InstructIons pertaInInG to the InstaLLer
13. fIttIngs present In the paCkagIng
• template
• gas cock (2)
• inlet water tap with filter (3)
• heating system delivery cock (1)
• heating system return cock (4)
• washers
• telescopic tubes
• screws and wall plugs
14. InstallatIon of flue
Figure 8
0301_1008
4
3
2
1
We guarantee ease and flexibility of installation for a gas-fired forced draft boiler thanks to the fittings and fixtures supplied
(described below).
The boiler is especially designed for connection to an exhaust flue / air ducting, with either coaxial, vertical or horizontal
terminal. By means of a splitting kit a two-pipe system may also be installed.
In case exhaust and intake flues not supplied by
BAXI S.p.A.
have been installed, these must be certified for the
type of use and must have a maximum pressure drop of 100 pa.
010828_0200
c
33
c
33
c
13
c
13
c
43
c
53
c
83
Figure 9
Warnings
for the following types of installation:
c
13
, c
33
The terminals for the split flue must be provided for within a square
with 50 cm sides. Detailed instructions are given together with
each accessory
c
53
The terminals for combustion air intake and for the expulsion of
combustion products must not be provided for on opposite walls
of the building.
c
6
3
The maximum pressure drop of the ducts must not exceed 100
Pa. The ducts must be certified for the specific use and for a
temperature of over 100°C. The chimney flue must be certified
in accordance with the prEN 1856-1 Regulation.
c
43
, c
83
The chimney or flue used must be suitable for the use.