System
Select the solar system required.
Maximum accumulator temperature
Adjust the desired maximum temperature of the accumulator.
Connection temperature for the auxiliary heating
Set the required connection temperature.
Shutdown temperature for the auxiliary heating
Set the required shutdown temperature.
Finalising settings in the commissioning menu
After accessing the last channel in the commissioning menu, a safety
request is displayed to confirm the settings made. To confirm the settings
made, press the central key.
9.3.2
Factory setting values
Tab.16 Factory values
Channel
Meaning
Factory set
ting
SIST
System
1
DT O
Difference in connection temperature
6.0 K
DT F
Difference in shutdown temperature
4.0 K
DT N
Difference in nominal temperature
10.0 K
A MX
Maximum accumulator temperature
60 ºC
AUM
Increase
2 k
CSEG
Collector temperature limit
130 ºC
ORC
Collector cooling option
OFF
OMNC
Minimum threshold collector option
OFF
OAH
Antifreeze option
OFF
OCT
Vacuum tube collector option
OFF
Fig.30
System
1
SIST
SET
BA-0
0
0
0
0
5
9
-0
1
Fig.31
Maximum accumulator temperature
9O
AMAX
SET
o
C
BA-0
0
0
0
0
6
0
-0
1
Fig.32
Connection temperature
4O
CA1O
SET
o
C
BA-0
0
0
0
0
6
1
-0
1
Fig.33
Shutdown temperature
45
CA1F
SET
o
C
BA-0
0
0
0
0
6
2
-0
1
Fig.34
Confirmation
PUSH
OK
SET
BA-0
0
0
0
0
6
3
-0
1