid.

TEST FOR SPILLAGE

(a)

Check that all four edges of the closure plate are
sealed.

(b)

After fitting the fire ensure that all doors and windows of
the room are closed and they are not opened until the
fire has been checked for clearance of products.

(c)

Light the fire and leave on full rate for 5 minutes.

(d)

The fire should be checked visually for the absence of
spillage by holding a smoke match 50mm (2in) inside
the draught diverter behind the fire ensuring that the
smoke is drawn into the flue outlet (Fig.8). If there is
any doubt repeat the test after a further 10 minutes. If
spillage still persists the chimney may be faulty. The
cause of the fault MUST be identified and corrected
before leaving the fire installed. IF THE FAULT
CANNOT BE CORRECTED, TURN OFF AND
DISCONNECT THE GAS SUPPLY TO THE FIRE -
SEEK EXPERT ADVICE.

(e)

IMPORTANT NOTE: 

If there is a fan in the room or

adjoining room then the spillage test must be repeated
with the fan turned on and any interconnecting doors
between the fan and the appliance left open.

(f)

Remove the control knob.

Содержание Solaire Super

Страница 1: ...heating spares co Tel 0161 620 6677 Please leave these Instructions with the user Baxi Solaire Super Gas Fire Natural Gas Comp No 236216 10 95 Baxi Solaire Super G C No 32 077 36 Installation And Servicing Instructions ...

Страница 2: ...above the fire provided that it does not exceed 150mm 6in deep and is at least 100mm 4in above the top of the fire A clearance of 75mm 3in is required at each side of the fire for access during servicing b Fireplace opening At the height of the flue outlet the fireplace should have a minimum dimension of 100mm 4in from the front face of the opening to the fireplace back brick Fig 3 There must be a...

Страница 3: ...EGULATIONS The mains lead has the billowing specifications 16 0 2mm 3 core PVC covered PVC insulated wire to BS 6500 IMPORTANT Mains lead wires Green and yellow Earth Blue Neutral Brown Live FOR THE MAINS PLUG USE A 3AMP FUSE The appliance is supplied with approximately 3 metres of wire and a mains plug A longer cable may be fitted as follows a Remove the socket and plug from the cable supplied b ...

Страница 4: ...T THE FIRE SEEK EXPERT ADVICE HEARTH FIXING Fireplace or Surround a Fit the fire backing plate to the fire using the M5 x 8mm thread forming screws provided The backing plate may be screwed to the wall for extra support if necessary Fig 6 b Position the fire minus the outer case against the closure plate and determine the position of the gas connection c Adjust the feet to level the fire Fig 7 Che...

Страница 5: ...Check that the ignition is satisfactory e Check the fire pressure with the control knob turned fully anti clockwise The pressure should be 12 5mbar 1 0mbar 5 0 in wg 0 4 in wg No adjustment is provided on the fire Turn the control knob to the OFF position Remove the pressure gauge and refit the pressure test point sealing screw Turn the fire on full again and check for gas soundness using a suitab...

Страница 6: ...entilation hole at the bottom of the closure plate is not covered 1 Remove the outer case for access to all controls a Pull off the control knob b Remove the cover panel under the front of the fire by grasping it firmly by its side edges and pulling forwards c Remove the two case securing screws Fig 7 d Lift the case away from the heat exchanger 2 Remove the glass front panel Fig 10 a Ensure that ...

Страница 7: ...Supplied By www heating spares co Tel 0161 620 6677 Commission the Fire Page 7 ...

Страница 8: ...t panel as described above Remove the coal bed by lifting it carefully away from the Locating pins On re assembly ensure that the coal bed is correctly located over the locating pins BURNER Figs 10 11 and 12 a Remove the glass front and coal bed as described above b Pull back the sleeve and disconnect the electrode lead from the electrode c Disconnect the compression nuts from the injectors d Remo...

Страница 9: ...8 040955 C Knob Gas Tap Control 156 430 234544 D Flame Failure Device Gas Tap 378 916 235335 E Piezo Unit Vernitron 66111 393 734 042941 F Encapsulated Unit Concentric TE 418 384 248 082462 G Injector F11 Cat 18 230 381 879 092133 H Burner Aeromatic Baxi Special 155 949 043210 I Oxy pilot Assembly 350mm SIT OP 9402 378 914 236204 J Lead Electrode 400mm 378 911 236209 K Coal Bed 156 429 235149 L Fi...

Страница 10: ...Supplied By www heating spares co Tel 0161 620 6677 Fault Finding Chart Page 10 11 BAXI SOLAIRE SUPER Gas Type G20 Natural Gas Click here for Helplines ...

Отзывы: